SKU
MPN
IB IL 230 PWR IN
Weight
0.165 kg
Series IB-IL
IB IL 230 PWR IN - Inline function terminal
Inline power terminal block, without accessories, without fuse, 230 V AC
- Diagnostic and status indicators
- Supplying the L phase (230 V AC)
Technical Specifications
Product properties
Type | modular |
Type | Inline |
Insulation characteristics
Protection class | I (IEC 61140, EN 61140, VDE 0140-1) |
Module
ID code (dec.) | none |
ID code (hex) | none |
Register length | 0 bit |
Electrical properties
Test section | 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. |
Test section | 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. |
Test section | 7.5 V supply (bus logics) / I/O area 120 V AC 2500 V AC 50 Hz 1 min. |
Test section | Routine test 1200 V AC 50 Hz 1 min. |
Test section | I/O area 120 V AC/PE 500 V AC 50 Hz 1 min. |
Test section | Output / Phase 500 V AC 50 Hz 1 min. |
Supply
I/O voltage | 230 V AC |
I/O voltage range | 207 V AC ... 253 V AC (including all tolerances, including ripple) |
Residual ripple | ± 23 V |
Max. current consumption | 8 A |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Inline local bus
Connection Method | Inline data jumper |
Dimensions
Width | 36.6 mm |
Height | 119.8 mm |
Depth | 71.5 mm |
Material specifications
Color | gray |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 55 °C |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 75 % ... 85 % |
Permissible humidity (storage/transport) | 75 % ... 85 % |
Mounting
Mounting Type | DIN rail mounting |
Why Proax for Phoenix Contact 2740339?
Proax is an authorized distributor of Phoenix Contact 2740339 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- IB IL 24/48 DOR 2/W-XC-PAC - Inline, Relay terminal, Relay output: 2 (floating contacts), 2 floating changeover contacts, 24 V AC / 48 V DC, for switching ohmic loads, Extreme conditions version, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field