Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
PSR-SPP- 24DC/FSP2/2X1/1X2
Weight
0.141 kg
This product is Not Cancellable/Not Returnable
Series PSR-SPP

PSR-SPP- 24DC/FSP2/2X1/1X2 - Coupling relay

Safe coupling relay for SIL 2 high and low demand applications, coupled digital output signals to the I/O, 2 enabling current paths, 1 signal contact, module for safe state off applications, integrated test pulse filter, width: 17.5 mm, pluggable Push-in terminal block

  • Narrow 17.5 mm housing
  • Up to SIL 2 in accordance with EN 61508
  • Easy proof test according to IEC 61508 thanks to integrated signal contact
  • Long service life thanks to filtering of controller test pulses
  • Force-guided contacts in accordance with EN 50205
  • 2 enabling current paths
  • Couples digital output signals from failsafe controllers to I/O devices (valves, etc.) for electrical isolation and power adaptation
Technical Specifications

Product properties

Product familyPSRclassic
ApplicationSafe switch off
ApplicationHigh demand
ApplicationLow demand
Mechanical service life10x 106 cycles
Relay typeElectromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3

Electrical properties

Maximum power dissipation for nominal condition2.4 W
Nominal operating mode100% operating factor

Air clearances and creepage distances between the power circuits

Rated Insulation Voltage250 V AC
Rated surge voltage/insulationSafe isolation, reinforced insulation 6 kV between the control circuits (A1/A2), (31/32), (13/14, 23/24)

General

Rated control circuit supply voltage US24 V DC -15 % / +10 %
Power consumption at UStyp. 1.32 W
Rated control supply current IStyp. 55 mA
Input voltage range20.4 V DC ... 26.4 V DC
Inrush Currentmax. 100 mA
Filter timemax. 5 ms (at A1 in the event of voltage dips at Us)
Filter timemax. 2 ms (Test pulse width; high test pulse at A1/A2)
Filter time≥ 100 ms (Test pulse width; high test pulse at A1/A2)
Filter timeTest pulse rate = 80 x Test pulse width
Filter timemax. 5 ms (Test pulse width; low test pulse at A1/A2)
Filter time≥ 50 ms (Test pulse rate; low test pulse at A1/A2)
Filter timeTest pulse rate = 15 x Test pulse width
Typ. starting time with Us50 ms
Typical release time50 ms
Recovery time1 s
Maximum switching frequency0.5 Hz
Protective circuitSurge protection; Suppressor diode, 33 V (A1 - A2)
Operating voltage display1 x yellow LED

Output data

Contact switching type2 enabling current paths
Contact switching type1 confirmation current path
Contact MaterialAgCuNi, + 0.2 µm Au
Maximum Switching Voltage250 V AC/DC (N/O contact / N/C contact, observe the load curve)
Minimum Switching Voltage15 V AC/DC (N/O contact / N/C contact)
Limiting Continuous Current5 A (N/O contact, pay attention to the derating)
Limiting Continuous Current100 mA (N/C contact)
Maximum Inrush Current5 A (N/O contact)
Maximum Inrush Current100 mA (N/C contact)
Inrush current, minimum5 mA (N/O contact / N/C contact)
Sq. Total current50 A2 (observe derating)
Interrupting rating (ohmic load) max.120 W (24 V DC, τ = 0 ms, N/C contact: 2.4 W)
Interrupting rating (ohmic load) max.192 W (48 V DC, τ = 0 ms, N/C contact: 4.8 W)
Interrupting rating (ohmic load) max.162 W (60 V DC, τ = 0 ms, N/C contact: 6 W)
Interrupting rating (ohmic load) max.66 W (110 V DC, τ = 0 ms, N/C contact: 11 W)
Interrupting rating (ohmic load) max.60 W (220 V DC, τ = 0 ms, N/C contact: 22 W)
Interrupting rating (ohmic load) max.1250 VA (250 V AC, τ = 0 ms, N/C contact: 25 VA)
Maximum interrupting rating (inductive load)72 W (24 V DC, τ = 40 ms, N/C contact: 2.4 W)
Maximum interrupting rating (inductive load)43 W (48 V DC, τ = 40 ms, N/C contact: 4.8 W)
Maximum interrupting rating (inductive load)41 W (60 V DC, τ = 40 ms, N/C contact: 6 W)
Maximum interrupting rating (inductive load)35 W (110 V DC, τ = 40 ms, N/C contact: 11 W)
Maximum interrupting rating (inductive load)48 W (220 V DC, τ = 40 ms, N/C contact: 22 W)
Switching capacitymin. 75 mW
Switching capacity (3600/h cycles)5 A (24 V (DC13))
Switching capacity (3600/h cycles)5 A (230 V (AC15))
Output fuse10 A gL/gG (N/O contact)
Output fuse4 A gL/gG (for low-demand applications)
Output fuse150 mA Fast-blow (N/C contact)

Connection technology

pluggableyes

Conductor connection

Connection MethodPush-in connection
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross-section AWG24 ... 16
Stripping length8 mm

Dimensions

Width17.5 mm
Height112 mm
Depth114.5 mm

Material specifications

Color (Housing)yellow (RAL 1018)
Housing MaterialPolyamide

Safety data

Stop category0

Safety data: EN ISO 13849

Category1 (Diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 90 %)
Performance level (PL)c (Diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 90 %)

Safety data: EN 50156

Safety Integrity Level (SIL)2

Safety data: IEC 61508 - High demand

Safety Integrity Level (SIL)2 (max. 10% of the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 90% )

Safety data: IEC 61508 - Low demand

Safety Integrity Level (SIL)2 (max. 10% of the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 90% )

Safety data: EN IEC 62061

Safety Integrity Level (SIL)1 (max. 10% of the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be ≥ 90% )

Ambient conditions

Degree of ProtectionIP20
Min. degree of protection of inst. locationIP54
Ambient Temperature (Operation)-20 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Maximum altitude≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Shock15g
Vibration (Operation)10 Hz ... 150 Hz, 2g

CE

CertificateCE-compliant

Air clearances and creepage distances between the power circuits

Standards/regulationsIEC 60664-1

Mounting

Mounting TypeDIN rail mounting
Mounting Positionany

Why Proax for Phoenix Contact 2986588?

Proax is an authorized distributor of Phoenix Contact 2986588 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability