Official Distributor
SKU
MPN
VAL-MB-T2 1500DC-PV/2+V-FM
Weight
0.389 kg
Series VAL-MB-T
VAL-MB-T2 1500DC-PV/2+V-FM - Type 2 surge arrester
Surge protective device for 2-pos. isolated and grounded 1,500 V DC PV voltage systems, for DIN rail mounting, with remote indication contact, temperature-monitored protective elements, status message on the module.
- Space-saving installation, thanks to the compact design
- Double terminal block for safe and easy equipotential bonding connection
- Screw shafts with raised domes to ensure safe working
- Main connections with extended insertion funnels for increased resistance to creepage
- Visual display for checking the status directly on the device
- Plug-in signal connection for remote status signaling
Technical Specifications
General
Note | The product is also suitable for use in photovoltaic systems with max. short-circuit current ISCPV = 15 kA (in accordance with EN 50539-11: 2013). |
Product properties
Product family | VALVETRAB MB |
IEC test classification | PV II |
IEC test classification | PV T2 |
EN type | T2 |
IEC power supply system | DC |
Type | DIN rail module, one-piece |
Installation location | Interior |
Installation location of the disconnect device | Internal |
Accessibility | Accessible |
Connection configuration | Y configuration |
SPD failure behavior | OCFM (Open-Circuit Failure Mode) |
Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics
Pollution degree | 2 |
Indicator/remote signaling
Connection name | Remote fault indicator contact |
Switching function | Changeover contact |
Operating Voltage | 5 V AC ... 250 V AC |
Operating Voltage | 5 V DC ... 30 V DC |
Operating current | 5 mA AC ... 1.5 A AC |
Operating current | 5 mA DC ... 1 A DC |
Connection data
Connection Method | Screw connection |
Screw thread | M5 |
Tightening torque | 3 Nm |
Stripping length | 16 mm |
Conductor cross section flexible | 2.5 mm² ... 35 mm² |
Conductor cross section AWG | 14 ... 2 |
Remote fault indicator contact
Connection Method | Screw connection |
Screw thread | M2 |
Tightening torque | 0.25 Nm |
Stripping length | 7 mm |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Dimensions
Width | 71.2 mm |
Height | 120 mm |
Depth | 65.5 mm (incl. DIN rail 7.5 mm) |
Horizontal pitch | 4 Div. |
Material specifications
Color | gray (RAL 7042) |
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V-0 |
Insulating material | PA 6.6 |
Insulating material | PBT |
Housing Material | PA 6.6 |
Mechanical data
Open side panel | No |
Protective circuit
Mode of protection | (L+) - (L-) |
Mode of protection | (L+) - PE |
Mode of protection | (L-) - PE |
Direction of action | (L+)-PE & (L-)-PE & (L+)-(L-) |
Rated load current IL | 50 A |
Residual current IPE | ≤ 55 µA DC |
Residual current IPE | ≤ 430 µA AC |
Standby power consumption PC | ≤ 85.00 mVA |
Nominal discharge current In (8/20) µs | 20 kA |
Maximum discharge current Imax (8/20) µs | 40 kA |
Total discharge current Itotal (8/20) µs | 40 kA |
Voltage protection level Up | ≤ 4.5 kV |
Residual voltage Ures | ≤ 4.5 kV (at In) |
Residual voltage Ures | ≤ 3.3 kV (at 3 kA) |
Residual voltage Ures | ≤ 3.6 kV (at 6.25 kA) |
Residual voltage Ures | ≤ 3.8 kV (at 10 kA) |
Residual voltage Ures | ≤ 4.2 kV (at 15 kA) |
Residual voltage Ures | ≤ 5.4 kV (at 40 kA) |
Response time tA | ≤ 25 ns |
PV protective circuit
Connection configuration | Y configuration |
SPD failure behavior | OCFM (Open-Circuit Failure Mode) |
Protective circuit DC voltage side (DC)
Open circuit voltage UOCSTC | ≤ 1250 V DC |
Maximum discharge current Imax (8/20) µs | 40 kA |
Response time tA | ≤ 25 ns |
Total discharge current Itotal (8/20) µs | 40 kA |
Insulation resistance Riso | > 5 GΩ (at 500 V DC) |
Nominal discharge current In (8/20) µs | 20 kA |
Rated load current IL | 50 A |
Continuous operating current ICPV | < 55 µA |
Maximum continuous operating voltage UCPV | 1500 V DC |
Short-circuit current rating ISCPV | 2000 A |
Residual voltage Ures | ≤ 4.5 kV (at In) |
Residual voltage Ures | ≤ 3.3 kV (at 3 kA) |
Residual voltage Ures | ≤ 3.6 kV (at 6.25 kA) |
Residual voltage Ures | ≤ 3.8 kV (at 10 kA) |
Residual voltage Ures | ≤ 4.2 kV (at 15 kA) |
Residual voltage Ures | ≤ 5.4 kV (at 40 kA) |
Residual current IPE | ≤ 55 µA DC |
Residual current IPE | ≤ 430 µA AC |
Voltage protection level Up | ≤ 4.5 kV |
Standby power consumption PC | ≤ 85.00 mVA |
Ambient conditions
Degree of Protection | IP20 (only when all terminal points are used) |
Ambient Temperature (Operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 6000 m (amsl) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 50g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (Operation) | 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
Standards and Regulations
Standards/specifications | EN 61643-31 |
Note | 2019 |
Standards/specifications | IEC 61643-31 |
Note | 2018 |
Mounting
Mounting Type | DIN rail: 35 mm |
Accessories
Why Proax for Phoenix Contact 2905646?
Proax is an authorized distributor of Phoenix Contact 2905646 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |