AM110-30-22-79
By ABB
SKU
ABBAM110302279
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 690 V. Magnetically latch, control voltage 220-240 V, AC/DC latch
Technical Specifications
Dimensions
| Product Net Width | 90 mm |
| Product Net Depth / Length | 156.5 mm |
| Product Net Height | 148 mm |
| Product Net Weight | 1.8 kg |
Technical
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 2 |
| Number of Auxiliary Contacts NC | 2 |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 160 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 160 A, (690 V) 55 °C 145 A, (690 V) 70 °C 130 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 110 A, (440 V) 55 °C 100 A, (500 V) 55 °C 100 A, (690 V) 55 °C 82 A, (1000 V) 55 °C 30 A, (380 / 400 V) 55 °C 110 A, (220 / 230 / 240 V) 55 °C 110 |
| Rated Operational Power AC-3 (Pe) | (415 V) 59 kW, (440 V) 59 kW, (500 V) 59 kW, (690 V) 75 kW, (1000 V) 40 kW, (380 / 400 V) 55 kW, (220 / 230 / 240 V) 30 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Short-Circuit Protective Devices | gG Type Fuses 160 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A, cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour, (AC-2 / AC-4) 150 cycles per hour, (AC-3) 300 cycles per hour |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 160 A, (220 V) 3 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 160 A, (220 V) 3 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 160 A, (220 V) 3 Poles in Series, 40 °C 160 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V, acc. to UL/CSA 600 V |
| Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kV |
| Mechanical Durability | 10 million |
| Maximum Mechanical Switching Frequency | 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (Uc) | 50 Hz 48 ... 130 V, 60 Hz 48 ... 130 V |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 22 V·A, Holding at Max. Rated Control Circuit Voltage 60 Hz 26 V·A, Holding at Max. Rated Control Circuit Voltage DC 2 W, Pull-in at Max. Rated Control Circuit Voltage 50 Hz 350 V·A, Pull-in at Max. Rated Control Circuit Voltage 60 Hz 450 V·A, Pull-in at Max. Rated Control Circuit Voltage DC 400 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 60 ... 130 ms, Between Coil De-energization and NO Contact Opening 55 ... 125 ms, Between Coil Energization and NC Contact Opening 27 ... 77 ms, Between Coil Energization and NO Contact Closing 30 ... 80 ms |
| Connecting Capacity Main Circuit | Bar 30 mm², Flexible with Cable End 1 x 10 ... 70 mm², Rigid 1 x 10 ... 95 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Flexible 2x0.75 ... 2.5 mm², Solid 2 x 1 ... 4 mm², Stranded 2 x 1 .... 4 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
| Connecting Terminals (delivered in open position) Main Poles | M8 hexagon socket screw with single connector |
| Terminal Type | Cable Clamp |
Technical UL/CSA
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| Horsepower Rating UL/CSA | (200 V AC) Three Phase 30 hp, (208 V AC) Three Phase 30 hp, (220 ... 240 V AC) Three Phase 40 hp, (440 ... 480 V AC) Three Phase 75 hp, (550 ... 600 V AC) Three Phase 100 hp |
Environmental
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C, Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C, Close to Contactor for Storage -60 ... +80 °C |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: A 20 g, Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: A 20 g, Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B1 15 g, Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C1 20 g, Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C2 20 g, Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B1 5 g, Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B2 15 g, Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C1 20 g, Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C2 20 g |
| RoHS Status | Following EU Directive 2011/65/EU |
Why Proax for ABB AM110-30-22-79?
Proax is an authorized distributor of ABB AM110-30-22-79 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Alternate Names | AM110302279 |
| Pack Size | 1 |