MCR-F-UI-DC - Frequency measuring transducer
MCR frequency measuring transducer, programmable, for converting frequencies into analog signals, with 3-way isolation and configurable output
- Replacement product MINI MCR-2-F-UI(-PT) 2902056 (2902058, Push-in version) in combination with MINI MCR-2-SPS-24-15(-PT) 1033202 (1033201, Push-in version)
- Can be programmed via membrane keypad or software
- Display of the input or output signal
- 3-way isolation
- Analog and switching output
- For NAMUR sensors, floating contacts, frequency generators, and NPN/PNP transistor outputs
- Frequencies up to 120 kHz
Technical Specifications
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
Operating elements | Membrane keypad with 3 keys and LCD display |
Electrical properties
Alignment span | ± 25 % |
Alignment zero | ± 25 % |
Electrical isolation between input and output | yes |
Maximum power dissipation for nominal condition | 1.8 W |
Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
Protective circuit | Transient protection |
Protective circuit | Reverse polarity protection |
Step response (10-90%) | < 25 ms |
Maximum temperature coefficient | 0.015 %/K |
Temperature coefficient, typical | 0.01 %/K |
Maximum transmission error | ≤ 0.15 % (of measured value) |
Transmission error, typical | 0.1 % |
Supply
Supply Voltage Range | 20 V DC ... 30 V DC |
Max. current consumption | < 60 mA (without load, without switching output) |
Measurement: Frequency
Configurable/programmable | Yes |
Available Input Sources | NPN/PNP transistor outputs |
Available Input Sources | NAMUR initiators |
Available Input Sources | Floating relay contact (dry contact) |
Available Input Sources | Frequency generator |
Encoder supply voltage | 15 V DC |
Encoder supply current | ≤ 25 mA (constant) |
Signal level | 2 VPP (In case of rectangle 0.1 Hz ... 120 kHz) |
Signal level | 2 VPP (In case of sine 8 Hz ... 120 kHz) |
Signal level | 13 VPP (In case of sine 1 Hz ... 120 kHz) |
Max. voltage input signal | 30 V (incl. DC voltage) |
Impulse form | any |
Pulse time | ≥ 1 µs |
Measured value resolution | > 12 bit |
A/D conversion time | ≤ 32 ms |
Frequency measuring range | 0.1 Hz ... 120 kHz |
Signal: I analog
Description of the input | Current input (isolating amplifier function) |
Number of Inputs | 1 |
Configurable/programmable | Yes |
Current Input Signal | 0 mA ... 20 mA (freely adjustable) |
Max. current input signal | 24 mA |
Input resistance current input | 200 Ω |
Measured value resolution | 14 bit (full-scale) |
Step response (10-90%) | < 25 ms |
Supply Voltage | 24 V DC |
Signal: U digital
Description of the input | Voltage input (isolating amplifier function) |
Configurable/programmable | Yes |
Voltage input signal | 0 V ... 10 V (freely adjustable) |
Max. voltage input signal | 12 V |
Input resistance of voltage input | 95 kΩ |
Measured value resolution | 14 bit (full-scale) |
Step response (10-90%) | < 25 ms |
Switching: Transistor
Output description | Switches supply voltage to terminal block SW, can carry a load of 100 mA, not protected against short-circuit |
Signal:
Number of Outputs | 1 |
Configurable/programmable | Yes |
Voltage output signal | 0 V ... 10 V |
Voltage output signal | 0 V ... 5 V |
Voltage output signal | 10 V ... 0 V |
Voltage output signal | 5 V ... 0 V |
Max. voltage output signal | 12.5 V |
Load/output load voltage output | ≥ 500 Ω |
Ripple | < 20 mVPP |
Configurable/programmable | Yes |
Current Output Signal | 0 mA ... 20 mA |
Current Output Signal | 4 mA ... 20 mA |
Current Output Signal | 20 mA ... 0 mA |
Current Output Signal | 20 mA ... 4 mA |
Max. current output signal | 25 mA |
Load/Output Load Current Output | ≤ 500 Ω |
Ripple | < 20 mVPP |
Connection data
Connection Method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Signaling
Status display | LC display |
Dimensions
Width | 45 mm |
Height | 75 mm |
Depth | 110 mm |
Material specifications
Color | green (RAL 6021) |
Housing Material | ASA-PC (V0) |
Ambient conditions
Ambient Temperature (Operation) | -20 °C ... 65 °C (for specified data) |
CE
Certificate | CE-compliant |
UL, USA/Canada
Identification | Class I, Div. 2, Groups A, B, C, D or Non-Hazardous Locations |
GL
Identification | DNV GL |
Mounting
Mounting Type | DIN rail mounting |
Mounting Position | any |
Accessories
Why Proax for Phoenix Contact 2814605?
Proax is an authorized distributor of Phoenix Contact 2814605 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |