VB7-30-10-80
By ABB
SKU
ABBVB7301080
MPN
GJL1311901R8100
Weight
0.355 kg
The VB7-30-10 mini reversing contactor is a compact 3 pole contactor with 1 auxiliary contact, screw terminals and normal mechanical interlock. They are ideally suited for applications where reliability is a must and space is at a premium. Mini reversing contactors are used in residential buldings, commercial buildings and industrial applications for the control of three-phase motor loads up to 5.5 kW (AC-3). Further features are the silent coil, a switch position indication and the integrated possibility for rail or wall mounting.
Technical Specifications
Dimensions
Product Net Width | 96.2 mm |
Product Net Depth / Length | 46.7 mm |
Product Net Height | 57.5 mm |
Product Net Weight | 0.355 kg |
Dimension Diagram | GJL1200447F0001 |
Technical
Number of Main Contacts NO | 3 |
Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 |
Number of Auxiliary Contacts NC | 0 |
Number of Poles | 3P |
Standards | IEC/EN 60947-1 |
Standards | IEC/EN 60947-4-1 |
Standards | IEC/EN 60947-5-1 |
Standards | UL 60947-1 |
Standards | UL 60947-4-1 |
Standards | IEC 60335-2-40 A2L |
Rated Operational Voltage | Auxiliary Circuit 690 V AC |
Rated Operational Voltage | Auxiliary Circuit 250 V DC |
Rated Operational Voltage | Main Circuit 690 V AC |
Rated Operational Voltage | Main Circuit 220 V DC |
Rated Frequency (f) | Main Circuit 60 Hz |
Rated Frequency (f) | Main Circuit 50 Hz |
Rated Frequency (f) | Main Circuit DC |
Conventional Free-air Thermal Current (Ith) | Main Circuit 20 A |
Rated Operational Current AC-1 (Ie) | (220 / 240 V) 40 °C 20 A |
Rated Operational Current AC-1 (Ie) | (220 / 240 V) 55 °C 16 A |
Rated Operational Current AC-1 (Ie) | (380 / 440 V) 40 °C 20 A |
Rated Operational Current AC-1 (Ie) | (380 / 440 V) 55 °C 16 A |
Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 6 A |
Rated Operational Current AC-1 (Ie) | (690 V) 55 °C 6 A |
Rated Operational Current AC-3 (Ie) | (230 V) 55°C 12 A |
Rated Operational Current AC-3 (Ie) | (400 V) 55 °C 12 A |
Rated Operational Current AC-3 (Ie) | (500 V) 55 °C 9 A |
Rated Operational Current AC-3 (Ie) | (690 V) NO 55°C 3.5 A |
Rated Operational Power AC-3 (Pe) | (230 V) Three Phase 3 kW |
Rated Operational Power AC-3 (Pe) | (400 V) Three Phase 5.5 kW |
Rated Operational Power AC-3 (Pe) | (500 V) Three Phase 5.5 kW |
Rated Operational Power AC-3 (Pe) | (690 V) Three Phase, NO 3 kW |
Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A |
Rated Insulation Voltage (Ui) | 690 V |
Rated Insulation Voltage (Ui) | acc. to UL/CSA 600 V |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 6 kV |
Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
Maximum Electrical Switching Frequency | (AC-15) 600 cycles per hour |
Maximum Electrical Switching Frequency | (AC-3) 600 cycles per hour |
Maximum Electrical Switching Frequency | (DC-1) 600 cycles per hour |
Maximum Electrical Switching Frequency | (DC-13) 600 cycles per hour |
Maximum Electrical Switching Frequency | (DC-3) 600 cycles per hour |
Mechanical Durability | Nr. Operations 10000000 cycle |
Minimum switching capacity | Auxiliary Circuit 17 V |
Minimum switching capacity | Auxiliary Circuit 5 mA |
Coil Operating Limits | (acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
Rated Control Circuit Voltage (Uc) | 220 ... 240 V AC |
Coil Consumption | Average Holding Value 50 Hz 3.5 V·A |
Coil Consumption | Average Pull-in Value 50 Hz 3.5 V·A |
Power Loss | at Rated Operating Conditions AC-1 per Pole 1.4 W |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 1 ... 2.5 mm² |
Connecting Capacity Main Circuit | Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm² |
Connecting Capacity Main Circuit | Flexible 1/2x 1 ... 2.5 mm² |
Connecting Capacity Main Circuit | Rigid 1/2x 1 ... 4 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 1 ... 2.5 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm² |
Connecting Capacity Auxiliary Circuit | Flexible 1/2x 1 ... 2.5 mm² |
Connecting Capacity Auxiliary Circuit | Rigid 1/2x 1 ... 4 mm² |
Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 1 ... 2.5 mm² |
Connecting Capacity Control Circuit | Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm² |
Connecting Capacity Control Circuit | Flexible 1/2x 1 ... 2.5 mm² |
Connecting Capacity Control Circuit | Rigid 1/2x 1 ... 4 mm² |
Wire Stripping Length | Auxiliary Circuit 9 mm |
Wire Stripping Length | Main Circuit 9 mm |
Degree of Protection | Main Circuit Terminals IP20 |
Recommended Screw Driver | M3 |
Recommended Screw Driver | Pozidriv 1 |
Tightening torque | Control Circuit 0.8 ... 1.1 N·m |
Tightening torque | Main Circuit 0.8 ... 1.1 N·m |
Terminal Type | Screw Terminals |
Product Name | Mini Reversing Contactor |
Technical UL/CSA
Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
General Use Rating UL/CSA | (600 V AC) 16 A |
Horsepower Rating UL/CSA | (115 V AC) Single Phase 0.75 Hp |
Horsepower Rating UL/CSA | (200 V AC) Three Phase 2 Hp |
Horsepower Rating UL/CSA | (220 ... 240 V AC) Three Phase 3 Hp |
Horsepower Rating UL/CSA | (230 V AC) Single Phase 1.5 Hp |
Horsepower Rating UL/CSA | (440 ... 480 V AC) Three Phase 5 Hp |
Horsepower Rating UL/CSA | (550 ... 600 V AC) Three Phase 5 Hp |
Connecting Capacity Main Circuit UL/CSA | Stranded 1/2x 22-10 AWG |
Connecting Capacity Auxiliary Circuit UL/CSA | Stranded 1/2x 22-10 AWG |
Contact Rating UL/CSA | A600 |
Tightening Torque UL/CSA | Auxiliary Circuit 7 in·lb |
Tightening Torque UL/CSA | Control Circuit 7 in·lb |
Tightening Torque UL/CSA | Main Circuit 7 in·lb |
Full Load Amps Motor Use | (115 V AC) Single Phase 13.8 A |
Full Load Amps Motor Use | (200 V AC) Three Phase 7.8 A |
Full Load Amps Motor Use | (220 ... 240 V AC) Three Phase 9.6 A |
Full Load Amps Motor Use | (230 V AC) Single Phase 10 A |
Full Load Amps Motor Use | (440 ... 480 V AC) Three Phase 7.6 A |
Full Load Amps Motor Use | (550 ... 600 V AC) Three Phase 6.1 A |
ABB EcoSolutions
End Of Life Disassembling Instructions | 1SBC100156C0269 |
Environmental Product Declaration - EPD | 1SAC200410H0001 |
Why Proax for ABB VB7-30-10-80?
Proax is an authorized distributor of ABB VB7-30-10-80 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | VB7301080 |
Pack Size | 1 |
Recommended