The VB7-30-10-P mini reversing contactor is a compact 3 pole contactor with 1 auxiliary contact, soldering pins and normal mechanical interlock. They are ideally suited for applications where reliability is a must and space is at a premium. Mini reversing contactors are used in residential buldings, commercial buildings and industrial applications for the control of three-phase motor loads up to 5.5 kW (AC-3). Further features are the silent coil, a switch position indication and the integrated possibility for rail mounting.
Technical Specifications

Dimensions

Product Net Width96.2 mm
Product Net Depth / Length47.7 mm
Product Net Height57.5 mm
Product Net Weight0.345 kg
Dimension DiagramGJL1200449F0001

Technical

Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC0
Number of Poles3P
StandardsIEC/EN 60947-1
StandardsIEC/EN 60947-4-1
StandardsIEC/EN 60947-5-1
StandardsUL 60947-1
StandardsUL 60947-4-1
StandardsIEC 60335-2-40 A2L
Rated Operational VoltageAuxiliary Circuit 690 V AC
Rated Operational VoltageAuxiliary Circuit 250 V DC
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational VoltageMain Circuit 220 V DC
Rated Frequency (f)Main Circuit 60 Hz
Rated Frequency (f)Main Circuit 50 Hz
Rated Frequency (f)Main Circuit DC
Conventional Free-air Thermal Current (Ith)Main Circuit 12 A
Rated Operational Current AC-1 (Ie)(220 / 240 V) 40 °C 12 A
Rated Operational Current AC-1 (Ie)(220 / 240 V) 55 °C 12 A
Rated Operational Current AC-1 (Ie)(380 / 440 V) 40 °C 12 A
Rated Operational Current AC-1 (Ie)(380 / 440 V) 55 °C 12 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 6 A
Rated Operational Current AC-1 (Ie)(690 V) 55 °C 6 A
Rated Operational Current AC-3 (Ie)(230 V) 55°C 12 A
Rated Operational Current AC-3 (Ie)(400 V) 55 °C 12 A
Rated Operational Current AC-3 (Ie)(500 V) 55 °C 9 A
Rated Operational Current AC-3 (Ie)(690 V) NO 55°C 3.5 A
Rated Operational Power AC-3 (Pe)(230 V) Three Phase 3 kW
Rated Operational Power AC-3 (Pe)(400 V) Three Phase 5.5 kW
Rated Operational Power AC-3 (Pe)(500 V) Three Phase 5.5 kW
Rated Operational Power AC-3 (Pe)(690 V) Three Phase, NO 3 kW
Rated Breaking Capacity AC-38 x Ie / AC-3
Rated Making Capacity AC-310 x Ie / AC-3
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Rated Insulation Voltage (Ui)690 V
Rated Insulation Voltage (Ui)acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)Main Circuit 6 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Maximum Electrical Switching Frequency(AC-15) 600 cycles per hour
Maximum Electrical Switching Frequency(AC-3) 600 cycles per hour
Maximum Electrical Switching Frequency(DC-1) 600 cycles per hour
Maximum Electrical Switching Frequency(DC-13) 600 cycles per hour
Maximum Electrical Switching Frequency(DC-3) 600 cycles per hour
Mechanical DurabilityNr. Operations 10000000 cycle
Minimum switching capacityAuxiliary Circuit 17 V
Minimum switching capacityAuxiliary Circuit 5 mA
Coil Operating Limits(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Rated Control Circuit Voltage (Uc)220 ... 240 V AC
Coil ConsumptionAverage Holding Value 50 Hz 3.5 V·A
Coil ConsumptionAverage Pull-in Value 50 Hz 3.5 V·A
Power Lossat Rated Operating Conditions AC-1 per Pole 1.4 W
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting on DIN RailTH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Degree of ProtectionMain Circuit Terminals IP20
Terminal TypeSoldering Pins
Product NameMini Reversing Contactor

Technical UL/CSA

Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
General Use Rating UL/CSA(600 V AC) 12 A
Horsepower Rating UL/CSA(115 V AC) Single Phase 0.75 Hp
Horsepower Rating UL/CSA(200 V AC) Three Phase 2 Hp
Horsepower Rating UL/CSA(220 ... 240 V AC) Three Phase 3 Hp
Horsepower Rating UL/CSA(230 V AC) Single Phase 1.5 Hp
Horsepower Rating UL/CSA(440 ... 480 V AC) Three Phase 5 Hp
Horsepower Rating UL/CSA(550 ... 600 V AC) Three Phase 5 Hp
Contact Rating UL/CSAA600
Full Load Amps Motor Use(115 V AC) Single Phase 13.8 A
Full Load Amps Motor Use(200 V AC) Three Phase 7.8 A
Full Load Amps Motor Use(220 ... 240 V AC) Three Phase 9.6 A
Full Load Amps Motor Use(230 V AC) Single Phase 10 A
Full Load Amps Motor Use(440 ... 480 V AC) Three Phase 7.6 A
Full Load Amps Motor Use(550 ... 600 V AC) Three Phase 6.1 A

ABB EcoSolutions

End Of Life Disassembling Instructions1SBC100156C0270
Environmental Product Declaration - EPD1SAC200410H0001

Why Proax for ABB VB7-30-10-P-80?

Proax is an authorized distributor of ABB VB7-30-10-P-80 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate NamesVB73010P80
Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability