2905640
SKU
PHX2905640
MPN
VAL-MB-T1/T2 1500DC-PV/2+V-FM
Weight
0.531 kg
Series VAL-MB-T
VAL-MB-T1/T2 1500DC-PV/2+V-FM - Lightning/surge arrester type 1/2
Lightning current arrester/surge protective device for 2-pos. isolated and grounded 1,500 V DC PV systems, for DIN rail mounting, with remote indication contact, temperature-monitored protective elements, status message on the module.
- Space-saving installation, thanks to the compact design
- Double terminal block for safe and easy equipotential bonding connection
- Screw shafts with raised domes to ensure safe working
- Main connections with extended insertion funnels for increased resistance to creepage
- Visual display for checking the status directly on the device
- Plug-in signal connection for remote status signaling
Technical Specifications
General
| Note | The product is also suitable for use in photovoltaic systems with max. short-circuit current ISCPV = 15 kA (in accordance with EN 50539-11: 2013). |
Product properties
| Product family | VALVETRAB MB |
| IEC test classification | PV I / II |
| IEC test classification | PV T1 / T2 |
| EN type | T1 / T2 |
| IEC power supply system | DC |
| Type | DIN rail module, one-piece |
| Installation location | Interior |
| Installation location of the disconnect device | Internal |
| Accessibility | Accessible |
| Connection configuration | Y configuration |
| SPD failure behavior | OCFM (Open-Circuit Failure Mode) |
| Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics
| Pollution degree | 2 |
Indicator/remote signaling
| Connection name | Remote fault indicator contact |
| Switching function | Changeover contact |
| Operating Voltage | 5 V AC ... 250 V AC |
| Operating Voltage | 5 V DC ... 30 V DC |
| Operating current | 5 mA AC ... 1.5 A AC |
| Operating current | 5 mA DC ... 1 A DC |
Connection data
| Connection Method | Screw connection |
| Screw thread | M5 |
| Tightening torque | 3 Nm |
| Stripping length | 16 mm |
| Conductor cross section flexible | 2.5 mm² ... 35 mm² |
| Conductor cross section AWG | 14 ... 2 |
Remote fault indicator contact
| Connection Method | Screw connection |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Dimensions
| Width | 71.2 mm |
| Height | 120 mm |
| Depth | 65.5 mm (incl. DIN rail 7.5 mm) |
| Horizontal pitch | 4 Div. |
Material specifications
| Color | gray (RAL 7042) |
| Color | gray (RAL 7042) |
| Flammability rating according to UL 94 | V-0 |
| Insulating material | PA 6.6 |
| Insulating material | PBT |
| Housing Material | PA 6.6 |
Mechanical data
| Open side panel | No |
Protective circuit
| Mode of protection | (L+) - (L-) |
| Mode of protection | (L+) - PE |
| Mode of protection | (L-) - PE |
| Direction of action | (L+)-PE & (L-)-PE & (L+)-(L-) |
| Rated load current IL | 50 A |
| Residual current IPE | ≤ 100 µA DC |
| Residual current IPE | ≤ 540 µA AC |
| Standby power consumption PC | ≤ 150.00 mVA |
| Nominal discharge current In (8/20) µs | 20 kA |
| Maximum discharge current Imax (8/20) µs | 40 kA |
| Impulse discharge current (10/350) µs, charge | 3.125 As |
| Impulse discharge current (10/350) µs, specific energy | 9.77 kJ/Ω |
| Impulse discharge current (10/350) µs, peak value limp | 6.25 kA |
| Total discharge current Itotal (8/20) µs | 40 kA |
| Total discharge current Itotal (10/350) µs | 12.5 kA |
| Voltage protection level Up | ≤ 4.5 kV |
| Residual voltage Ures | ≤ 4.5 kV (at In) |
| Residual voltage Ures | ≤ 3.3 kV (at 3 kA) |
| Residual voltage Ures | ≤ 3.6 kV (at 6.25 kA) |
| Residual voltage Ures | ≤ 3.8 kV (at 10 kA) |
| Residual voltage Ures | ≤ 4.2 kV (at 15 kA) |
| Residual voltage Ures | ≤ 5.4 kV (at 40 kA) |
| Response time tA | ≤ 25 ns |
PV protective circuit
| Connection configuration | Y configuration |
| SPD failure behavior | OCFM (Open-Circuit Failure Mode) |
Protective circuit DC voltage side (DC)
| Open circuit voltage UOCSTC | ≤ 1250 V DC |
| Maximum discharge current Imax (8/20) µs | 40 kA |
| Response time tA | ≤ 25 ns |
| Impulse discharge current (10/350) µs, charge | 3.125 As |
| Impulse discharge current (10/350) µs, specific energy | 9.77 kJ/Ω |
| Impulse discharge current (10/350) µs, peak value limp | 6.25 kA |
| Total discharge current Itotal (8/20) µs | 40 kA |
| Total discharge current Itotal (10/350) µs | 12.5 kA |
| Insulation resistance Riso | > 5 GΩ (at 500 V DC) |
| Nominal discharge current In (8/20) µs | 20 kA |
| Rated load current IL | 50 A |
| Continuous operating current ICPV | < 100 µA |
| Maximum continuous operating voltage UCPV | 1500 V DC |
| Short-circuit current rating ISCPV | 2000 A |
| Residual voltage Ures | ≤ 4.5 kV (at In) |
| Residual voltage Ures | ≤ 3.3 kV (at 3 kA) |
| Residual voltage Ures | ≤ 3.6 kV (at 6.25 kA) |
| Residual voltage Ures | ≤ 3.8 kV (at 10 kA) |
| Residual voltage Ures | ≤ 4.2 kV (at 15 kA) |
| Residual voltage Ures | ≤ 5.4 kV (at 40 kA) |
| Residual current IPE | ≤ 100 µA DC |
| Residual current IPE | ≤ 540 µA AC |
| Voltage protection level Up | ≤ 4.5 kV |
| Standby power consumption PC | ≤ 150.00 mVA |
Ambient conditions
| Degree of Protection | IP20 (only when all terminal points are used) |
| Ambient Temperature (Operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 6000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 50g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (Operation) | 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
Standards and Regulations
| Standards/specifications | EN 61643-31 |
| Note | 2019 |
| Standards/specifications | IEC 61643-31 |
| Note | 2018 |
Mounting
| Mounting Type | DIN rail: 35 mm |
Accessories
Why Proax for Phoenix Contact 2905640?
Proax is an authorized distributor of Phoenix Contact 2905640 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended