By ABB
SKU
MPN
1SFL487002R1411
Weight
3.243 kg
Series AF 3-pole Contactor Series
The AF190-30-11-14 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 90 kW / 400 V AC (AC-3) or 125 hp / 480 V UL and switching power circuits up to 275 A (AC-1) or 250 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
AF 3-pole Contactor Series
ABB's AF series includes a variety of 3-pole contactors designed for controlling 3-phase motors and power circuits. These contactors are categorized into several sub-series based on their current ratings and applications.
Each sub-series features integrated electronic coils that reduce energy consumption by up to 80%, provide surge protection, and allow operation across wide voltage ranges without coil changes. ABB also offers auxiliary contact blocks and accessories to enhance functionality
Technical Specifications
Dimensions
Product Net Width | 105 mm |
Product Net Depth / Length | 152 mm |
Product Net Height | 196 mm |
Product Net Weight | 2.4 kg |
Technical
Number of Main Contacts NO | 3 |
Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 |
Number of Auxiliary Contacts NC | 1 |
Rated Operational Voltage | Main Circuit 1000 V |
Rated Frequency (f) | Main Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A |
Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 250 A |
Rated Operational Current AC-1 (Ie) | (1000 V) 55 °C 225 A |
Rated Operational Current AC-1 (Ie) | (1000 V) 60 °C 225 A |
Rated Operational Current AC-1 (Ie) | (1000 V) 70 °C 185 A |
Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 275 A |
Rated Operational Current AC-1 (Ie) | (690 V) 55 °C 250 A |
Rated Operational Current AC-1 (Ie) | (690 V) 60 °C 250 A |
Rated Operational Current AC-1 (Ie) | (690 V) 70 °C 200 A |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 190 A |
Rated Operational Current AC-3 (Ie) | (440 V) 55 °C 190 A |
Rated Operational Current AC-3 (Ie) | (500 V) 55 °C 156 A |
Rated Operational Current AC-3 (Ie) | (690 V) 55 °C 135 A |
Rated Operational Current AC-3 (Ie) | (1000 V) 55 °C 85 A |
Rated Operational Current AC-3 (Ie) | (380 / 400 V) 55 °C 190 A |
Rated Operational Current AC-3 (Ie) | (220 / 230 / 240 V) 55 °C 190 A |
Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 190 A |
Rated Operational Current AC-3e (Ie) | (440 V) 60 °C 190 A |
Rated Operational Current AC-3e (Ie) | (500 V) 60 °C 135 A |
Rated Operational Current AC-3e (Ie) | (690 V) 60 °C 135 A |
Rated Operational Current AC-3e (Ie) | (1000 V) 60 °C 85 A |
Rated Operational Current AC-3e (Ie) | (380 / 400 V) 60 °C 190 A |
Rated Operational Current AC-3e (Ie) | (220 / 230 / 240 V) 60 °C 190 A |
Rated Operational Power AC-3 (Pe) | (415 V) 90 kW |
Rated Operational Power AC-3 (Pe) | (440 V) 110 kW |
Rated Operational Power AC-3 (Pe) | (500 V) 110 kW |
Rated Operational Power AC-3 (Pe) | (690 V) 132 kW |
Rated Operational Power AC-3 (Pe) | (1000 V) 110 kW |
Rated Operational Power AC-3 (Pe) | (380 / 400 V) 90 kW |
Rated Operational Power AC-3 (Pe) | (220 / 230 / 240 V) 55 kW |
Rated Operational Power AC-3e (Pe) | (415 V) 90 kW |
Rated Operational Power AC-3e (Pe) | (440 V) 110 kW |
Rated Operational Power AC-3e (Pe) | (500 V) 110 kW |
Rated Operational Power AC-3e (Pe) | (690 V) 132 kW |
Rated Operational Power AC-3e (Pe) | (1000 V) 110 kW |
Rated Operational Power AC-3e (Pe) | (380 / 400 V) 90 kW |
Rated Operational Power AC-3e (Pe) | (220 / 230 / 240 V) 55 kW |
Rated Breaking Capacity AC-3 | 8 x Ie AC-3 |
Rated Breaking Capacity AC-3e | 8.5 x Ie AC-3e |
Rated Making Capacity AC-3 | 10 x Ie AC-3 |
Rated Making Capacity AC-3e | 12 x Ie AC-3e |
Short-Circuit Protective Devices | gG Type Fuses 355 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2200 A |
Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
Maximum Electrical Switching Frequency | (AC-2 / AC-4) 150 cycles per hour |
Maximum Electrical Switching Frequency | (AC-3) 300 cycles per hour |
Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 250 A |
Rated Operational Current DC-1 (Ie) | (220 V) 3 Poles in Series, 40 °C 250 A |
Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 250 A |
Rated Operational Current DC-3 (Ie) | (220 V) 3 Poles in Series, 40 °C 250 A |
Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 250 A |
Rated Operational Current DC-5 (Ie) | (220 V) 3 Poles in Series, 40 °C 250 A |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
Rated Insulation Voltage (Ui) | acc. to UL/CSA 600 V |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kV |
Mechanical Durability | 5 million |
Maximum Mechanical Switching Frequency | 300 cycles per hour |
Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
Rated Control Circuit Voltage (Uc) | 50 Hz 250 ... 500 V |
Rated Control Circuit Voltage (Uc) | 60 Hz 250 ... 500 V |
Rated Control Circuit Voltage (Uc) | DC Operation 250 ... 500 V |
Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·A |
Coil Consumption | Holding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·A |
Coil Consumption | Holding at Max. Rated Control Circuit Voltage DC 3.9 W |
Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 260 V·A |
Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 260 V·A |
Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage DC 230 W |
Operate Time | Between Coil De-energization and NO Contact Opening 37 ... 47 ms |
Operate Time | Between Coil Energization and NO Contact Closing 25 ... 55 ms |
Connecting Capacity Main Circuit | Flexible 2 x 50 ... 95 mm² |
Connecting Capacity Main Circuit | Rigid Al-Cable 1 x 95 ... 185 mm² |
Connecting Capacity Main Circuit | Rigid Cu-Cable 1 x 6 ... 150 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² |
Connecting Capacity Auxiliary Circuit | Flexible 2x0.75 ... 2.5 mm² |
Connecting Capacity Auxiliary Circuit | Solid 2 x 1 ... 4 mm² |
Connecting Capacity Auxiliary Circuit | Stranded 2 x 1 .... 4 mm² |
Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
Terminal Type | Main Circuit: Bars |
Technical UL/CSA
Maximum Operating Voltage UL/CSA | Main Circuit 1000 V |
General Use Rating UL/CSA | (600 V AC) 250 A |
Horsepower Rating UL/CSA | (200 V AC) Three Phase 50 hp |
Horsepower Rating UL/CSA | (208 V AC) Three Phase 50 hp |
Horsepower Rating UL/CSA | (220 ... 240 V AC) Three Phase 60 hp |
Horsepower Rating UL/CSA | (440 ... 480 V AC) Three Phase 125 hp |
Horsepower Rating UL/CSA | (550 ... 600 V AC) Three Phase 150 hp |
Why Proax for ABB AF190-30-11-14?
Proax is an authorized distributor of ABB AF190-30-11-14 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | AF190301114 |
Pack Size | 1 |
Recommended