1132800
SKU
PHX1132800
MPN
AXL P BK PN
Weight
0.322 kg
AXL P BK PN - Bus coupler
Axioline P, Bus coupler, PROFINET, RJ45 jack, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and connectors
- 2 Ethernet ports (with integrated switch)
- PROFINET RT
- Supports S2 system redundancy
- Web-based management
- Hot-swappable
- Firmware can be updated through Web-based manager
- High temperature operating range
Documents
Technical Specifications
Dimensions
| Width | 45 mm |
| Height | 126.93 mm |
| Depth | 75 mm |
| Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
Note on application
| Note on application | Only for industrial use |
Utilization restriction
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| CCCex note | Use in potentially explosive areas is not permitted in China. |
PROFINET
| Number of interfaces | 2 |
| Connection Method | RJ45 jack |
| Note on the connection method | Auto negotiation and autocrossing |
| Transmission Speed | 100 Mbps (full duplex) |
| Transmission physics | Ethernet in RJ45 twisted pair |
Axioline P local bus
| Number of interfaces | 1 |
| Connection Method | Bus base module |
| Transmission Speed | 100 Mbps |
System limits
| Number of supported devices | max. 63 (per station) |
PROFINET
| Device function | PROFINET device |
| Specification | Version 2.3 |
| Conformance class | Conformance-Class C |
| Device ID | 0172hex |
| Vendor ID | 00B0hex |
Product properties
| Product family | Axioline P |
| Type | block modular |
| Mounting Position | any |
| Scope of delivery | including bus base module and connectors |
Insulation characteristics
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Electrical properties
| Maximum power dissipation for nominal condition | 5 W |
Potentials: Supply of the bus coupler (UL)
| Supply Voltage | 24 V DC |
| Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 4.15 A (19.2 V DC) |
| Current draw | max. 3 A (via bus base module) |
| Current draw | 125 mA (24 V DC) |
| Protective circuit | Surge protection; electronic |
| Protective circuit | Reverse polarity protection; electronic |
Potentials: Axioline P local bus supply (UBus)
| Supply Voltage | 5 V DC (via bus base module) |
| Power Supply Unit | max. 3 A |
| Current draw | 3 A (via bus base module) |
Electrical isolation/isolation of the voltage ranges
| Test voltage: PROFINET interface 1 / PROFINET interface 2 | 1500 V AC, 50 Hz, 1 min |
| Test voltage: PROFINET interface 1 / 24 V communications voltage (UL) feed-in | 1500 V AC, 50 Hz, 1 min |
| Test voltage: PROFINET interface 1 / functional ground | 1500 V AC, 50 Hz, 1 min |
| Test voltage: PROFINET interface 2 / 24 V communications voltage (UL) feed-in | 1500 V AC, 50 Hz, 1 min |
| Test voltage: PROFINET interface 2 / functional ground | 1500 V AC, 50 Hz, 1 min |
| Test voltage: 24 V communications voltage (UL) feed-in / functional ground | 500 V AC, 50 Hz, 1 min |
Connection technology
| Connection name | Power supply |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline P: system and installation” user manual. |
Conductor connection
| Connection Method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Stripping length | 8 mm |
Power supply
| Connection Method | Push-in connection |
| Note on the connection method | Please observe the information provided on conductor cross sections in the “Axioline P: system and installation” user manual. |
| Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Stripping length | 8 mm |
Ambient conditions
| Ambient Temperature (Operation) | -40 °C ... 70 °C (Mounting position: panel mounting on horizontal DIN rail) |
| Ambient Temperature (Operation) | -40 °C ... 50 °C (Mounting position: any) |
| Degree of Protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 2000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 2000 m above sea level) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
Standards and Regulations
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
ATEX
| Identification | II 3 G Ex ec IIC T4 Gc |
| Certificate | IBExU 18ATEXB018 X |
IECEx
| Identification | Ex ec IIC T4 Gc |
| Certificate | IECEx IBE 18.0023X |
UKCA Ex (UKEX)
| Identification | II 3G Ex ec IIC T4 Gc X |
| Certificate | PxCAI22UKEx2316390X |
Ex data
| UL, USA / Canada | Class I, Div. 2, Groups A, B, C, D T4Class I, Zone 2, IIC T4 |
Mounting
| Mounting Type | DIN rail mounting |
| Mounting Position | any |
Why Proax for Phoenix Contact 1132800?
Proax is an authorized distributor of Phoenix Contact 1132800 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended