
SKU
MPN
PTVFIX 6/18X2,5-NS35A BK
Weight
0.04 kg
Series PTVFIX
PTVFIX 6/18X2,5-NS35A BK - Distribution block
Distribution block, nom. voltage: 690 V, nominal current: 24 A, number of connections: 19, number of positions: 1, connection method: Push-in connection, Load contact, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, Line contact, Rated cross section: 6 mm2, cross section: 0.5 mm2 - 10 mm2, mounting type: NS 35/7,5, NS 35/15, color: black
- Flexible use, thanks to DIN rail mounting, direct mounting or adhesive mounting
- Clear wiring, thanks to eleven different color variants
- Time-saving conductor connection, thanks to tool-free Push-in direct connection technology
- Time savings of up to 80 %, thanks to ready-to-mount blocks without manual bridging
- Space savings of up to 50 % on the DIN rail, thanks to transverse mounting
Technical Specifications
General
Note | The maximum load current of a single clamping unit must not be exceeded. |
Note | For power distribution applications, IEC 60364-4-43.2008; modified + corrigendum Okt. 2008 (DIN VDE 0100-430:2010-10) section 433.2 ff must be observed! |
Product properties
Number of Positions | 1 |
Number of Connections | 19 |
Number of rows | 1 |
Potentials | 1 |
Insulation characteristics
Overvoltage category | III |
Degree of pollution | 3 |
Electrical properties
Rated surge voltage | 8 kV |
Maximum power dissipation for nominal condition | 0.77 W |
Connection data
Service Entrance | yes |
Number of connections per level | 19 |
Nominal cross section | 2.5 mm² |
Load contact
Stripping length | 8 mm ... 10 mm |
Internal cylindrical gage | A3 |
Internal cylindrical gage | B3 |
Connection in acc. with standard | IEC 60947-7-1 |
Conductor cross section rigid | 0.14 mm² ... 4 mm² |
Cross section AWG | 26 ... 12 (converted acc. to IEC) |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section, flexible [AWG] | 26 ... 14 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve) | 0.5 mm² |
Nominal Current | 24 A |
Maximum Load Current | 32 A (with 4 mm² conductor cross section) |
Maximum total current | 57 A (with 10 mm² conductor cross section) |
Nominal Voltage | 690 V |
Note | The IEC 60947-7-1 standard applies for the use of mounting accessories. |
Nominal cross section | 2.5 mm² |
Line contact
Stripping length | 10 mm ... 12 mm |
Internal cylindrical gage | A5 |
Internal cylindrical gage | B4 |
Conductor cross section rigid | 0.5 mm² ... 10 mm² |
Cross section AWG | 20 ... 8 (converted acc. to IEC) |
Conductor cross section flexible | 0.5 mm² ... 6 mm² |
Conductor cross section, flexible [AWG] | 20 ... 10 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 6 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 6 mm² |
Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve) | 0.5 mm² ... 1.5 mm² |
Nominal Current | 41 A (with 6 mm² conductor cross section) |
Maximum Load Current | 57 A (with 10 mm² conductor cross section) |
Maximum total current | The maximum load current of the individual terminal point must not be exceeded. |
Nominal cross section | 6 mm² |
Connection in acc. with standard | IEC 60998-2-2 |
Nominal Voltage | 450 V (in accordance with IEC 60998-2-2) |
Load contact Connection cross sections directly pluggable
Conductor cross section rigid | 0.34 mm² ... 4 mm² |
Conductor cross section, rigid [AWG] | 22 ... 18 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.34 mm² ... 2.5 mm² |
Line contact Connection cross sections directly pluggable
Conductor cross section rigid | 1 mm² ... 10 mm² |
Conductor cross section, rigid [AWG] | 18 ... 8 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 1 mm² ... 6 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 1 mm² ... 6 mm² |
Dimensions
Width | 56.9 mm |
Height | 45.7 mm |
Depth | 29.2 mm |
Depth on NS 35/7,5 | 30.9 mm |
Material specifications
Color | black |
Flammability rating according to UL 94 | V0 |
Insulating material group | I |
Insulating material | PA |
Static insulating material application in cold | -60 °C |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Surge voltage test
Result | Test passed |
Temperature-rise test
Requirement temperature-rise test | Increase in temperature ≤ 45 K |
Result | Test passed |
Short-time withstand current 6 mm² | 0.72 kA |
Short-time withstand current 10 mm² | 1.2 kA |
Result | Test passed |
Power-frequency withstand voltage
Test voltage setpoint | 1.89 kV |
Result | Test passed |
Mechanical data
Open side panel | No |
Mechanical strength
Result | Test passed |
Attachment on the carrier
DIN rail/fixing support | NS 35 |
Result | Test passed |
Note | When aligning several blocks, it is recommended to either place a DIN rail adapter underneath the connection point or a flange element between the blocks. |
Note | For versions with 6 or 7 connections, it is enough to place one DIN rail adapter centrally per block and place flange elements after every other block. |
Note | Depending on the application case and mechanical load, other arrangements of the mounting accessory can also be chosen. |
Note | When using the DIN rail adapter PTFIX-NS35, an aligned block must not protrude by more than a half. |
Test for conductor damage and slackening
Rotation speed | 10 rpm |
Revolutions | 135 |
Conductor cross section/weight | 0.5 mm² / 0.3 kg |
Conductor cross section/weight | 6 mm² / 1.4 kg |
Conductor cross section/weight | 10 mm² / 2 kg |
Result | Test passed |
Aging
Temperature cycles | 192 |
Result | Test passed |
Needle-flame test
Time of exposure | 30 s |
Result | Test passed |
Oscillation/broadband noise
Specification | DIN EN 50155 (VDE 0115-200):2018-05 |
Spectrum | Service life test category 2, bogie-mounted |
Frequency | f1 = 5 Hz to f2 = 250 Hz |
ASD level | 6.12 (m/s²)²/Hz |
Acceleration | 3.12g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Result | Test passed |
Shocks
Specification | DIN EN 50155 (VDE 0115-200):2018-05 |
Pulse shape | Half-sine |
Acceleration | 30g |
Shock duration | 18 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Result | Test passed |
Ambient conditions
Ambient Temperature (Operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, no longer than 24 h, -60°C to +70°C) |
Ambient temperature (assembly) | -5 °C ... 70 °C |
Ambient temperature (actuation) | -5 °C ... 70 °C |
Permissible humidity (operation) | 20 % ... 90 % |
Permissible humidity (storage/transport) | 30 % ... 70 % |
Standards and Regulations
Connection in acc. with standard | IEC 60947-7-1 |
Connection in acc. with standard | IEC 60998-2-2 |
Mounting
Mounting Type | NS 35/7,5 |
Mounting Type | NS 35/15 |
Why Proax for Phoenix Contact 1019562?
Proax is an authorized distributor of Phoenix Contact 1019562 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 10 |
Recommended
- PTVFIX 6/12X2,5-NS35A GN - Distribution block, nom. voltage: 690 V, nominal current: 24 A, number of connections: 13, number of positions: 1, connection method: Push-in connection, Load contact, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, Line contact, Rated cross section: 6 mm2, cross section: 0.5 mm2 - 10 mm2, mounting type: NS 35/7,5, NS 35/15, color: green
- Distribution block, nom. voltage: 450 V, nominal current: 24 A, number of connections: 7, number of positions: 1, connection method: Push-in connection, Load contact, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, Line contact, Rated cross section: 6 mm2, cross section: 0.5 mm2 - 10 mm2, mounting type: for snapping onto a DIN rail adapter, Direct mounting with flange, Free-hanging, color: gray
- PTVFIX 2,5/5 - Device terminal block, nom. voltage: 450 V, number of connections: 10, number of positions: 5, connection method: Push-in connection, Push-in connection, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, mounting type: for snapping onto a DIN rail adapter, Direct mounting with flange, Free-hanging, color: gray
- PTVFIX 6X2,5 RD - Distribution block, nom. voltage: 450 V, nominal current: 24 A, number of connections: 6, number of positions: 1, connection method: Push-in connection, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, mounting type: for snapping onto a DIN rail adapter, Direct mounting with flange, Free-hanging, color: red