MPN
1SFL647001R6911
Weight
16.671 kg
The AF1250-30-11-69 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, switching power circuits up to 1260 A (AC-1) or 1210 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

AF 3-pole Contactor Series

ABB's AF series includes a variety of 3-pole contactors designed for controlling 3-phase motors and power circuits. These contactors are categorized into several sub-series based on their current ratings and applications.

Each sub-series features integrated electronic coils that reduce energy consumption by up to 80%, provide surge protection, and allow operation across wide voltage ranges without coil changes. ABB also offers auxiliary contact blocks and accessories to enhance functionality

Technical Specifications

Dimensions

Product Net Width210 mm
Product Net Depth / Length242 mm
Product Net Height344 mm
Product Net Weight14.6 kg

Technical

Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC1
Rated Operational VoltageMain Circuit 1000 V
Rated Frequency (f)Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1050 A
Rated Operational Current AC-1 (Ie)(1000 V) 40 °C 1260 A
Rated Operational Current AC-1 (Ie)(1000 V) 55 °C 1040 A
Rated Operational Current AC-1 (Ie)(1000 V) 70 °C 875 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 1260 A
Rated Operational Current AC-1 (Ie)(690 V) 55 °C 1040 A
Rated Operational Current AC-1 (Ie)(690 V) 70 °C 875 A
Rated Breaking Capacity AC-38 x Ie AC-3
Rated Making Capacity AC-310 x Ie AC-3
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 7200 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1500 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 4000 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 8000 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 5200 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 7500 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 7000 A
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Rated Operational Current DC-1 (Ie)(220 V) 3 Poles in Series, 40 °C 1250 A
Rated Operational Current DC-1 (Ie)(600 V) 3 Poles in Series, 40 °C 1250 A
Rated Operational Current DC-1 (Ie)(850 V) 3 Poles in Series, 40 °C 1250 A
Rated Operational Current DC-3 (Ie)(220 V) 3 Poles in Series, 40 °C 1250 A
Rated Operational Current DC-3 (Ie)(600 V) 3 Poles in Series, 40 °C 1250 A
Rated Operational Current DC-3 (Ie)(850 V) 3 Poles in Series, 40 °C 1250 A
Rated Operational Current DC-5 (Ie)(220 V) 3 Poles in Series, 40 °C 1250 A
Rated Operational Current DC-5 (Ie)(600 V) 3 Poles in Series, 40 °C 1250 A
Rated Operational Current DC-5 (Ie)(850 V) 3 Poles in Series, 40 °C 1250 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Insulation Voltage (Ui)acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kV
Mechanical Durability0.5 million
Maximum Mechanical Switching Frequency300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)50 Hz 48 ... 130 V
Rated Control Circuit Voltage (Uc)60 Hz 48 ... 130 V
Rated Control Circuit Voltage (Uc)DC Operation 48 ... 130 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage DC 5 V·A
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage 50 Hz 1100 V·A
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage 60 Hz 1100 V·A
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage DC 1020 V·A
Operate TimeBetween Coil De-energization and NC Contact Closing 50 ... 70 ms
Operate TimeBetween Coil De-energization and NO Contact Opening 53 ... 73 ms
Operate TimeBetween Coil Energization and NC Contact Opening 45 ... 115 ms
Operate TimeBetween Coil Energization and NO Contact Closing 50 ... 120 ms
Connecting Capacity Main CircuitBar 50 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible 2x0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitSolid 2 x 1 ... 4 mm²
Connecting Capacity Auxiliary CircuitStranded 1 x 1 .... 4 mm²
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Connecting Terminals (delivered in open position) Main PolesM 3.5 (+,-) pozidriv 2 screw with cable clamp
Terminal TypeMain Circuit: Bars

Technical UL/CSA

Horsepower Rating NEMA(230 V AC) Three Phase 300 Hp
Horsepower Rating NEMA(460 V AC) Three Phase 600 Hp
Horsepower Rating NEMA(575 V AC) Three Phase 600 Hp
Maximum Operating Voltage UL/CSAMain Circuit 1000 V
General Use Rating UL/CSA(1000 V AC) 1210 A

Why Proax for ABB AF1250-30-11-69?

Proax is an authorized distributor of ABB AF1250-30-11-69 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesAF1250301169
Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability