2862178
SKU
PHX2862178
MPN
IB IL 24/230 DOR1/W-PC-PAC
Weight
0.08 kg
This product is Not Cancellable/Not Returnable
Series IB-IL
IB IL 24/230 DOR1/W-PC-PAC - Inline terminal
Inline, Relay terminal, Relay output: 1 (floating contacts), 24 V DC, 230 V AC, for switching inductive and capacitive loads, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
- Safe isolation in acc. with EN 50178
- Floating connection for one actuator
- Nominal current at the output: 2.2 A
- Total current of the terminal: 2.6 A
Technical Specifications
Dimensions
| Width | 12.2 mm |
| Height | 119.8 mm |
| Depth | 71.5 mm |
| Note on dimensions | Housing dimensions |
Material specifications
| Color | gray |
Inline local bus
| No. of channels | 2 |
| Connection Method | Inline data jumper |
| Transmission Speed | 500 kbps |
Module
| ID code (dec.) | 189 |
| ID code (hex) | BD |
| Length code (hex) | C2 |
| Length code (dec) | 194 |
| Process data channel | 2 bit |
| Input address area | 0 Byte |
| Output address area | 2 bit (Only bit0 is occupied) |
| Register length | 2 bit |
| Required parameter data | 3 Byte |
| Required configuration data | 4 Byte |
Relay
| Number of Outputs | 1 (floating contacts) |
| Connection Method | Spring-cage connection |
| Switching voltage | max. 250 V DC |
| Switching voltage | min. 5 V DC |
| Switching voltage | max. 253 V AC |
| Switching current | max. 2.6 A (At 30 V DC) |
| Switching current | max. 0.15 A (for 250 V DC) |
| Switching capacity | max. 750 VA (see to derating) |
| Limiting Continuous Current | 2.6 A |
| Mechanical service life | 2x 10⁷ cycles |
Product properties
| Product family | Inline |
| Type | modular |
| Scope of delivery | including Inline connector and labeling field |
| No. of channels | 1 |
| Operating mode | Process data mode with 2 bits |
| Special Properties | for switching inductive and capacitive loads |
Potentials: Communications power (UL)
| Supply Voltage | 7.5 V DC (via voltage jumper) |
| Current draw | max. 60 mA |
| Power consumption | max. 0.45 W |
Electrical isolation/isolation of the voltage ranges
| Test voltage: Relay contact / Bus logics | 4 kV, 50 Hz, 1 min. |
| Test voltage: Contact/contact | 1 kV, 50 Hz, 1 min. |
| Test voltage: Contact / PE | 1 kV, 50 Hz, 1 min. |
Connection technology
| Connection name | Inline connector |
Conductor connection
| Connection Method | Spring-cage connection |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
Inline connector
| Connection Method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
Ambient conditions
| Ambient Temperature (Operation) | -25 °C ... 55 °C |
| Degree of Protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Standards and Regulations
| Protection class | I (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2862178?
Proax is an authorized distributor of Phoenix Contact 2862178 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
IB IL 24/48 DOR 2/W-XC-PAC - Inline, Relay terminal, Relay output: 2 (floating contacts), 2 floating changeover contacts, 24 V AC / 48 V DC, for switching ohmic loads, Extreme conditions version, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field