Official Distributor
SKU
MPN
AXC F XT SPLC 1000
Weight
0.317 kg
AXC F XT SPLC 1000 - PLC extension module
The AXC F XT SPLC 1000 is a left-alignable, safety-oriented controller for operating PROFIsafe devices. The SPLC 1000 is connected to the AXC F 2152 or AXC F 3152 modular controllers from the PLCnext Control series.
- Implementation of safety-related applications up to SIL 3/PL e
- PROFIsafe F-Host for up to 32 PROFIsafe F-Devices in PROFINET or Axioline
- PROFIsafe F-Device for communication with a higher-level PROFIsafe F-Host SPLC
- 2 x diverse SCPUs with Cortex M4-based architecture
- Full integration into the PLCnext Technology ecosystem
Technical Specifications
Dimensions
Width | 45 mm |
Height | 126.93 mm |
Depth | 75 mm |
Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
External dimensions
Width / Height / Depth | 45 mm / 126.93 mm / 75 mm (The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).) |
Notes
General | If the SPLC-1000 is operated with AXC F 2152, the AXC BS L 2 bus base module must be used. |
Interfaces
Web server | No |
System properties
Processor | Arm® Cortex®-M4, 180 MHz (CPU1) |
Processor | Arm® Cortex®-M4, 100 MHz (CPU2) |
Function
Diagnostics display | No |
Controller redundancy | No |
Safety function | yes |
System requirements
Engineering tool | PLCnext Engineer |
Product properties
Product family | PLCnext Control Extension |
Type | modular |
Insulation characteristics
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Display
Diagnostics display | No |
Electrical properties
Maximum power dissipation for nominal condition | typ. 1.92 W |
Maximum power dissipation for nominal condition | typ. 1.92 W |
Supply
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Max. current consumption | 100 mA |
Typical current consumption | 80 mA |
Potentials: Supply of the logic voltage UL
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 100 mA |
Current draw | typ. 80 mA |
Protective circuit | Reverse polarity protection; Polarity protection diode |
Protective circuit | Transient protection; Suppressor diode |
Connection technology
Connection name | Axioline F connector |
Conductor connection
Connection Method | Push-in connection |
Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Axioline F connector
Connection Method | Push-in connection |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 60 °C up to 2000 m above mean sea level |
Ambient Temperature (Operation) | -25 °C ... 55 °C up to 3000 m above mean sea level |
Ambient Temperature (Operation) | -25 °C ... 50 °C up to 4000 m above mean sea level |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (according to DIN EN 61131-2) |
Permissible humidity (storage/transport) | 5 % ... 95 % (according to DIN EN 61131-2) |
Shock (operation) | 30g (in accordance with EN 60068-2-27/IEC 60068-2-27) |
Shock (storage/transport) | 30g (in accordance with EN 60068-2-27/IEC 60068-2-27) |
Vibration (Operation) | 5g (in accordance with EN 60068-2-6/IEC 60068-2-6) |
Vibration (storage/transport) | 5g (in accordance with EN 60068-2-6/IEC 60068-2-6) |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 58 kPa ... 106 kPa (up to 4500 m above mean sea level) |
Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37 | Use of the device in these ambient conditions is prohibited. |
ATEX
Identification | II 3 G Ex ec IIC T4 Gc |
Certificate | UL 21 ATEX 2651X |
References to standards | EN IEC 60079-0, EN IEC 60079-7 |
IECEx
Identification | Ex ec IIC T4 Gc |
Certificate | IECEx ULD 21.0029X |
References to standards | IEC 60079-0 Ed. 7, IEC 60079-7 Ed. 5.1 |
UL Ex, USA / Canada
Identification | Class I, Zone 2, AEx ec IIC T4, Ex ec IIC T4 Gc X |
Identification | Class I, Div. 2 Groups A, B, C, D T4 |
Certificate | E366272 |
References to standards | UL 60079-0 Ed. 7 / CSA C22.2 NO. 60079-0 Ed. 4 |
References to standards | UL 60079-7 Ed. 5 / CSA C22.2 NO. 60079-7 Ed. 2 |
UL, USA/Canada
Identification | cULus |
Certificate | E238705 |
Industrial Cyber Security
Identification | Industrial IT Security, IACS Component |
Certificate | IITS2 029429 0027 |
Note | Configuration: Security Profile active |
References to standards | IEC 62443-4-1:2018 |
References to standards | IEC 62443-4-2:2019 |
References to standards | PPP 15003B:2021 (IEC 62443-4-1: Full ML3 Process Profile) |
Mounting
Mounting Type | DIN rail mounting |
Why Proax for Phoenix Contact 1159811?
Proax is an authorized distributor of Phoenix Contact 1159811 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended