By ABB
SKU
MPN
1SFL431001R8111
Weight
2.023 kg
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V.Operated with control voltage, versions from 24….690 AC, 50 and 60 Hz
Technical Specifications
Dimensions
Product Net Width | 102 mm |
Product Net Depth / Length | 123.5 mm |
Product Net Height | 148 mm |
Product Net Weight | 1.8 kg |
Technical
Number of Main Contacts NO | 3 |
Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 |
Number of Auxiliary Contacts NC | 1 |
Rated Operational Voltage | Main Circuit 1000 V |
Rated Frequency (f) | Main Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 145 A |
Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 145 A |
Rated Operational Current AC-1 (Ie) | (690 V) 55 °C 135 A |
Rated Operational Current AC-1 (Ie) | (690 V) 70 °C 115 A |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 96 A |
Rated Operational Current AC-3 (Ie) | (440 V) 55 °C 93 A |
Rated Operational Current AC-3 (Ie) | (500 V) 55 °C 80 A |
Rated Operational Current AC-3 (Ie) | (690 V) 55 °C 65 A |
Rated Operational Current AC-3 (Ie) | (1000 V) 55 °C 30 A |
Rated Operational Current AC-3 (Ie) | (380 / 400 V) 55 °C 96 A |
Rated Operational Current AC-3 (Ie) | (220 / 230 / 240 V) 55 °C 96 |
Rated Operational Power AC-3 (Pe) | (415 V) 55 kW |
Rated Operational Power AC-3 (Pe) | (440 V) 55 kW |
Rated Operational Power AC-3 (Pe) | (500 V) 55 kW |
Rated Operational Power AC-3 (Pe) | (690 V) 55 kW |
Rated Operational Power AC-3 (Pe) | (1000 V) 40 kW |
Rated Operational Power AC-3 (Pe) | (380 / 400 V) 45 kW |
Rated Operational Power AC-3 (Pe) | (220 / 230 / 240 V) 25 kW |
Rated Breaking Capacity AC-3 | 8 x Ie AC-3 |
Rated Making Capacity AC-3 | 10 x Ie AC-3 |
Short-Circuit Protective Devices | gG Type Fuses 160 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 800 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 350 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1320 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 500 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A |
Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
Maximum Electrical Switching Frequency | (AC-2 / AC-4) 150 cycles per hour |
Maximum Electrical Switching Frequency | (AC-3) 300 cycles per hour |
Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 145 A |
Rated Operational Current DC-1 (Ie) | (220 V) 3 Poles in Series, 40 °C 145 A |
Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 145 A |
Rated Operational Current DC-3 (Ie) | (220 V) 3 Poles in Series, 40 °C 145 A |
Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 145 A |
Rated Operational Current DC-5 (Ie) | (220 V) 3 Poles in Series, 40 °C 145 A |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
Rated Insulation Voltage (Ui) | acc. to UL/CSA 600 V |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kV |
Mechanical Durability | 10 million |
Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
Rated Control Circuit Voltage (Uc) | 50 Hz 24 V |
Rated Control Circuit Voltage (Uc) | 60 Hz 24 V |
Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 22 V·A |
Coil Consumption | Holding at Max. Rated Control Circuit Voltage 60 Hz 26 V·A |
Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 350 V·A |
Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 450 V·A |
Operate Time | Between Coil De-energization and NC Contact Closing 7 ... 15 ms |
Operate Time | Between Coil De-energization and NO Contact Opening 10 ... 18 ms |
Operate Time | Between Coil Energization and NC Contact Opening 7 ... 22 ms |
Operate Time | Between Coil Energization and NO Contact Closing 10 ... 25 ms |
Connecting Capacity Main Circuit | Bar 30 mm² |
Connecting Capacity Main Circuit | Flexible with Cable End 1 x 10 ... 70 mm² |
Connecting Capacity Main Circuit | Rigid 2 x 6 ... 65 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² |
Connecting Capacity Auxiliary Circuit | Flexible 1x0.75 ... 2.5 mm² |
Connecting Capacity Auxiliary Circuit | Solid 2 x 1 ... 4 mm² |
Connecting Capacity Auxiliary Circuit | Stranded 2 x 1 .... 4 mm² |
Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
Connecting Terminals (delivered in open position) Main Poles | M8 hexagon socket screw with single connector |
Terminal Type | Cable Clamp |
Technical UL/CSA
Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
General Use Rating UL/CSA | (600 V AC) 125 A |
Horsepower Rating UL/CSA | (200 V AC) Three Phase 30 hp |
Horsepower Rating UL/CSA | (208 V AC) Three Phase 30 hp |
Horsepower Rating UL/CSA | (220 ... 240 V AC) Three Phase 30 hp |
Horsepower Rating UL/CSA | (440 ... 480 V AC) Three Phase 60 hp |
Horsepower Rating UL/CSA | (550 ... 600 V AC) Three Phase 75 hp |
Why Proax for ABB A95-30-11-81?
Proax is an authorized distributor of ABB A95-30-11-81 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | A95301181 |
Pack Size | 1 |
Recommended