SKU
MPN
UNO-UPS/24DC/24DC/60W
Weight
1.182 kg
This product is Not Cancellable/Not Returnable
UNO-UPS/24DC/24DC/60W - Uninterruptible power supply
Uninterruptible power supply with integrated battery, lead AGM, VRLA technology, 24 V DC, 2x 0.8 Ah.
- Compact and narrow
Technical Specifications
General
Note on the battery | This product contains a battery with a limited shelf life that must be charged every few months. The product packaging indicates when the battery must be started up or recharged. The general shelf life can be found in the technical data area under “Latest startup”. |
DC operation
Input Voltage | 24 V DC |
Input voltage range | 22.5 V DC ... 29.5 V DC |
Voltage type of supply voltage | DC |
Buffer period | 45 min. (0.5 A) |
Buffer period | 20 min. (1 A) |
Buffer period | 8 min. (2 A) |
Buffer period | 5 min. (2.5 A) |
Current consumption | 2.8 A (max.) |
Current consumption | < 60 mA |
Current consumption | < 300 mA |
Input fuse | 5 A (electronic) |
Output data
Efficiency | > 95 % (for charged batteries) |
Efficiency | > 92 % (Battery operation) |
Nominal Output Voltage | 24 V DC |
Nominal output current (IN) | 2.5 A |
Bridging time | 300 s |
Output Power | 60 W |
Power dissipation | 3 W (Mains operation) |
Power dissipation | 6 W (Battery operation) |
Power dissipation | Battery operation |
Connection in series | No |
Mains operation
Nominal Output Voltage | 24 V DC |
Output voltage range | UOut = UIn - 0.5 V DC |
Nominal output current (IN) | 2.5 A (Permanent) |
Battery operation
Nominal Output Voltage | 24 V DC |
Output voltage range | 20 V DC ... 27.3 V DC |
Nominal output current (IN) | 2.5 A (Permanent) |
Signal: Alarm
Output description | Transistor (24 V DC/15 mA) |
Signal: Battery mode
Output description | Transistor (24 V DC/15 mA) |
Energy storage
Charging current | 200 mA |
Nominal capacity | 2x 0.8 Ah |
Charging time | approx. 5 h |
Battery module service life | 3 Years ... 5 Years (20 °C) |
Latest startup date (battery only) | 3 Months (0 °C ... 20 °C) |
Latest startup date (battery only) | 1 Months (30 °C ... 40 °C) |
Latest startup (battery only) - range | 3 Months ... 1 Months (20 °C ... 30 °C) |
Battery technology | Lead rechargeable battery module |
Accumulator type | YUASA NP0.8-12 |
Accumulator type | YUCEL Y0.8-12 |
Accumulator type | YUVOLT 0.8-12 |
Battery presence check (cyclic) | 60 s |
Battery fuse | T 5 A 32 V |
IQ Technology | no |
Input
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Output
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signal
Connection Method | Screw connection |
Conductor cross section, rigid min. | 0.2 mm² |
Conductor cross section, rigid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 7 mm |
Screw thread | M3 |
Tightening torque, min | 0.5 Nm |
Tightening torque max | 0.6 Nm |
Signaling
Types of signaling | LED |
Signal output
Signalization designation | Power In OK |
Status display | LED |
Note on status display | static on |
Signal output: Switching output
Signalization designation | Alarm |
Status display | LED |
Note on status display | static on |
Signal output
Status display | LED |
Note on status display | flashing |
Signal output: Switching output
Signalization designation | Battery mode |
Status display | LED |
Note on status display | flashing |
Signal output
Signalization designation | Service |
Status display | LED |
Note on status display | flashing |
Product properties
Product family | UNO UPS ‒ UPS with integrated battery |
IQ Technology | no |
MTBF (IEC 61709, SN 29500) | > 1900000 h (40 °C) |
Insulation characteristics
Protection class | III |
Degree of pollution | 2 |
Life expectancy (electrolytic capacitors)
Time | 170312 h |
Dimensions
Width | 110 mm |
Height | 90 mm |
Depth | 84 mm |
Installation dimensions
Installation distance right/left | 0 mm / 0 mm (≤ 70 °C) |
Installation distance top/bottom | 30 mm / 30 mm (≤ 70 °C) |
Mounting
Mounting Type | DIN rail: 35 mm |
Assembly instructions | alignable: 0 mm horizontally, 30 mm vertically |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
Material specifications
Housing Material | Plastic |
Housing Material | PC+ABS |
Type of housing | Plastic |
Foot latch material | POM (Polyoxymethylene) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -15 °C ... 50 °C |
Ambient temperature (storage/transport) | -20 °C ... 60 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (Operation) | < 13.2 Hz, amplitude ±1.0 mm (according to IEC 60068-2-6) |
Vibration (Operation) | 13.2 Hz ... 100 Hz, 0.7g |
Standards and Regulations
Standard - Electrical safety | IEC 62368-1 (SELV) |
Approvals
UL approvals | UL Listed UL 508 |
UL approvals | UL/C-UL Recognized UL 60950-1 |
EMC data
EMC requirements for noise emission | EN 61000-6-3 |
EMC requirements for noise emission | EN 61000-6-4 |
EMC requirements for noise immunity | EN 61000-6-1 |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | 6 kV (Test Level 3) |
Discharge in air | 8 kV (Test Level 3) |
Comments | Criterion A |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 3 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Signal | 2 kV (Test Level 4 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 0.5 kV (Test Level 1 - symmetrical) |
Input | 0.5 kV (Test Level 1 - asymmetrical) |
Output | 0.5 kV (Test Level 1 - symmetrical) |
Output | 0.5 kV (Test Level 1 - asymmetrical) |
Signal | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
I/O/S | asymmetrical |
Frequency Range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Emitted interference
Emitted radio interference in acc. with EN 55011 | EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Accessories
Why Proax for Phoenix Contact 2905907?
Proax is an authorized distributor of Phoenix Contact 2905907 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Best Sellersin Power supply