Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
QUINT4-PS/1AC/24DC/40/+
Weight
3.261 kg
This product is Not Cancellable/Not Returnable
Series QUINT4-PS

QUINT4-PS/1AC/24DC/40/+ - Power supply unit

Primary-switched QUINT POWER supply for DIN rail mounting, with selectable output characteristic curve and SFB (Selective Fuse Breaking) Technology, protective coating and integrated decoupling MOSFET, input: 1-phase, output: 24 V DC / 40 A

Technical Specifications

Input data

Control input (configurable) RemOutput power ON/OFF (SLEEP MODE)
DefaultOutput power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)

AC operation

Network TypeStar network
Nominal input voltage range100 V AC ... 240 V AC
Input voltage range100 V AC ... 240 V AC -15 % ... +10 %
Derating< 100 V AC (1 %/V)
Electric strength, max.300 V AC 60 s
Typical national grid voltage120 V AC
Typical national grid voltage230 V AC
Voltage type of supply voltageAC
Inrush Currenttyp. 12 A (at 25 °C)
Inrush current integral (I2t)< 0.3 A2s
Inrush current limitation12 A (after 1 ms)
AC frequency range50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN)50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN)16.7 Hz (acc. to EN 50163)
Mains buffering timetyp. 27 ms (120 V AC)
Mains buffering timetyp. 27 ms (230 V AC)
Current consumption13.6 A (100 V AC)
Current consumption9.9 A (120 V AC)
Current consumption5.4 A (230 V AC)
Current consumption5.4 A (240 V AC)
Nominal Power Consumption1072 VA
Protective circuitTransient surge protection; Varistor, gas-filled surge arrester
Switch-on time< 1 s
Typical response time300 ms (from SLEEP MODE)
Input fuse16 A (slow-blow, internal)
Recommended breaker for input protection16 A ... 20 A (Characteristic B, C, D, K or comparable)
Discharge current to PE< 3.5 mA
Discharge current to PE1.7 mA (264 V AC, 60 Hz)

DC operation

Nominal input voltage range110 V DC ... 250 V DC
Input voltage range110 V DC ... 250 V DC -18 % ... +40 %
Derating< 110 V DC (1 %/V)
Voltage type of supply voltageDC
Current consumption12 A (110 V DC)
Current consumption5 A (250 V DC)

Output data

Efficiencytyp. 94.7 % (120 V AC)
Efficiencytyp. 95.7 % (230 V AC)
Output characteristicU/I Advanced
Output characteristicSmart HICCUP
Output characteristicFUSE MODE
Nominal Output Voltage24 V DC
Setting range of the output voltage (USet)24 V DC ... 28 V DC (constant capacity)
Nominal output current (IN)40 A
Static Boost (IStat.Boost)45 A
Dynamic Boost (IDyn.Boost)60 A (5 s)
Selective Fuse Breaking (ISFB)215 A (15 ms)
Magnetic circuit breaker trippingA1...A40 / B2...B25 / C1...C13 / Z1...Z16
Derating> 60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance≤ 35 V DC
Protection against overvoltage at the output (OVP)< 30 V DC (double protection with shut off within 20 ms)
Control deviation< 0.5 % (Static load change 10 % ... 90 %)
Control deviation< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
Control deviation< 0.25 % (change in input voltage ±10 %)
Residual ripple< 40 mVPP (with nominal values)
Short-circuit-proofyes
No-load proofyes
Output Power960 W
Output Power1080 W
Output Power1440 W
Maximum no-load power dissipation< 5 W (120 V AC)
Maximum no-load power dissipation< 5 W (230 V AC)
Power loss nominal load max.< 55 W (120 V AC)
Power loss nominal load max.< 44 W (230 V AC)
Power dissipation SLEEP MODE< 3 W (120 V AC)
Power dissipation SLEEP MODE< 3 W (230 V AC)
Crest factortyp. 1,7 (120 V AC)
Crest factortyp. 1.65 (230 V AC)
Rise time< 60 ms (UOut = 10 % ... 90 %)
Connection in parallelyes, for redundancy and increased capacity
Connection in seriesyes

Signal

Signal ground SGndReference potential for Out1, Out2, and Rem

Signal Out 1 (configurable)

Digital24 V DC 20 mA
Default24 V DC 20 mA 24 V DC for UOut > 0.9 x USet

Signal Out 2 (configurable)

Digital24 V DC 20 mA
Analog4 mA ... 20 mA ±5 % (Load ≤400 Ω)
Default24 V DC 20 mA 24 V DC for POut < PN

Signal relay 13/14 (configurable)

Defaultclosed (Uout > 0.9 USet)
Digital24 V DC 1 A
Digital30 V AC/DC 0.5 A

Input

Connection MethodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.6 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.10
Stripping length8 mm
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Output

Connection MethodScrew connection
Conductor cross section, rigid min.0.5 mm²
Conductor cross section, rigid max.16 mm²
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.16 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.16 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.16 mm²
Conductor cross section AWG min.20
Conductor cross section AWG max.6
Stripping length10 mm
Tightening torque, min1.2 Nm
Tightening torque max1.5 Nm

Signal

Connection MethodPush-in connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.1 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.0.75 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Signaling

Types of signalingLED
Types of signalingFloating signal contact
Types of signalingActive signal output Out1 (digital, configurable)
Types of signalingActive signal output Out2 (analog, configurable)
Types of signalingRemote contact
Types of signalingSignal ground SGnd

Signal output

POut> 100 % (LED lights up yellow, output power > 960 W)
POut> 75 % (LED lights up green, output power > 720 W)
POut> 50 % (LED lights up green, output power > 480 W)
UOut> 0.9 x USet (LED lights up green)
UOut< 0.9 x USet (LED flashes green)

Electrical properties

Number of phases1.00
Insulation voltage input/output4 kV AC (type test)
Insulation voltage input/output2 kV AC (routine test)
Switching frequency85.00 kHz ... 107.00 kHz (Auxiliary converter stage)
Switching frequency45.00 kHz ... 200.00 kHz (Main converter stage)
Switching frequency50.00 kHz ... 500.00 kHz (PFC stage)

Product properties

Product familyQUINT POWER
MTBF (IEC 61709, SN 29500)> 908000 h (25 °C)
MTBF (IEC 61709, SN 29500)> 539000 h (40 °C)
MTBF (IEC 61709, SN 29500)> 243000 h (60 °C)

Insulation characteristics

Protection classI
Degree of pollution2

Life expectancy (electrolytic capacitors)

Current20 A
Temperature40 °C
Time360000 h
Additional text120 V AC
Current20 A
Temperature40 °C
Time455000 h
Additional text230 V AC
Current40 A
Temperature25 °C
Time389000 h
Additional text120 V AC
Current40 A
Temperature25 °C
Time460000 h
Additional text230 V AC
Current40 A
Temperature40 °C
Time137000 h
Additional text120 V AC
Current40 A
Temperature40 °C
Time162000 h
Additional text230 V AC

Dimensions

Width120 mm
Height130 mm
Depth140 mm

Installation dimensions

Installation distance right/left5 mm / 5 mm
Installation distance top/bottom50 mm / 50 mm

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsalignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting Positionhorizontal DIN rail NS 35, EN 60715
With protective coatingyes

Material specifications

Flammability rating according to UL 94 (housing / terminal blocks)V0
Housing MaterialMetal
Hood versionStainless steel X6Cr17
Side element versionAluminum

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-40 °C ... 75 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 5000 m (> 2000 m, observe derating)
Climatic class3K22 (in accordance with EN 60721-3-3)
Max. permissible relative humidity (operation)≤ 100 % (at 25 °C, non-condensing)
Shock11 ms, 15 g, in each space direction (according to IEC 60068-2-27)
Vibration (Operation)5 Hz ... 100 Hz resonance search 0.7g, 90 min., resonance frequency 0.7g, 90 min. (in accordance with DNV GL Class A)5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C) mounted with UWA 130 - 2901664

Standards and Regulations

Rail applicationsEN 50121-3-2
Rail applicationsEN 50121-4
Rail applicationsEN 50121-5
Rail applicationsEN 50163
Rail applicationsIEC 62236-3-2
Rail applicationsIEC 62236-4
Rail applicationsIEC 62236-5
HART FSK Physical Layer Test Specification ComplianceOutput voltage UOut compliant
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Standard - Electrical safetyIEC 61010-2-201 (SELV)
Explosive atmosphereIEC 60079-0
Explosive atmosphereIEC 60079-7
Explosive atmosphereIEC 60079-11
Explosive atmosphereIEC 60079-15
Standard – Safety extra-low voltageIEC 61010-1 (SELV)
Standard – Safety extra-low voltageIEC 61010-2-201 (PELV)
Standard - Safe isolationIEC 61558-2-16
Standard - Safe isolationIEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory useIEC 61010-1
Battery chargingDIN 41773-1
Approval - requirement of the semiconductor industry with regard to mains voltage dipsSEMI F47-0706, EN 61000-4-11

Overvoltage category

EN 61010-1II (≤ 5000 m)
EN 62477-1III (≤ 2000 m)
EN 61558-2-16II (≤ 5000 m)

Approvals

CSACAN/CSA-C22.2 No. 61010-2-201
CSACSA-C22.2 No. 107.1-16
Shipbuilding approvalDNV
SIQCB-Scheme (IEC 61010-1, IEC 61010-2-201)
UL approvalsUL Listed UL 508
UL approvalsUL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) applied for

Conformity/Approvals

ATEXSIQ 23 ATEX 161 X
ATEX II 3 G Ex ec ic nC IIC T4 Gc
INMETRODNV 19.0187 X
IECExIECEx SIQ 23.0001X
IECExEx ec ic nC IIC T4 Gc
Functional Safety in accordance with IEC 61508SIL 3 applied for

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise emissionEN 61000-6-4
EMC requirements for noise immunityEN 61000-6-1
EMC requirements for noise immunityEN 61000-6-2
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
EMC requirements, power plantIEC 61850-3
EMC requirements, power plantEN 61000-6-5
Conducted noise emissionEN 55016
Conducted noise emissionEN 61000-6-3 (Class B)
Noise emissionAdditional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Noise emissionEN 55016
Noise emissionEN 61000-6-3 (Class B)
DNV GL conducted interferenceClass A
Additional textArea power distribution
DNV GL noise radiationClass A
Additional textArea power distribution

Harmonic currents

Standards/regulationsEN 61000-3-2
Standards/regulationsEN 61000-3-2 (Class A)
Frequency Range0 kHz ... 2 kHz

Flicker

Standards/regulationsEN 61000-3-3
Standards/regulationsEN 61000-3-3
Frequency Range0 kHz ... 2 kHz

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge8 kV (Test Level 4)
Discharge in air15 kV (Test Level 4)
CommentsCriterion A

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 1 GHz
Test field strength20 V/m (Test Level 3)
Frequency Range1 GHz ... 6 GHz
Test field strength10 V/m (Test Level 3)
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input4 kV (Test Level 4 - asymmetrical)
Output4 kV (Test Level 4 - asymmetrical)
Signal4 kV (Test Level 4 - asymmetrical)
CommentsCriterion A

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Inputtyp. 3 kV (Test Level 4 - symmetrical)
Inputtyp. 6 kV (Test Level 4 - asymmetrical)
Output1 kV (Test Level 3 - symmetrical)
Output2 kV (Test Level 3 - asymmetrical)
Signal4 kV (Test Level 4 - asymmetrical)
CommentsCriterion A

Conducted interference

Standards/regulationsEN 61000-4-6
I/O/Sasymmetrical
Frequency Range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)

Power frequency magnetic field

Standards/regulationsEN 61000-4-8
Frequency16.7 Hz
Frequency50 Hz
Frequency60 Hz
Test field strength100 A/m
Additional text60 s
CommentsCriterion A
Frequency50 Hz
Frequency60 Hz
Frequency Range50 Hz ... 60 Hz
Test field strength1 kA/m
Additional text3 s
Frequency0 Hz
Test field strength300 A/m
Additional textDC, 60 s

Voltage dips

Standards/regulationsEN 61000-4-11
Voltage230 V AC
Frequency50 Hz
Voltage dip70 %
Number of periods0.5 / 1 / 25 / 30 periods
Additional textTest Level 2
CommentsCriterion A: 0.5 / 1 / 25 / 30 periods
Voltage dip40 %
Number of periods5 / 10 / 50 periods
Additional textTest Level 2
CommentsCriterion A
Voltage dip0 %
Number of periods0,5 / 1 / 5 / 50 / 250 periods
Additional textTest Level 2
CommentsCriterion A: 0.5 / 1 periodCriterion B: 5 / 50 / 250 periods

Pulse-shape magnetic field

Standards/regulationsEN 61000-4-9
Test field strength1000 A/m
CommentsCriterion A

Attenuated sinusoidal oscillations (ring wave)

Standards/regulationsEN 61000-4-12
Input2 kV (Test Level 4 - symmetrical)
Input4 kV (Test Level 4 - asymmetrical)
CommentsCriterion A

Asymmetrical conducted disturbance variables

Standards/regulationsEN 61000-4-16
Test level 115 Hz 150 Hz (Test Level 4)
Voltage30 V 3 V
Test level 2150 Hz 1.5 kHz (Test Level 4)
Voltage3 V
Test level 31.5 kHz 15 kHz (Test Level 4)
Voltage3 V 30 V
Test level 415 kHz 150 kHz (Test Level 4)
Voltage30 V
Test level 516.7 Hz 50 Hz 60 Hz (Test Level 4)
Voltage30 V (10 s)
Test level 6150 Hz 180 Hz (Test Level 4)
Voltage30 V (10 s)
Test level 716.7 Hz 50 Hz 60 Hz (Test Level 4)
Voltage300 V (3 s)
CommentsCriterion A

Attenuated oscillating wave

Standards/regulationsEN 61000-4-18
Input, output (test level 1)100 kHz 1 MHz (Test Level 3 - symmetrical)
Voltage1 kV
Input, output (test level 2)10 MHz (Test Level 3 - asymmetrical)
Voltage2 kV
Input, output (test level 3)100 kHz 1 MHz (Test Level 3 - asymmetrical)
Voltage2.5 kV
Signals (test level 1)100 kHz 1 MHz (Test Level 3 - symmetrical)
Voltage1 kV
Signals (test level 2)100 kHz 1 MHz (Test Level 3 - asymmetrical)
Voltage2.5 kV
CommentsCriterion A

Attenuated oscillating magnetic field

Standards/regulationsEN 61000-4-10
Test field strength100 A/m
Test level 1100 kHz
Test field strength100 A/m
Test level 21 MHz
CommentsCriterion A

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Criterion CTemporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

Why Proax for Phoenix Contact 2904618?

Proax is an authorized distributor of Phoenix Contact 2904618 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability