Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
PLC-RPT-230UC/21-21/SO46
Weight
0.073 kg
Series PLC-RPT

PLC-RPT-230UC/21-21/SO46 - Relay Module

PLC-INTERFACE for protection against interference currents or interference voltages on the control side. Consisting of basic terminal block with Push-in connection and plug-in miniature relay with power contact, 2 changeover contacts, 230 V AC input voltage

Technical Specifications

Notes

Notes on operationThe PLC-ATP partition plate must be installed for voltages greater than 250 V (L1, L2, L3) between identical terminal blocks on adjacent modules.
Notes on operationThe PLC-ATP separating plate should be installed for safe isolation between adjacent modules
Notes on operationThe system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
Assembly instruction:The PLC-ATP separating plate is required at the start and end of every PLC terminal strip.

Product properties

Product familyPLC-INTERFACE
ApplicationFilter to prevent interference
Operating mode100% operating factor
Mechanical service lifeapprox. 3x 107 cycles

Insulation characteristics

InsulationBasic insulation

Insulation characteristics: Air clearances and creepage distances between the power circuits

InsulationBasic insulation
Overvoltage categoryIII
Pollution degree3

Electrical properties

Maximum power dissipation for nominal condition2.3 W
Test voltage (Winding/contact)4 kVrms (50 Hz, 1 min., winding/contact)

Air clearances and creepage distances between the power circuits

Rated Insulation Voltage250 V AC
Rated surge voltage4 kV (Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths)

Coil side

Nominal input voltage UN230 V AC
Nominal input voltage UN220 V DC
Input voltage range179.4 V AC ... 264.5 V AC (20 °C)
Input voltage range171.6 V DC ... 253 V DC (20 °C)
Mains frequency50/60 Hz
Drive and functionmonostable
Drive (polarity)polarized
Typical input current at UN8.5 mA (50 Hz)
Typical input current at UN10 mA (60 Hz)
Typical response time7 ms
Typical release time10 ms
Typical release voltage60 V AC
Coil Voltage110 V DC
Protective circuitRC element
Protective circuitBridge rectifier
Status displayYellow LED

Switching

Contact switching type2 changeover contacts
Type of switch contactSingle contact
Contact MaterialAgNi
Maximum Switching Voltage250 V AC/DC
Minimum Switching Voltage5 V (10 mA)
Limiting Continuous Current6 A
Maximum Inrush Current15 A (300 ms)
Min. switching current10 mA (5 V)
Interrupting rating (ohmic load) max.144 W (24 V DC)
Interrupting rating (ohmic load) max.96 W (48 V DC)
Interrupting rating (ohmic load) max.60 W (60 V DC)
Interrupting rating (ohmic load) max.44 W (110 V DC)
Interrupting rating (ohmic load) max.57 W (220 V DC)
Interrupting rating (ohmic load) max.1500 VA (250 V AC)
Switching capacity min.0.12 W
Switching capacity2 A (DC13, 24 V)
Switching capacity0.2 A (DC13, 250 V)
Switching capacity3 A (AC15, 24 V)
Switching capacity3 A (AC15, 250 V)

Connection data

Connection MethodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.14 mm² ... 2.5 mm²
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm² (Single ferrule)
Conductor cross section flexible2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG26 ... 14

Dimensions

Width14 mm
Height80 mm
Depth94 mm

Material specifications

Colorgray (RAL 7042)

Ambient conditions

Degree of protection (Relay base)IP20 (Relay base)
Degree of protection (Relay)RT III (Relay)
Degree of protection (Installation location)IP54 (Installation location)
Ambient Temperature (Operation)-40 °C ... 55 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m

CE

CertificateCE-compliant

UKCA

CertificateUKCA-compliant

Shipbuilding approval

CertificateTAE0000196

Corrosive gas test

IdentificationISA-S71.04. G3 Harsh Group
IdentificationEN 60068-2-60

DNV GL data

TemperatureD
HumidityA
VibrationB/C
EMCB
EnclosureRequired protection according to the Rules shall be provided upon installation on board

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive
Electromagnetic compatibilityConformance with EMC directive

Air clearances and creepage distances between the power circuits

Standards/regulationsIEC 60947-5-1

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsin rows with zero spacing
Mounting Positionany

Why Proax for Phoenix Contact 1136245?

Proax is an authorized distributor of Phoenix Contact 1136245 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability