2702409
SKU
PHX2702409
MPN
TC EXTENDER 2001 ETH-2S
Weight
0.268 kg
Series TC-EXTENDER
TC EXTENDER 2001 ETH-2S - Ethernet extenders
Second generation: Unmanaged Ethernet extender for point-to-point connections, line and ring structures, data rates up to 30 Mbps, distances of up to 20 km on in-house copper cables, diagnostics via USB and LEDs, 2 SHDSL ports, 1 LAN port
- Distances up to 20 km
- Up to 15.3 Mbps in 2-wire operation
- Up to 30 Mbps in 4-wire operation
- Robust modulation method (SHDSL)
- Automatic SHDSL data rate detection
- Transparent transmission of all standard Ethernet protocols, including EtherNet/IP™, Modbus/TCP, PROFINET, PROFIsafe, EtherCAT®, KNX, BACnet/IP
- Network transparent (no IP configuration required)
- Automatic detection of network cable type (auto MDI(X))
- Automatic network data rate detection (10/100 Mbps)
- Easy startup, plug and play
- Future proof (IPv4 and IPv6-compatible)
- 2 digital outputs for alerting external controllers
Technical Specifications
Utilization restriction
| CCCex note | Use in potentially explosive areas is not permitted in China. |
Product properties
| MTTF | 711 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
| MTTF | 308 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) |
| MTTF | 125 Years (SN 29500 standard, temperature 40°C, operating cycle 100%) |
Functionality
| Basic Functions | Ethernet extenders in accordance with ITU-T G.991.2 |
Electrical properties
| Electrical isolation | VCC // Ethernet // DSL (A) // DSL (B) // FE |
| Maximum power dissipation for nominal condition | 4.32 W |
| Mains type | Permanent line |
| Test voltage data interface/power supply | 500 V AC (In accordance with EN/IEC 60079-7) |
| Test voltage data interface/power supply | 1.5 kV AC (50 Hz, 1 min.) |
Supply
| Supply Voltage Range | 18 V DC ... 30 V DC |
| Nominal Supply Voltage | 24 V DC ±5 % (as an alternative or redundant, via backplane bus contact and system current supply) |
| Nominal Supply Voltage | 5 V DC (configuration only, via mini-USB type B) |
| Typical current consumption | < 180 mA (24 V DC) |
| Max. current consumption | ≤ 2 A (For operation in a joining station, via the DIN rail connector) |
Function
| Status and diagnostic indicators | LEDs: US (supply voltage), ACT/LINK (Ethernet data traffic), ERR (errors)2x LINK / 2x STAT (DSL data traffic port A and port B), DIAG (diagnostic messages) |
Signal
| Output name | Digital output |
| Number of Outputs | 2 |
| Voltage output signal | 18 V DC ... 30 V DC (depending on the operating voltage) |
| Current Output Signal | ≤ 150 mA (Short-circuit-proof) |
| Behavior of outputs | Deactivated for device supply via DIN rail connector |
Supply
| Connection Method | COMBICON plug-in screw terminal block |
| Tightening torque | 0.56 Nm ... 0.79 Nm |
Interfaces
| Signal | Ethernet |
| Basic Functions | Ethernet extenders in accordance with ITU-T G.991.2 |
Data: Ethernet interface, 10/100Base-T(X) in accordance with IEEE 802.3
| Serial transmission speed | 10/100 Mbps, auto negotiation |
| Connection Method | RJ45 jack, shielded |
| Connection Method | 1 port 10/100Base-T(X), auto negotiation |
| No. of channels | 1 |
| Transmission length | < 100 m (shielded twisted pair) |
| Protocols Supported | Protocol-transparent for TCP/IP, IPv4, and IPv6 |
Data: SHDSL interface according to ITU-T G.991.2.bis
| Serial transmission speed | 4-wire operation: 64 kbps ... 30 Mbps |
| Serial transmission speed | 2-wire operation: 32 kbps ... 15.3 Mbps |
| Connection Method | 2 x 2-pos. COMBICON plug-in screw terminal blocks |
| No. of channels | 2 (2-wire operation) |
| Tightening torque | 0.56 Nm ... 0.79 Nm |
| Transmission length | < 20 km (Depending on data rate and cable cross section) |
| Single conductor/terminal point, rigid | 0.2 mm² ... 2.5 mm² |
| Single-wire/terminal point, flexible | 0.2 mm² ... 2.5 mm² |
| Max. AWG conductor cross section, flexible | 14 |
| Min. AWG conductor cross section, flexible | 24 |
| Single-wire/terminal point, rigid AWG max. | 14 |
| Single-wire/terminal point, rigid AWG min. | 24 |
| Stripping length | 7 mm |
Data: USB 2.0
| Connection Method | Mini-USB type B, 5-pos. |
| Transmission length | < 5 m (only for configuration and diagnostics) |
Dimensions
| Width | 35 mm |
| Height | 99 mm |
| Depth | 114.5 mm |
Material specifications
| Color (Housing) | gray (RAL 7042) |
| Material (Housing) | PA 6.6-FR |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -20 °C ... 60 °C (Freestanding (40 mm spacing to the right and left), no supply of other modules via the device) |
| Ambient Temperature (Operation) | -20 °C ... 55 °C (Mounted in rows with zero spacing and low power dissipation of aligned modules) |
| Ambient Temperature (Operation) | -20 °C ... 50 °C (Mounted in rows with zero spacing) |
| Ambient Temperature (Operation) | -20 °C ... 45 °C (aligned without spacing and supply of other modules via the device, 1.5 A) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation) |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
CE
| Certificate | CE-compliant |
ATEX
| Identification | II 3 G Ex ec IIC T4 Gc |
| Certificate | PxCIF11ATEX2313643X |
| Note | Please follow the special installation instructions in the documentation! |
UKEX
| Identification | II 3 G Ex ec IIC T4 Gc |
| Certificate | PxCIMA22UKEX2313643X |
UL, USA/Canada
| Identification | 508 Listed |
Corrosive gas test
| Identification | ISA-S71.04-1985 G3 Harsh Group A |
EMC data
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Electrostatic discharge
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | ± 6 kV |
| Discharge in air | ± 8 kV |
| Indirect discharge | ± 6 kV |
| Comments | Criterion B |
Electromagnetic HF field
| Standards/regulations | EN 61000-4-3 |
| Frequency Range | 80 MHz ... 3 GHz |
| Field intensity | 10 V/m |
| Comments | Criterion A |
Fast transients (burst)
| Standards/regulations | EN 61000-4-4 |
| Input | ± 2 kV |
| Signal | ± 2 kV |
| Comments | Criterion B |
Surge current load (surge)
| Standards/regulations | EN 61000-4-5 |
| Input | ± 0.5 kV (sym./asym.) |
| Output | ± 1 kV (asymmetrical, unshielded) |
| Signal | ± 1 kV (asymmetrical, shielded Ethernet cable) |
| Signal | ± 1 kV (asymmetrical: line to ground, unshielded SHDSL cable) |
| Comments | Criterion A |
Conducted interference
| Standards/regulations | EN 61000-4-6 |
| Frequency Range | 0.15 MHz ... 80 MHz |
| Comments | Criterion A |
| Voltage | 10 V |
Emitted interference
| Standards/regulations | EN 55011 |
| Comments | Class A, industrial applications |
Criteria
| Criterion A | Normal operating behavior within the specified limits. |
| Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Standards and Regulations
| Standards/regulations | EN 50121-4 |
Mounting
| Mounting Type | DIN rail: 35 mm |
| Assembly instructions | The product can be snapped onto all 35 mm DIN rails in accordance with EN 60715. |
Accessories
Why Proax for Phoenix Contact 2702409?
Proax is an authorized distributor of Phoenix Contact 2702409 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended