Official Distributor
SKU
MPN
PLC-OPT- 24DC/300DC/1
Weight
0.031 kg
This product is Not Cancellable/Not Returnable
Series PLC-OPT
PLC-OPT- 24DC/300DC/1 - Solid-state relay module
PLC-INTERFACE, integrated solid-state relay, with push-in connection, for mounting on NS 35/7,5 DIN rails, input: 24 V DC, output: 12 - 300 V DC/1 A
- Wear-free switching with no contact bounce
- Resistant to vibrations and shocks
- Protective circuit in input and output
- Status indicator
- DC voltage outputs up to 300 V DC/1 A
- Option of bridging adjacent modules
Technical Specifications
Product properties
Product family | PLC-INTERFACE |
Application | With integrated solid-state relay |
Operating mode | 100% operating factor |
Insulation characteristics
Insulation | Basic insulation |
Insulation characteristics: Standards/regulations
Insulation | Basic insulation |
Overvoltage category | III |
Pollution degree | 2 |
Electrical properties
Maximum power dissipation for nominal condition | 0.19 W |
Standards/regulations
Rated Insulation Voltage | 300 V |
Rated surge voltage | 2.5 kV |
Input data
Nominal input voltage UN | 24 V DC |
Input voltage range in reference to UN | 0.8 ... 1.2 |
Input voltage range | 19.2 V DC ... 28.8 V DC |
Switching threshold "0" signal in reference to UN | ≤ 0.4 |
Switching threshold "1" signal in reference to UN | ≥ 0.8 |
Typical input current at UN | 8 mA |
Typical response time | 0.3 ms |
Typical turn-off time | 0.7 ms |
Operating voltage display | Yellow LED |
Protective circuit | Reverse polarity protection; Polarity protection diode |
Protective circuit | Surge protection; Varistor |
Transmission frequency | 50 Hz |
Output data
Designation | Output data |
Contact switching type | 1 N/O contact |
Design of digital output | electronic |
Contact connection type | Power contact |
Output voltage range | 12 V DC ... 300 V DC (Partition plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal points in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) |
Limiting Continuous Current | 1 A (see derating curve) |
Voltage drop at max. limiting continuous current | < 500 mV |
Protective circuit | Reverse polarity protection; Polarity protection diode |
Protective circuit | Surge protection; Varistor |
Connection data
Connection Method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² (Single ferrule) |
Conductor cross section flexible | 2x 0.5 mm² ... 1 mm² (TWIN ferrule) |
Conductor cross section AWG | 26 ... 14 |
Dimensions
Width | 6.2 mm |
Height | 80 mm |
Depth | 95 mm |
Material specifications
Color | gray (RAL 7042) |
Flammability rating according to UL 94 | V0 (Housing) |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
CE
Certificate | CE-compliant |
UKCA
Certificate | UKCA-compliant |
Shipbuilding approval
Certificate | TAE0000196 |
Corrosive gas test
Identification | ISA-S71.04. G3 Harsh Group |
Identification | EN 60068-2-60 |
DNV GL data
Temperature | D |
Humidity | A |
Vibration | B/C |
EMC | B |
Enclosure | Required protection according to the Rules shall be provided upon installation on board |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive |
Electromagnetic compatibility | Conformance with EMC directive |
Standards/regulations
Standards/regulations | IEC 60947-5-1 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | in rows with zero spacing |
Mounting Position | any |
Accessories
- 2295554 - V8 adapter for 8 x PLC-INTERFACE (6.2 mm), controller: PLC system cabling of output cards, connection 1: IDC/FLK pin strip 1x 14-position, connection 2: Plug-in connection (Can be snapped onto 8x PLC-INTERFACE terminals), connection 3: Screw connection 1x 2-position, number of channels: 8, control logic: plusschaltend
- 2304102 - V8 adapter for 8 x PLC-INTERFACE (6.2 mm), controller: PLC system cabling of output cards, connection 1: IDC/FLK pin strip 1x 14-position, connection 2: Plug-in connection (Can be snapped onto 8x PLC-INTERFACE terminals), connection 3: Screw connection 1x 2-position, number of channels: 8, control logic: minusschaltend
- 2296058 - V8 adapter for 8 x PLC-INTERFACE (6.2 mm), controller: PLC system cabling of output cards, connection 1: D-SUB pin strip 1x 15-position, connection 2: Plug-in connection (Can be snapped onto 8x PLC-INTERFACE terminals), connection 3: Screw connection 1x 2-position, number of channels: 8, control logic: plusschaltend
- 2296061 - V8 adapter for 8 x PLC-INTERFACE (6.2 mm), controller: PLC system cabling of output cards, connection 1: D-SUB socket strip 1x 15-position, connection 2: Plug-in connection (Can be snapped onto 8x PLC-INTERFACE terminals), connection 3: Screw connection 1x 2-position, number of channels: 8, control logic: plusschaltend
Why Proax for Phoenix Contact 2900383?
Proax is an authorized distributor of Phoenix Contact 2900383 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 10 |
Recommended