Official Distributor
SKU
MPN
QUINT4-PS/1AC/24DC/2.5/SC
Weight
0.316 kg
Series QUINT4-PS
QUINT4-PS/1AC/24DC/2.5/SC - Power supply unit
Primary-switched power supply unit QUINT POWER, Screw connection, DIN rail mounting, input: 1-phase, output: 24 V DC / 2.5 A. Alternative item: 2909576
- Starting of heavy loads with dynamic boost
- Preventive function monitoring indicates critical operating states before errors occur
- High efficiency and long service life, with low power dissipation and low heating
- Space savings in the control cabinet, thanks to a narrow, slim-line design
- Free selection between Push-in and screw connection
Technical Specifications
AC operation
Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
Electric strength, max. | 300 V AC 30 s |
Typical national grid voltage | 120 V AC |
Typical national grid voltage | 230 V AC |
Voltage type of supply voltage | AC/DC |
Inrush Current | typ. 10 A (at 25 °C) |
Inrush current integral (I2t) | < 0.1 A2s |
Inrush current limitation | 4.3 A (after 1 ms) |
Inrush current limitation | < 10 A |
Frequency range (fN) | 50 Hz ... 60 Hz -10 % ... +10 % |
Mains buffering time | typ. 54 ms (120 V AC) |
Mains buffering time | typ. 54 ms (230 V AC) |
Current consumption | 0.85 A (100 V AC) |
Current consumption | 0.7 A (120 V AC) |
Current consumption | 0.39 A (230 V AC) |
Current consumption | 0.37 A (240 V AC) |
Nominal Power Consumption | 71 VA |
Protective circuit | Transient surge protection; Varistor |
Typical response time | 500 ms |
Input fuse | 3.15 A (slow-blow, internal) |
Recommended breaker for input protection | 6 A ... 16 A (Characteristic B, C or comparable) |
Discharge current to PE | < 0.25 mA (264 V AC, 60 Hz) |
Discharge current to PE | 0.22 mA (264 V AC, 60 Hz) |
DC operation
Input voltage range | 110 V DC ... 250 V DC -20 % ... +40 % |
Voltage type of supply voltage | AC/DC |
Current consumption | 0.75 A (110 V DC) |
Current consumption | 0.33 A (250 V DC) |
Output data
Efficiency | typ. 91.9 % (120 V AC) |
Efficiency | typ. 92.6 % (230 V AC) |
Output characteristic | U/I Advanced |
Nominal Output Voltage | 24 V DC |
Setting range of the output voltage (USet) | 24 V DC ... 28 V DC (constant capacity) |
Nominal output current (IN) | 2.5 A |
Static Boost (IStat.Boost) | 3.125 A (≤ 40 °C) |
Dynamic Boost (IDyn.Boost) | 5 A (≤60 °C (5 s), Input <150 V AC Derating 0.5 %/V) |
Derating | > 60 °C (2.5 %/K) |
Feedback voltage resistance | ≤ 35 V DC |
Protection against overvoltage at the output (OVP) | ≤ 32 V DC |
Control deviation | < 0.5 % (Static load change 10 % ... 90 %) |
Control deviation | < 2 % (Dynamic load change 10 % ... 90 %, (10 Hz)) |
Control deviation | < 0.1 % (change in input voltage ±10 %) |
Residual ripple | < 40 mVPP (with nominal values) |
Short-circuit-proof | yes |
No-load proof | yes |
Output Power | 60 W |
Output Power | 75 W |
Output Power | 120 W |
Maximum no-load power dissipation | < 1 W (230 V AC) |
Maximum no-load power dissipation | < 1 W (120 V AC) |
Power loss nominal load max. | < 5 W (230 V AC) |
Power loss nominal load max. | < 5 W (120 V AC) |
Crest factor | typ. 1.69 (120 V AC) |
Crest factor | typ. 1,82 (230 V AC) |
Rise time | 50 ms (UOut = 10 % ... 90 %) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Signal (configurable)
Digital | 0 V DC 24 V DC 30 mA |
Default | 24 V DC 30 mA 24 V DC for UOut > 0.9 x USet |
Input
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.14 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.14 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
Conductor cross section AWG min. | 26 |
Conductor cross section AWG max. | 14 |
Stripping length | 8 mm |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Output
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.14 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.14 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
Conductor cross section AWG min. | 26 |
Conductor cross section AWG max. | 14 |
Stripping length | 8 mm |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signal
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.14 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.14 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
Conductor cross section AWG min. | 26 |
Conductor cross section AWG max. | 14 |
Stripping length | 8 mm |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signaling
Types of signaling | LED |
Signal output
POut | > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting) |
UOut | > 0.9 x USet (LED lights up green) |
UOut | < 0.9 x USet (LED flashes green) |
Electrical properties
Number of phases | 1.00 |
Insulation voltage input/output | 4 kV AC (type test) |
Insulation voltage input/output | 3 kV AC (routine test) |
Switching frequency | 4.00 kHz ... 70.00 kHz (Auxiliary converter stage) |
Switching frequency | 30.00 kHz ... 150.00 kHz (PFC stage) |
Switching frequency | 70.00 kHz ... 150.00 kHz (Main converter stage) |
Product properties
Product family | QUINT POWER |
MTBF (IEC 61709, SN 29500) | > 1347000 h (25 °C) |
MTBF (IEC 61709, SN 29500) | > 734000 h (40 °C) |
MTBF (IEC 61709, SN 29500) | > 295000 h (60 °C) |
Environmental protection directive | RoHS Directive 2011/65/EU |
Environmental protection directive | WEEE |
Environmental protection directive | Reach |
Insulation characteristics
Protection class | II |
Degree of pollution | 2 |
Life expectancy (electrolytic capacitors)
Current | 2.5 A |
Temperature | 40 °C |
Time | 148000 h |
Additional text | 120 V AC |
Current | 2.5 A |
Temperature | 40 °C |
Time | 153000 h |
Additional text | 230 V AC |
Current | 2.5 A |
Temperature | 25 °C |
Time | 419000 h |
Additional text | 120 V AC |
Current | 2.5 A |
Temperature | 25 °C |
Time | 432000 h |
Additional text | 230 V AC |
Dimensions
Width | 32 mm |
Height | 99 mm |
Depth | 90 mm |
Installation dimensions
Installation distance right/left (active) | 15 mm / 15 mm (POut ≥50% ) |
Installation distance right/left (passive) | 5 mm / 5 mm (POut ≥50% ) |
Installation distance top/bottom (active) | 30 mm / 30 mm (POut ≥50% ) |
Installation distance top/bottom (passive) | 30 mm / 30 mm (POut ≥50% ) |
Installation distance top/bottom (active, passive) | 30 mm / 30 mm (POut ≤50 %) |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | DIN rail mounting |
With protective coating | No |
Material specifications
Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
Housing Material | Plastic |
Type of housing | Polycarbonate |
Hood version | Polycarbonate |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -40 °C |
Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) |
Climatic class | 3K3 (in acc. with EN 60721) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | < 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in accordance with IEC 60068-2-6) |
Standards and Regulations
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard - Electrical safety | IEC 61010-2-201 (SELV) |
Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
Standard – Safety extra-low voltage | IEC 61010-2-201 (PELV) |
Standard - Safe isolation | IEC 61558-2-16 |
Standard - Safe isolation | IEC 61010-2-201 |
Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
Standard - Safety of transformers | EN 61558-2-16 |
Standard - power supply devices for low voltage with DC output | EN 61204-3 |
Overvoltage category
EN 61010-1 | II (≤ 5000 m) |
EN 62477-1 | III (≤ 2000 m) |
Approvals
SIQ | CB-Scheme (IEC 61010-1, IEC 61010-2-201) |
UL approvals | UL Listed UL 61010-1 |
UL approvals | UL Listed UL 61010-2-201 |
UL approvals | UL 1310 Class 2 Power Units |
UL approvals | ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
EMC data
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
EMC requirements, power plant | IEC 61850-3 |
EMC requirements, power plant | EN 61000-6-5 |
Conducted noise emission | EN 55016 |
Conducted noise emission | EN 61000-6-3 (Class B) |
Noise emission | Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) |
Noise emission | EN 55016 |
Noise emission | EN 61000-6-3 (Class B) |
Harmonic currents
Frequency Range | 0 kHz ... 2 kHz |
Flicker
Frequency Range | 0 kHz ... 2 kHz |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 8 kV (Test Level 3) |
Comments | Criterion A |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 1 GHz |
Test field strength | 20 V/m |
Frequency Range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 4 kV (Test Level 4 - asymmetrical) |
Signal | 4 kV (Test Level 4 - asymmetrical) |
Comments | Criterion B |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 1 kV (Test Level 3 - symmetrical) |
Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 0.5 kV (Test Level 2 - symmetrical) |
Output | 0.5 kV (Test Level 1 - asymmetrical) |
Signal | 0.5 kV (Test Level 2 - symmetrical) |
Signal | 0.5 kV (Test Level 1 - asymmetrical) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
I/O/S | asymmetrical |
Frequency Range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Power frequency magnetic field
Standards/regulations | EN 61000-4-8 |
Frequency | 16.67 Hz |
Frequency | 50 Hz |
Frequency | 60 Hz |
Test field strength | 100 A/m |
Additional text | 60 s |
Comments | Criterion A |
Frequency | 50 Hz |
Frequency | 60 Hz |
Frequency Range | 50 Hz ... 60 Hz |
Test field strength | 1 kA/m |
Additional text | 3 s |
Frequency | 0 Hz |
Test field strength | 300 A/m |
Additional text | DC, 60 s |
Voltage dips
Standards/regulations | EN 61000-4-11 |
Voltage | 100 V AC |
Frequency | 60 Hz |
Voltage dip | 70 % |
Number of periods | 0.5 / 1 / 25 periods |
Additional text | Test Level 2 |
Comments | Criterion B |
Voltage dip | 40 % |
Number of periods | 5 / 10 / 50 periods |
Additional text | Test Level 2 |
Comments | Criterion B |
Voltage dip | 0 % |
Number of periods | 0.5 / 1 / 5 / 50 periods |
Additional text | Test Level 2 |
Comments | Criterion B |
Pulse-shape magnetic field
Standards/regulations | EN 61000-4-9 |
Test field strength | 1000 A/m |
Comments | Criterion A |
Attenuated sinusoidal oscillations (ring wave)
Standards/regulations | EN 61000-4-12 |
Input | 2 kV (symmetrical) |
Input | 4 kV (asymmetrical) |
Comments | Criterion B |
Asymmetrical conducted disturbance variables
Standards/regulations | EN 61000-4-16 |
Test level 1 | 16.67 Hz 50 Hz 60 Hz (Test Level 3) |
Voltage | 30 V (Permanent) |
Test level 2 | 16.67 Hz 50 Hz 60 Hz (Test Level 4) |
Voltage | 300 V (1 s) |
Comments | Criterion A |
Attenuated oscillating wave
Standards/regulations | EN 61000-4-18 |
Input/Output/Signal | 1 kV (symmetrical) |
Input/Output/Signal | 2.5 kV (asymmetrical) |
Comments | Criterion B |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Accessories
Why Proax for Phoenix Contact 2904598?
Proax is an authorized distributor of Phoenix Contact 2904598 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended