SKU
MPN
VAL-SEC-T2-2C-350-FM
Weight
0.231 kg
This product is Not Cancellable/Not Returnable
Series VAL-SEC-T2
VAL-SEC-T2-2C-350-FM - Type 2 surge arrester
Plug-in surge arrester, in accordance with Type 2/Class II, for 2-phase power supply networks with combined PE and N installed in one conductor (3-conductor system: L1, L2, PEN), with remote indication contact.
- Surge protection family for universal use with optimum energy coordination from the lightning current arrester to the device protection
- Easy to maintain due to consistently pluggable protection modules
- Excellent level of information provided by mechanical/visual status indicator and remote indication contact
- More space in the control cabinet due to the narrow overall width of just 12 mm per position and use without separate backup fuse up to 315 A gG
Technical Specifications
Product properties
Product family | SEC Family |
IEC test classification | II |
IEC test classification | T2 |
EN type | T2 |
IEC power supply system | TN-C |
Type | DIN rail module, two-section, divisible |
Number of Positions | 2 |
Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
Electrical properties
Nominal frequency fN | 50 Hz (60 Hz) |
Indicator/remote signaling
Connection name | Remote fault indicator contact |
Switching function | Changeover contact |
Operating Voltage | 5 V AC ... 250 V AC |
Operating Voltage | 125 V DC (200 mA DC) |
Operating current | 5 mA AC ... 1 A AC |
Operating current | 1 A DC (30 V DC) |
Connection data
Connection Method | Screw connection |
Screw thread | M5 |
Tightening torque | 4.5 Nm |
Stripping length | 16 mm |
Conductor cross section flexible | 2.5 mm² ... 16 mm² |
Conductor cross section rigid | 2.5 mm² ... 25 mm² |
Conductor cross section AWG | 12 ... 4 |
Connection Method | Fork-type cable lug |
Conductor cross section flexible | 1.5 mm² ... 6 mm² |
Remote fault indicator contact
Connection Method | Plug-in/screw connection via COMBICON |
Screw thread | M2 |
Tightening torque | 0.25 Nm |
Stripping length | 7 mm |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Dimensions
Width | 25.4 mm |
Height | 97.9 mm |
Depth | 74.5 mm (incl. DIN rail 7.5 mm) |
Horizontal pitch | 1.4 Div. |
Material specifications
Color (Male connector) | light grey (RAL 7035) |
Color (Base element) | gray (RAL 7042) |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PA6.6-FR 20% GF |
Insulating material | PBT-FR |
Material group | I |
Housing Material | PA 6.6-FR 20 % GF |
Housing Material | PBT-FR |
Protective circuit
Mode of protection | L-PEN |
Direction of action | 2L-N/PE |
Nominal voltage UN | 240/415 V AC (TN-C) |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 350 V AC |
Rated load current IL | 40 A (Biconnect M4 fork-type cable lug 6 mm²) |
Rated load current IL | 63 A (TWIN ferrule 2 x 10 mm²) |
Nominal discharge current In (8/20) µs | 20 kA |
Maximum discharge current Imax (8/20) µs | 40 kA |
Short-circuit current rating ISCCR | 25 kA (for a backup fuse of up to 315 A gG) |
Short-circuit current rating ISCCR | 50 kA (for a backup fuse of up to 200 A gG) |
Voltage protection level Up | ≤ 1.5 kV |
Residual voltage Ures | ≤ 1.5 kV (at In) |
Residual voltage Ures | ≤ 1.3 kV (at 10 kA) |
Residual voltage Ures | ≤ 1.2 kV (at 5 kA) |
Residual voltage Ures | ≤ 1.1 kV (at 4 kA) |
Residual voltage Ures | ≤ 1 kV (at 2 kA) |
TOV behavior at UT | 415 V AC (5 s / withstand mode) |
TOV behavior at UT | 457 V AC (120 min / safe failure mode) |
Response time tA | ≤ 25 ns |
Max. backup fuse with V-type through wiring | 40 A (gG / Biconnect M4 fork-type cable lug, 6 mm²) |
Max. backup fuse with V-type through wiring | 63 A (gG / TWIN ferrule 2x 10mm²) |
Max. backup fuse with branch wiring | 315 A (gG) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (Operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
UL specifications
Maximum continuous operating voltage MCOV (L-L) | 700 V AC |
Maximum continuous operating voltage MCOV (L-N) | 350 V AC |
Nominal discharge current In (L-L) | 20 kA |
Nominal discharge current In (L-N) | 20 kA |
Mode of protection | L-L |
Mode of protection | L-N |
Nominal Voltage | 277/480 V AC |
Power distribution system | Wye |
Nominal frequency | 50/60 Hz |
Measured limiting voltage MLV (L-L) | 3280 V |
Measured limiting voltage MLV (L-N) | 2000 V |
SPD Type | 4CA |
UL indicator/remote signaling
Operating Voltage | 125 V AC |
AC operating current | 1 A AC |
UL connection data
Tightening torque | 40 lbf-in. ... 50 lbf-in. |
Conductor cross section AWG | 14 ... 2 (solid) |
Conductor cross section AWG | 14 ... 4 (flexible) |
Air clearances and creepage distances
Standards/regulations | DIN VDE 0110-1 / IEC 60664-1 / IEC 61643-1 |
Standards/specifications | IEC 61643-11 |
Note | 2011 |
EN 61643-11
Standards/specifications | EN 61643-11 |
Note | 2012 |
Mounting
Mounting Type | DIN rail: 35 mm |
Accessories
Why Proax for Phoenix Contact 2905337?
Proax is an authorized distributor of Phoenix Contact 2905337 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended