ABBOfficial Distributor

By ABB

SKU
MPN
1SFL487102R1411
Weight
1 kg
The AF190-40-11-14 is a 4 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 90 kW / 400 V AC (AC-3) / and switching power circuits up to 275 A (AC-1) or 230 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Technical Specifications

Dimensions

Product Net Width140 mm
Product Net Depth / Length153 mm
Product Net Height196 mm
Product Net Weight3.3 kg

Technical

Number of Main Contacts NO4
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC1
Rated Operational VoltageMain Circuit 1000 V
Rated Frequency (f)Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A
Rated Operational Current AC-1 (Ie)(1000 V) 40 °C 250 A
Rated Operational Current AC-1 (Ie)(1000 V) 55 °C 225 A
Rated Operational Current AC-1 (Ie)(1000 V) 60 °C 225 A
Rated Operational Current AC-1 (Ie)(1000 V) 70 °C 185 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 275 A
Rated Operational Current AC-1 (Ie)(690 V) 55 °C 250 A
Rated Operational Current AC-1 (Ie)(690 V) 60 °C 250 A
Rated Operational Current AC-1 (Ie)(690 V) 70 °C 200 A
Rated Operational Current AC-3 (Ie)(415 V) 55 °C 190 A
Rated Operational Current AC-3 (Ie)(440 V) 55 °C 190 A
Rated Operational Current AC-3 (Ie)(380 / 400 V) 55 °C 190 A
Rated Operational Current AC-3 (Ie)(220 / 230 / 240 V) 55 °C 190 A
Rated Operational Power AC-3 (Pe)(415 V) 90 kW
Rated Operational Power AC-3 (Pe)(440 V) 110 kW
Rated Operational Power AC-3 (Pe)(380 / 400 V) 90 kW
Rated Operational Power AC-3 (Pe)(220 / 230 / 240 V) 55 kW
Rated Breaking Capacity AC-38 x Ie AC-3
Rated Making Capacity AC-310 x Ie AC-3
Short-Circuit Protective DevicesgG Type Fuses 355 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 A
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Insulation Voltage (Ui)acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kV
Mechanical Durability5 million
Maximum Mechanical Switching Frequency300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)50 Hz 250 ... 500 V
Rated Control Circuit Voltage (Uc)60 Hz 250 ... 500 V
Rated Control Circuit Voltage (Uc)DC Operation 250 ... 500 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·A
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·A
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage DC 3.9 W
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage 50 Hz 260 V·A
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage 60 Hz 260 V·A
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage DC 230 W
Operate TimeBetween Coil De-energization and NO Contact Opening 45 ... 80 ms
Operate TimeBetween Coil Energization and NO Contact Closing 25 ... 60 ms
Connecting Capacity Main CircuitFlexible 2 x 50 ... 95 mm²
Connecting Capacity Main CircuitRigid Al-Cable 1 x 95 ... 185 mm²
Connecting Capacity Main CircuitRigid Cu-Cable 2 x 50 ... 120 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible 2x0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitSolid 1 x 1 ... 4 mm²
Connecting Capacity Auxiliary CircuitStranded 2 x 1 .... 4 mm²
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal TypeMain Circuit: Bars

Technical UL/CSA

Maximum Operating Voltage UL/CSAMain Circuit 1000 V
General Use Rating UL/CSA(600 V AC) 230 A
Horsepower Rating UL/CSA(200 ... 208 V AC) Three Phase 20 Hp
Horsepower Rating UL/CSA(200 V AC) Three Phase 50 hp
Horsepower Rating UL/CSA(208 V AC) Three Phase 50 hp
Horsepower Rating UL/CSA(220 ... 240 V AC) Three Phase 25 Hp
Horsepower Rating UL/CSA(220 ... 240 V AC) Three Phase 60 hp
Horsepower Rating UL/CSA(440 ... 480 V AC) Three Phase 60 Hp
Horsepower Rating UL/CSA(440 ... 480 V AC) Three Phase 125 hp
Horsepower Rating UL/CSA(550 ... 600 V AC) Three Phase 75 Hp
Horsepower Rating UL/CSA(550 ... 600 V AC) Three Phase 150 hp

Why Proax for ABB AF190-40-11-14?

Proax is an authorized distributor of ABB AF190-40-11-14 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesAF190401114
Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability