A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 48-130 V, AC/DC
Technical Specifications
Dimensions
| Product Net Width | 102 mm |
| Product Net Depth / Length | 123.5 mm |
| Product Net Height | 148 mm |
| Product Net Weight | 1.9 kg |
| Dimension Diagram | 53540923-2 |
Technical
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Poles | 3P |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 160 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 160 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 55 °C 145 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 70 °C 130 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 110 A |
| Rated Operational Current AC-3 (Ie) | (440 V) 55 °C 100 A |
| Rated Operational Current AC-3 (Ie) | (500 V) 55 °C 100 A |
| Rated Operational Current AC-3 (Ie) | (690 V) 55 °C 82 A |
| Rated Operational Current AC-3 (Ie) | (1000 V) 55 °C 30 A |
| Rated Operational Current AC-3 (Ie) | (380 / 400 V) 55 °C 110 A |
| Rated Operational Current AC-3 (Ie) | (220 / 230 / 240 V) 55 °C 110 |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-1 (Ie) | (220 V) 3 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-3 (Ie) | (220 V) 3 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-5 (Ie) | (220 V) 3 Poles in Series, 40 °C 160 A |
| Rated Operational Power AC-3 (Pe) | (415 V) 59 kW |
| Rated Operational Power AC-3 (Pe) | (440 V) 59 kW |
| Rated Operational Power AC-3 (Pe) | (500 V) 59 kW |
| Rated Operational Power AC-3 (Pe) | (690 V) 75 kW |
| Rated Operational Power AC-3 (Pe) | (1000 V) 40 kW |
| Rated Operational Power AC-3 (Pe) | (380 / 400 V) 55 kW |
| Rated Operational Power AC-3 (Pe) | (220 / 230 / 240 V) 30 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Short-Circuit Protective Devices | gG Type Fuses 160 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
| Rated Insulation Voltage (Ui) | acc. to UL/CSA 600 V |
| Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Maximum Electrical Switching Frequency | (AC-2 / AC-4) 150 cycles per hour |
| Maximum Electrical Switching Frequency | (AC-3) 300 cycles per hour |
| Mechanical Durability | 10 million |
| Maximum Mechanical Switching Frequency | 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (Uc) | 50 Hz 48 ... 130 V |
| Rated Control Circuit Voltage (Uc) | 60 Hz 48 ... 130 V |
| Rated Control Circuit Voltage (Uc) | DC Operation 48 ... 130 V |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 7 V·A |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 60 Hz 7 V·A |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage DC 2 W |
| Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 350 V·A |
| Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 350 V·A |
| Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage DC 400 W |
| Power Loss | at Rated Operating Conditions per Pole 3.5 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 60 ... 130 ms |
| Operate Time | Between Coil De-energization and NO Contact Opening 55 ... 125 ms |
| Operate Time | Between Coil Energization and NC Contact Opening 27 ... 77 ms |
| Operate Time | Between Coil Energization and NO Contact Closing 30 ... 80 ms |
| Connecting Capacity Main Circuit | Bar 30 mm² |
| Connecting Capacity Main Circuit | Flexible with Cable End 2 x 6 ... 35 mm² |
| Connecting Capacity Main Circuit | Rigid 1 x 10 ... 95 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible 2x0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Solid 2 x 1 ... 4 mm² |
| Connecting Capacity Auxiliary Circuit | Stranded 2 x 1 .... 4 mm² |
| Connecting Capacity | Bar 30 mm² |
| Connecting Capacity | Flexible with Cable End 1 x 10 ... 70 mm² |
| Connecting Capacity | Rigid 1 x 10 ... 95 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
| Connecting Terminals (delivered in open position) Main Poles | M8 hexagon socket screw with single connector |
| Tightening torque | Main Circuit 8 N·m |
| Terminal Type | Cable Clamp |
| Product Name | Block Contactor |
Technical UL/CSA
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 140 A |
| Horsepower Rating UL/CSA | (200 V AC) Three Phase 30 hp |
| Horsepower Rating UL/CSA | (208 V AC) Three Phase 30 hp |
| Horsepower Rating UL/CSA | (220 ... 240 V AC) Three Phase 40 hp |
| Horsepower Rating UL/CSA | (440 ... 480 V AC) Three Phase 75 hp |
| Horsepower Rating UL/CSA | (550 ... 600 V AC) Three Phase 100 hp |
| Full Load Amps Motor Use | (440 ... 480 V AC) Three Phase 96 A |
| Full Load Amps Motor Use | (550 ... 600 V AC) Three Phase 99 A |
Why Proax for ABB AF110-30-11-69?
Proax is an authorized distributor of ABB AF110-30-11-69 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Alternate Names | AF110301169 |
| Pack Size | 1 |
Recommended