PSR-SPP- 24DC/ESD/4X1/30 - Safety relays
Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e in accordance with EN ISO 13849, automatic or manual activation, 2 N/O contacts with a fixed dropout delay of 0.1 s ... 30 s, pluggable Push-in terminal block
- Maximum of 3 undelayed and 2 dropout delay contacts
- Manually monitored and automatic activation
- Up to Cat. 3/4 and PL d/e in accordance with EN ISO 13849-1, SIL 3 in accordance with EN IEC 62061, SIL 3 in accordance with IEC 61508
- For emergency stop and safety door monitoring, plus evaluation of light grids
- 1- and 2-channel control
- Protective labels to prevent manipulation of the set time (PSR-ESD-300) or electronic protection against manipulation (PSR-ESD-30)
- Fixed delay times of 0.1 s ... 300 s
Technical Specifications
Product properties
| Product family | PSRclassic |
| Application | Emergency stop |
| Application | Safety door |
| Application | Light grid |
| Mechanical service life | approx. 10⁷ cycles |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
Times
| Typical response time | 150 ms (Monitored/manual and auto-start) |
| Typical release time | 20 ms (Undelayed contacts) |
| Typical release time | 100 ms |
| Delay time range | 0.1 s ... 30 s ±30 % (adjustable) |
| Recovery time | 330 ms (Restart) |
| Recovery time | 1 s (Electric torque) |
Electrical properties
| Maximum power dissipation for nominal condition | 1.8 W |
| Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits
| Rated Insulation Voltage | 250 V |
| Rated surge voltage/insulation | 4 kV / basic insulation |
Supply
| Rated control circuit supply voltage US | 24 V DC |
| Inrush Current | typ. 250 mA |
General
| Nominal input voltage UN | 24 V DC |
| Input voltage range in reference to UN | 0.85 ... 1.1 |
| Typical input current at UN | 75 mA DC |
| Voltage at input/start and feedback circuit | approx. 24 V DC |
| Typical response time | 150 ms (Monitored/manual and auto-start) |
| Typical release time | 20 ms (Undelayed contacts) |
| Typical release time | 100 ms (delayed contacts) |
| Typical release time range | 0.1 s ... 30 s |
| Recovery time | 330 ms (Restart) |
| Recovery time | 1 s (Electric torque) |
| Protective circuit | Suppressor diode, 33 V DC |
| Max. permissible overall conductor resistance | 500 Ω (Input and reset circuit at UN) |
| Operating voltage display | Green LED |
| Status display | LED K1/K2 and K3(t)/K4(t), green |
Output data
| Contact switching type | 4 enabling current paths |
| Contact Material | AgSnO2 |
| Maximum Switching Voltage | 250 V AC/DC |
| Minimum Switching Voltage | 15 V AC/DC |
| Limiting Continuous Current | 6 A (N/O contact) |
| Maximum Inrush Current | 6 A |
| Inrush current, minimum | 25 mA |
| Sq. Total current | 120 A2 (see to derating) |
| Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 288 W (48 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 90 W (110 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 88 W (220 V DC, τ = 0 ms) |
| Interrupting rating (ohmic load) max. | 1500 VA (250 V AC, τ = 0 ms) |
| Maximum interrupting rating (inductive load) | 42 W (24 V DC, τ = 40 ms) |
| Maximum interrupting rating (inductive load) | 33 W (48 V DC, τ = 40 ms) |
| Maximum interrupting rating (inductive load) | 25 W (110 V DC, τ = 40 ms) |
| Maximum interrupting rating (inductive load) | 23 W (220 V DC, τ = 40 ms) |
| Switching capacity min. | 0.4 W |
| Switching capacity (360/h cycles) | on request |
| Switching capacity (3600/h cycles) | 3 A (24 V (DC13)) |
| Switching capacity (3600/h cycles) | 3 A (230 V (AC15)) |
| Output fuse | 10 A gL/gG NEOZED (N/O contact) |
Connection technology
| pluggable | yes |
Conductor connection
| Connection Method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
| Conductor cross-section AWG | 24 ... 16 |
| Stripping length | 8 mm |
Dimensions
| Width | 22.5 mm |
| Height | 112 mm |
| Depth | 114.5 mm |
Material specifications
| Housing Material | Polyamide |
Safety data
| Stop category | 0 |
| Stop category | 1 |
Safety data: EN ISO 13849
| Category | 4 |
| Performance level (PL) | e |
Safety data
| Safety Integrity Level (SIL) | 3 |
Safety data: EN IEC 62061
| Safety Integrity Level (SIL) | 3 |
Ambient conditions
| Degree of Protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient Temperature (Operation) | -20 °C ... 45 °C |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Shock | 15g |
| Vibration (Operation) | 10 Hz ... 150 Hz, 2g |
Air clearances and creepage distances between the power circuits
| Standards/regulations | DIN EN 60947-1 |
Mounting
| Mounting Type | DIN rail mounting |
| Mounting Position | any |
Why Proax for Phoenix Contact 2981813?
Proax is an authorized distributor of Phoenix Contact 2981813 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended