Official Distributor
SKU
Weight
0.888 kg
Series UNO2-PS
UNO2-PS/1AC/48DC/240W - Power supply unit
Primary-switched power supply unit, UNO POWER, Screw connection, DIN rail mounting, input: 1-phase, output: 48 V DC / 5 A, adjustable from 42 V DC ... 56 V DC
- Save space in the control cabinet with an extremely narrow overall width of just 45 mm
- Save energy, thanks to a high degree of efficiency
- Outdoor installation possible, with a wide temperature range of -25°C … +70°C
- Simple output voltage monitoring, thanks to the floating DC OK relay contact
Technical Specifications
AC operation
Supply system configuration | Star network (TN, TT, IT (PE)) |
Nominal input voltage range | 100 V AC ... 240 V AC |
Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
Derating | < 90 V AC (1 %/V) |
Typical national grid voltage | 120 V AC |
Typical national grid voltage | 230 V AC |
Voltage type of supply voltage | AC |
Inrush Current | typ. 10 A (at 25 °C) |
Inrush current integral (I2t) | < 0.05 A2s |
Frequency range (fN) | 50 Hz ... 60 Hz ±10 % |
Mains buffering time | typ. 20 ms (120 V AC) |
Mains buffering time | typ. 20 ms (230 V AC) |
Current consumption | 2.6 A (100 V AC) |
Current consumption | 2.2 A (120 V AC) |
Current consumption | 1.16 A (230 V AC) |
Current consumption | 1.2 A (240 V AC) |
Protective circuit | Transient surge protection; Varistor, gas-filled surge arrester |
Switch-on time | typ. 530 ms |
Device mains fuse | 5 A internal (device protection), fast-blow |
Recommended breaker for input protection | 10 A ... 16 A (Characteristic B, C, D, K or comparable) |
Discharge current to PE | < 3.5 mA |
Output data
Efficiency | typ. 91.5 % (120 V AC) |
Efficiency | typ. 93 % (230 V AC) |
Nominal Output Voltage | 48 V DC |
Setting range of the output voltage (USet) | 42 V DC ... 56 V DC (≥48 V DC, constant capacity restricted<48 V DC, constant current restricted) |
Nominal output current (IN) | 5 A |
Short-circuit-proof | yes |
No-load proof | yes |
Crest factor | typ. 1.637 (120 V AC) |
Crest factor | typ. 1.54 (230 V AC) |
Output power (PN) | 240 W |
Connection in parallel | yes, for redundancy |
Connection in series | yes, for increased output voltage |
Feedback voltage resistance | ≤ 60 V DC |
Protection against overvoltage at the output (OVP) | ≤ 60 V DC |
Residual ripple | typ. 50 mVPP (with nominal values) |
Control deviation | < 1 % (change in load, static 10 % ... 90 %) |
Control deviation | < 3 % (change in load, dynamic 10 % ... 90 %) |
Control deviation | < 0.1 % (change in input voltage ±10 %) |
Rise time | < 1 s (UOut = 10 % ... 90 %) |
Minimum no-load power dissipation | < 2.9 W (120 V AC) |
Maximum no-load power dissipation | < 3 W (230 V AC) |
Minimum nominal load power dissipation | < 23 W (120 V AC) |
Power loss nominal load max. | < 19 W (230 V AC) |
Signal relay 13/14
Connection level | 3.x |
Connection labeling | 3.1 (13), 3.2 (14) |
Switch contact (floating) | OptoMOS |
Switching voltage | max. 30 V AC/DC |
Switching voltage | max. 60 V DC |
Current carrying capacity | max. 50 mA |
State condition | UOUT ≥ 0.9 x UN (UN = 48 V DC) (Contact closed) |
State condition | UOUT < 42 V DC (Contact open) |
State condition | UOUT > 60 V DC (Contact open) |
Input
Position | 1.x |
Identification | 1.1 (), 1.2 (L), 1.3 (N) |
Conductor connection
Connection Method | Screw connection |
rigid | 0.2 mm² ... 2.5 mm² |
flexible | 0.2 mm² ... 2.5 mm² |
flexible with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
flexible with ferrule with plastic sleeve | 0.25 mm² ... 2.5 mm² |
rigid (AWG) | 24 ... 14 (Cu) |
Stripping length | 6.5 mm |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Tightening torque | 4 lbf-in. ... 5 lbf-in. |
Drive form screw head | Slotted L |
Output
Position | 2.x |
Identification | 2.1, 2.2 (+), 2.3, 2.4 (-) |
Conductor connection
Connection Method | Screw connection |
rigid | 0.2 mm² ... 2.5 mm² |
flexible | 0.2 mm² ... 2.5 mm² |
flexible with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
flexible with ferrule with plastic sleeve | 0.25 mm² ... 2.5 mm² |
rigid (AWG) | 24 ... 14 (Cu) |
Stripping length | 6.5 mm |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Tightening torque | 4 lbf-in. ... 5 lbf-in. |
Drive form screw head | Slotted L |
Signal
Position | 3.x |
Identification | 3.1 (13), 3.2 (14) |
Conductor connection
Connection Method | Screw connection |
rigid | 0.2 mm² ... 2.5 mm² |
flexible | 0.2 mm² ... 2.5 mm² |
flexible with ferrule without plastic sleeve | 0.25 mm² ... 2.5 mm² |
flexible with ferrule with plastic sleeve | 0.25 mm² ... 2.5 mm² |
rigid (AWG) | 24 ... 14 (Cu) |
Stripping length | 6.5 mm |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Tightening torque | 4 lbf-in. ... 5 lbf-in. |
Drive form screw head | Slotted L |
LED signaling
Types of signaling | DC OK LED - signal state operation (UN = 48 V DC, IOut = IN) |
Function | Visual operating state display |
Color | green |
LED off | Supply voltage input AC not present (Off) |
LED on (green), DC OK | UOUT ≥ 0.9 x UN (UN = 48 V DC) (On (green), DC OK) |
LED on (flashing green) DC OK < 0.9 x UN | UOUT > 60 V DC (on (flashing green)) |
Electrical properties
Number of phases | 1.00 |
Insulation voltage input/output | 4 kV AC (type test) |
Insulation voltage input/output | 3 kV AC (routine test) |
Insulation voltage input / PE | 3.5 kV AC (type test) |
Insulation voltage input / PE | 2.4 kV AC (routine test) |
Product properties
Product family | UNO POWER |
MTBF (IEC 61709, SN 29500) | > 1000000 h (25 °C) |
MTBF (IEC 61709, SN 29500) | > 550000 h (40 °C) |
MTBF (IEC 61709, SN 29500) | > 280000 h (55 °C) |
Environmental protection directive | RoHS Directive 2011/65/EU |
Environmental protection directive | WEEE |
Environmental protection directive | Reach |
Insulation characteristics
Protection class | I |
Degree of pollution | 2 |
Item dimensions
Width | 45 mm |
Height | 130 mm |
Depth | 129 mm |
Depth | 125 mm (Device depth (DIN rail mounting)) |
Installation dimensions
Installation distance right/left (active, passive) | 0 mm / 0 mm (POut ≥50% ) |
Installation distance top/bottom (active, passive) | 30 mm / 30 mm (POut ≥50% ) |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | alignable: 0 mm horizontally, 30 mm vertically |
Mounting Position | horizontal DIN rail NS 35, EN 60715 |
With protective coating | No |
Material specifications
Flammability rating according to UL 94 | V0 (Housing, terminal blocks) |
Housing Material | Metal |
Housing Material | Aluminum (AlMg3) / sheet steel, zinc-plated |
Hood version | Stainless steel |
Side element version | Aluminum |
Foot latch material | Sheet steel, zinc-plated |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -40 °C |
Maximum altitude | ≤ 3000 m (> 2000 m, Derating: 10 %/1000 m) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock (operation) | 18 ms, 30g, per spatial direction (IEC 60068-2-27) |
Vibration (Operation) | 10 Hz ... 50 Hz, amplitude ±0.2 mm |
Vibration (Operation) | 50 Hz to 150 Hz, 2.3 g, 90 min. |
Overvoltage category
EN 61010-1 | II (≤ 3000 m) |
EN 62477-1 | III (≤3000 m) |
Safety of power supply units up to 1100 V (insulation distances)
Standard designation | Safety of power supply units up to 1100 V (insulation distances) |
Standards/specifications | DIN EN 61558-2-16 |
Electrical safety
Standard designation | Electrical safety |
Standards/specifications | IEC 61010-2-201 (SELV) |
Electronic equipment for use in power installations
Standard designation | Equipping high voltage installations with electronic equipment |
Standards/specifications | EN 50178/VDE 0160 (PELV) |
Safety for measurement, control, and laboratory equipment
Standard designation | Safety for equipment for measurement, control, and laboratory use |
Standards/specifications | IEC 61010-1 |
Protective extra-low voltage
Standard designation | Protective extra-low voltage |
Standards/specifications | IEC 61010-1 (SELV) |
Standards/specifications | IEC 61010-2-201 (PELV) |
Safe isolation
Standard designation | Safe isolation |
Standards/specifications | IEC 61558-2-16 |
Standards/specifications | IEC 61010-2-201 |
Limitation of harmonic line currents
Standard designation | Limitation of harmonic line currents |
Standards/specifications | EN 61000-3-2 |
Mains voltage dips
Standard designation | Requirement of the semiconductor industry with regard to mains voltage dips |
Standards/specifications | SEMI F47 - 0706 (185 V AC) |
UL
Identification | UL/C-UL Listed UL 61010-1 |
Identification | UL/C-UL Listed UL 61010-2-201 |
Identification | UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
SIQ
Identification | CB scheme (IEC 61010-1, IEC 61010-2-201) |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Interference emission | Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
EMC requirements for noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Conducted noise emission | EN 55016 |
Conducted noise emission | EN 61000-6-3 (Class B) |
Noise emission | EN 55016 |
Noise emission | EN 61000-6-3 (Class B) |
Harmonic currents
Standards/regulations | EN 61000-3-2 |
Standards/regulations | EN 61000-3-2 (Class A) |
Frequency Range | 0 kHz ... 2 kHz |
Flicker
Standards/regulations | EN 61000-3-3 |
Frequency Range | 0 kHz ... 2 kHz |
Electrostatic discharge
Standards/regulations | EN 61000-4-2 |
Contact discharge | 6 kV (Test Level 3) |
Discharge in air | 8 kV (Test Level 3) |
Comments | Criterion A |
Electromagnetic HF field
Standards/regulations | EN 61000-4-3 |
Frequency Range | 80 MHz ... 1 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency Range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst)
Standards/regulations | EN 61000-4-4 |
Input | 4 kV (Test Level 4 - asymmetrical) |
Output | 2 kV (Test Level 3 - asymmetrical) |
Comments | Criterion A |
Surge voltage load (surge)
Standards/regulations | EN 61000-4-5 |
Input | 1 kV (Test Level 3 - symmetrical) |
Input | 2 kV (Test Level 3 - asymmetrical) |
Output | 0.5 kV (Test Level 2 - symmetrical) |
Output | 1 kV (Test Level 2 - asymmetrical) |
Comments | Criterion B |
Conducted interference
Standards/regulations | EN 61000-4-6 |
Input/Output | asymmetrical |
Frequency Range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Voltage dips
Standards/regulations | EN 61000-4-11 |
Voltage | 230 V AC |
Frequency | 50 Hz |
Voltage dip | 70 % |
Number of periods | 25 / 30 periods |
Comments | Criterion A |
Voltage dip | 40 % |
Number of periods | 12 periods |
Additional text | Test Level 2 |
Comments | Criterion A |
Voltage dip | 0 % |
Number of periods | 1 period |
Additional text | Test Level 2 |
Comments | Criterion B |
Criteria
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Why Proax for Phoenix Contact 1110155?
Proax is an authorized distributor of Phoenix Contact 1110155 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended