2912413
SKU
PHX2912413
MPN
PLC-RSP- 24DC/ 1IC/ACT
Weight
0.063 kg
Series PLC-RSP
PLC-RSP- 24DC/ 1IC/ACT - Relay Module
PLC-INTERFACE for high switch-on currents, consisting of PLC-BSP.../1 IC/ACT basic terminal block with spring-cage connection and plug-in miniature relay, for mounting on DIN rail NS 35/7,5, max. switch-on current up to 130 A, 1 N/O contact, input voltage 24 V DC
- Direct connection of load return line thanks to actuator version
- Efficient connection to system cabling using V8 adapter
- Safe isolation between coil and contact side
- Max. inrush current of 130 A
- Functional plug-in bridges
Technical Specifications
Product properties
| Product family | PLC-INTERFACE |
| Application | high inrush currents |
| Operating mode | 100% operating factor |
| Mechanical service life | 3x 10⁷ cycles |
Insulation characteristics
| Insulation | Safe isolation, reinforced insulation |
Insulation characteristics: Standards/regulations
| Insulation | Safe isolation, reinforced insulation |
| Overvoltage category | III |
| Pollution degree | 2 |
Electrical properties
| Maximum power dissipation for nominal condition | 0.43 W |
| Test voltage (Winding/contact) | 4 kV AC (50 Hz, 1 min., winding/contact) |
Standards/regulations
| Rated surge voltage | 6 kV |
Coil side
| Nominal input voltage UN | 24 V DC |
| Input voltage range | 20.2 V DC ... 33.6 V DC |
| Drive and function | monostable |
| Typical input current at UN | 18 mA |
| Typical response time | 8 ms |
| Typical release time | 10 ms |
| Protective circuit | Reverse polarity protection; Polarity protection diode |
| Protective circuit | Freewheeling diode; Freewheeling diode |
| Operating voltage display | Yellow LED |
Switching
| Contact switching type | 1 N/O contact |
| Type of switch contact | Single contact |
| Contact Material | AgSnO |
| Maximum Switching Voltage | 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) |
| Minimum Switching Voltage | 12 V AC/DC (at 100 mA) |
| Limiting Continuous Current | 6 A |
| Limiting Continuous Current | 10 A (the value is permissible if both connections 13, both connections 14 and both connections BB are bridged) |
| Maximum Inrush Current | 80 A (for 20 ms) |
| Maximum Inrush Current | 130 A (peak, at capacitive load, 230 V AC, 24 μF) |
| Min. switching current | 100 mA (at 12 V DC) |
| Interrupting rating (ohmic load) max. | 144 W (at 24 V DC) |
| Interrupting rating (ohmic load) max. | 58 W (at 48 V DC) |
| Interrupting rating (ohmic load) max. | 48 W (at 60 V DC) |
| Interrupting rating (ohmic load) max. | 50 W (at 110 V DC) |
| Interrupting rating (ohmic load) max. | 80 W |
| Interrupting rating (ohmic load) max. | 85 W (for 250 V DC) |
| Interrupting rating (ohmic load) max. | 1500 VA (for 250 V AC) |
| Interrupting rating (ohmic load) max. bridged | 240 W (for 24 V DC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.) |
| Interrupting rating (ohmic load) max. bridged | 2500 VA (for 250 V AC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.) |
| Switching capacity | 2 A (at 24 V, DC13) |
| Switching capacity | 0.2 A (at 110 V, DC13) |
| Switching capacity | 0.2 A (at 250 V, DC13) |
| Switching capacity | 6 A (at 24 V, AC15) |
| Switching capacity | 6 A (at 120 V, AC15) |
| Switching capacity | 6 A (at 250 V, AC15) |
Coil side
| Connection Method | Spring-cage connection |
| Stripping length | 8 mm |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
Contact side
| Connection Method | Spring-cage connection |
| Stripping length | 8 mm |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
Dimensions
| Width | 14 mm |
| Height | 80 mm |
| Depth | 94 mm |
Material specifications
| Color | green (RAL 6021) |
| Flammability rating according to UL 94 | V0 (Housing) |
Ambient conditions
| Degree of protection (Relay) | RT II (Relay) |
| Degree of protection (Relay base) | IP20 (Relay base) |
| Ambient Temperature (Operation) | -40 °C ... 60 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Standards/regulations
| Standards/regulations | IEC 60664 |
| Standards/regulations | EN 50178 |
Mounting
| Mounting Type | DIN rail mounting |
| Assembly instructions | in rows with zero spacing |
| Mounting Position | any |
Accessories
PLC-V8L/FLK14/OUT - V8 adapter for 8 x PLC-INTERFACE (14 mm), controller: PLC system cabling of output cards, connection 1: IDC/FLK pin strip 1x 14-position, connection 2: Plug-in connection (Can be snapped onto 8x PLC-INTERFACE terminals), connection 3: Screw connection 1x 2-position, number of channels: 8, control logic: plusschaltend
V8 adapter for 8 x PLC-INTERFACE (14 mm), controller: PLC system cabling of output cards, connection 1: IDC/FLK pin strip 1x 14-position, connection 2: Plug-in connection (Can be snapped onto 8x PLC-INTERFACE terminals), connection 3: Screw connection 1x 2-position, number of channels: 8, control logic: minusschaltend
Why Proax for Phoenix Contact 2912413?
Proax is an authorized distributor of Phoenix Contact 2912413 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 10 |