Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
QUINT-PS/3AC/24DC/40
Weight
3.005 kg
Series QUINT-PS

QUINT-PS/3AC/24DC/40 - Power supply unit

Primary-switched power supply unit QUINT POWER, Screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input: 3-phase, output: 24 V DC / 40 A

  • Reliable starting of difficult loads
  • High level of system availability even in the event of permanent phase failure
  • Preventive function monitoring
Technical Specifications

AC operation

Nominal input voltage range3x 400 V AC ... 500 V AC
Input voltage range3x 400 V AC ... 500 V AC -20 % ... +15 %
Voltage type of supply voltageAC/DC
Inrush Current< 15 A (at 25 °C)
Inrush current integral (I2t)< 1 A2s
Inrush current limitation15 A
AC frequency range45 Hz ... 65 Hz
Frequency range DC0 Hz
Mains buffering time> 25 ms (400 V AC)
Mains buffering time> 35 ms (500 V AC)
Current consumption3x 2.1 A (400 V AC)
Current consumption3x 1.5 A (500 V AC)
Nominal Power Consumption1342 VA
Protective circuitTransient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi)0.76
Typical response time< 0.5 s
Permissible backup fuseB6 B10 B16 AC:
Permissible DC backup fuseDC: Connect a suitable fuse upstream
Recommended breaker for input protection6 A ... 20 A (Characteristic B, C, D, K or comparable)
Discharge current to PE< 3.5 mA

DC operation

Nominal input voltage range± 500 V DC ... 600 V DC
Input voltage range500 V DC ... 600 V DC -10 % ... +34 % (mid-point earthed)
Current consumption2.2 A (500 V DC)
Current consumption1.9 A (600 V DC)
Recommended breaker for input protection1x 6 A ≥ 1000 V DC (10 x 38 mm, 30 kA L/R = 2 ms)

Output data

Efficiencytyp. 94 % (400 V AC)
Output characteristicU/I
Nominal Output Voltage24 V DC ±1 %
Setting range of the output voltage (USet)18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)40 A
POWER BOOST (IBoost)45 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC )
Static Boost (IStat.Boost)45 A
Selective Fuse Breaking (ISFB)215 A (12 ms)
Magnetic circuit breaker trippingB2 / B4 / B6 / B10 / B16 / B25 / C2 / C4 / C6 / C13
Derating60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance≤ 35 V DC
Protection against overvoltage at the output (OVP)≤ 35 V DC
Control deviation< 1 % (change in load, static 10 % ... 90 %)
Control deviation< 3 % (change in load, dynamic 10 % ... 90 %)
Control deviation< 0.1 % (change in input voltage ±10 %)
Residual ripple< 40 mVPP (with nominal values)
Short-circuit-proofyes
Output Power960 W
Output Power1080 W
Peak switching voltages nominal load< 5 mVPP (at nominal values, 20 MHz)
Maximum no-load power dissipation18 W
Power loss nominal load max.63 W
Rise time< 0.15 s (UOUT (10 % ... 90 %))
Connection in parallelyes, for redundancy and increased capacity
Connection in seriesyes

Signal: DC OK active

Output descriptionUOUT > 0.9 x UN: High signal
Switching voltage range18 V DC ... 24 V DC
Output Voltage+ 24 V DC
Maximum Inrush Current≤ 20 mA (short-circuit-proof)
Continuous load current≤ 20 mA

Signal: DC OK floating

Output descriptionRelay contact, UOUT > 0.9 x UN: Contact closed
Maximum Switching Voltage30 V AC/DC
Maximum Switching Voltage24 V DC
Maximum Inrush Current0.5 A
Maximum Inrush Current1 A
Continuous load current≤ 1 A

Signal: POWER BOOST, active

Output descriptionIOUT < IN: High signal
Switching voltage range18 V DC ... 24 V DC
Output Voltage+ 24 V DC
Maximum Inrush Current≤ 20 mA (short-circuit-proof)
Continuous load current≤ 20 mA

Input

Connection MethodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.6 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Conductor cross section AWG min.18
Conductor cross section AWG max.10
Stripping length7 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Output

Connection MethodScrew connection
Conductor cross section, rigid min.0.5 mm²
Conductor cross section, rigid max.16 mm²
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.16 mm²
Conductor cross section AWG min.8
Conductor cross section AWG max.6
Stripping length10 mm
Screw threadM4
Tightening torque, min1.2 Nm
Tightening torque max1.5 Nm

Signal

Connection MethodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.6 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Conductor cross section AWG min.18
Conductor cross section AWG max.10
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Signaling

Types of signalingLED
Types of signalingActive switching output
Types of signalingRelay contact
Operating voltage displayGreen LED

Signal output: DC OK active

Status displayUOUT > 0.9 x UN: "DC OK" LED green
Note on status displayUOUT < 0.9 x UN: Flashing "DC OK" LED

Signal output: DC OK floating

Status displayUOUT > 0.9 x UN: "DC OK" LED green
Note on status displayUOUT < 0.9 x UN: Flashing "DC OK" LED

Signal output: POWER BOOST, active

Status displayIOUT > IN: LED "BOOST" yellow

Electrical properties

Number of phases3.00
Insulation voltage input/output4 kV AC (type test)
Insulation voltage input/output2 kV AC (routine test)
Insulation voltage output / PE500 V DC (routine test)
Insulation voltage input / PE3.5 kV AC (type test)
Insulation voltage input / PE2 kV AC (routine test)

Product properties

Product familyQUINT POWER
MTBF (IEC 61709, SN 29500)> 880000 h (25 °C)
MTBF (IEC 61709, SN 29500)> 500000 h (40 °C)
MTBF (IEC 61709, SN 29500)> 216000 h (60 °C)

Insulation characteristics

Protection classI
Degree of pollution2

Dimensions

Width96 mm
Height130 mm
Depth176 mm

Installation dimensions

Installation distance right/left5 mm / 5 mm
Installation distance top/bottom50 mm / 50 mm

Alternative assembly

Width176 mm
Height130 mm
Depth99 mm

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsalignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting Positionhorizontal DIN rail NS 35, EN 60715
With protective coatingNo

Material specifications

Housing MaterialMetal
Hood versionGalvanized sheet steel, free from chrome (VI)
Side element versionAluminum

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (start-up type tested)-40 °C
Maximum altitude5000 m
Climatic class3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (Operation)5 Hz ... 100 Hz resonance search 0.7g, 90 min., resonance frequency 0.7g, 90 min. (in accordance with DNV GL Class A)

Standards and Regulations

Rail applicationsEN 50121-4
Rail applicationsEN 50121-3-2
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Standard - Electrical safetyIEC 61010-2-201 (SELV)
Standard - Equipment safetyGS (tested safety)
Standard – Safety extra-low voltageIEC 61010-1 (SELV)
Standard – Safety extra-low voltageIEC 61010-2-201 (PELV)
Standard - Safe isolationIEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory useIEC 61010-1
Standard - surge resistanceVDE 0160 (curve W2)

Overvoltage category

EN 61010-1II (≤ 5000 m)
EN 62477-1III (≤ 2000 m)
EN 61558-2-16II (≤ 4000 m)

Approvals

CSACAN/CSA-C22.2 No. 60950-1-07
CSACSA-C22.2 No. 107.1-01
Shipbuilding approvalDNV GL (EMC A), ABS, LR, RINA, NK, BV
UL approvalsUL Listed UL 508
UL approvalsUL/C-UL Recognized UL 60950-1 (3-wire + PE, star net)
UL approvalsUL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise emissionEN 61000-6-4
EMC requirements for noise immunityEN 61000-6-1
EMC requirements for noise immunityEN 61000-6-2
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge8 kV (Test Level 4)
Discharge in air15 kV (Test Level 4)
CommentsCriterion A

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 1 GHz
Test field strength20 V/m (Test Level 3)
Frequency Range1 GHz ... 2 GHz
Test field strength10 V/m (Test Level 3)
Frequency Range2 GHz ... 3 GHz
Test field strength10 V/m (Test Level 3)
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input4 kV (Test Level 4 - asymmetrical)
Output2 kV (Test Level 3 - asymmetrical)
Signal2 kV (Test Level 4 - asymmetrical)
CommentsCriterion A

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Input1 kV (Test Level 2 - symmetrical)
Input2 kV (Test Level 3 - asymmetrical)
Output0.5 kV (Test Level 1 - symmetrical)
Output0.5 kV (Test Level 1 - asymmetrical)
Signal1 kV (Test Level 2 - asymmetrical)
CommentsCriterion B

Conducted interference

Standards/regulationsEN 61000-4-6
I/O/Sasymmetrical
Frequency Range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)

Emitted interference

Standards/regulationsEN 61000-6-3
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Accessories

Why Proax for Phoenix Contact 2866802?

Proax is an authorized distributor of Phoenix Contact 2866802 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability