SKU
MPN
FLT-CP-2C-350
Weight
0.672 kg
Series FLT-CP
FLT-CP-2C-350 - Type 1+2 special combined lightning current and surge arrester
Pluggable lightning current and surge arrester combination, in acc. with typ 1+2 / Class I+II / B+C arresters. Arresters coordinated following the AEC principle, for 2-phase power supply networks with PE and N (L1, L2, PEN) installed in one cable.
Technical Specifications
Product properties
IEC test classification | I + II |
IEC test classification | T1 + T2 |
EN type | T1 + T2 |
IEC power supply system | TN-C |
Type | DIN rail module, two-section, divisible |
Number of Positions | 2 |
Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
Electrical properties
Nominal frequency fN | 50 Hz (60 Hz) |
Indicator/remote signaling
Connection name | Remote fault indicator contact |
Switching function | Changeover contact |
Operating Voltage | 12 V AC ... 250 V AC |
Operating Voltage | 125 V DC (200 mA DC) |
Operating current | 10 mA AC ... 1 A AC |
Operating current | 1 A DC (30 V DC) |
Connection data
Connection Method | Screw terminal blocks |
Screw thread | M5 |
Tightening torque | 4.5 Nm |
Stripping length | 18 mm |
Conductor cross section flexible | 2.5 mm² ... 25 mm² |
Conductor cross section rigid | 2.5 mm² ... 35 mm² |
Conductor cross section AWG | 13 ... 2 |
Remote fault indicator contact
Connection Method | Plug-in/screw connection via COMBICON |
Screw thread | M2 |
Tightening torque | 0.25 Nm |
Stripping length | 7 mm |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Dimensions
Width | 71.2 mm |
Height | 95 mm |
Depth | 71.5 mm |
Horizontal pitch | 4 Div. |
Material specifications
Flammability rating according to UL 94 | V - 0 |
CTI value of material | 600 |
Insulating material | PA 6.6/PBT |
Material group | I |
Housing Material | PBT |
Mechanical data
Open side panel | No |
Protective circuit
Mode of protection | L-PEN |
Direction of action | 2L-N/PE |
Nominal voltage UN | 240/415 V AC (TN-C) |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 350 V AC |
Rated load current IL | 125 A (< 55 °C) |
Nominal discharge current In (8/20) µs | 25 kA |
Impulse discharge current (10/350) µs, charge | 12.5 As |
Impulse discharge current (10/350) µs, specific energy | 160 kJ/Ω |
Impulse discharge current (10/350) µs, peak value limp | 25 kA |
Follow current interrupt rating Ifi | 25 kA (264 V AC) |
Follow current interrupt rating Ifi | 3 kA (350 V AC) |
Short-circuit current rating ISCCR | 25 kA (264 V AC) |
Short-circuit current rating ISCCR | 3 kA (350 V AC) |
Voltage protection level Up | ≤ 1.5 kV |
Residual voltage Ures | ≤ 1.5 kV (at In) |
Residual voltage Ures | ≤ 1.2 kV (at 10 kA) |
Residual voltage Ures | ≤ 1 kV (at 5 kA) |
Residual voltage Ures | ≤ 0.9 kV (at 3 kA) |
Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 1.5 kV |
TOV behavior at UT | 415 V AC (5 s / withstand mode) |
TOV behavior at UT | 457 V AC (120 min / safe failure mode) |
Response time tA | ≤ 25 ns |
Max. backup fuse with V-type through wiring | 125 A (gG) |
Max. backup fuse with branch wiring | 315 A (gG) |
Ambient conditions
Degree of Protection | IP20 (only when all terminal points are used) |
Ambient Temperature (Operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (Operation) | 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
UL specifications
Maximum continuous operating voltage MCOV (L-L) | 528 V AC |
Maximum continuous operating voltage MCOV (L-G) | 264 V AC |
Nominal discharge current In (L-L) | 20 kA |
Nominal discharge current In (L-G) | 20 kA |
Mode of protection | L-L |
Mode of protection | L-G |
Nominal Voltage | 240/415 V AC |
Power distribution system | Delta |
Nominal frequency | 50/60 Hz |
Measured limiting voltage MLV (L-L) | 2450 V |
Measured limiting voltage MLV (L-G) | 1340 V |
Follow current (N-G) | 10 kA (264 V AC) |
SPD Type | 4CA |
UL indicator/remote signaling
Operating Voltage | 125 V AC |
AC operating current | 1 A AC |
UL connection data
Tightening torque | 40 lbf-in. |
Conductor cross section AWG | 12 ... 2 |
Air clearances and creepage distances
Standards/regulations | DIN VDE 0110-1 / IEC 60664-1 / IEC 61643-1 |
Standards/specifications | IEC 61643-11 |
Note | 2011 |
Standards/specifications | EN 61643-11 |
Note | 2012 |
Mounting
Mounting Type | DIN rail: 35 mm |
Why Proax for Phoenix Contact 2859770?
Proax is an authorized distributor of Phoenix Contact 2859770 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |