2882213
SKU
PHX2882213
MPN
MNT-1 D/WH
Weight
0.125 kg
MNT-1 D/WH - Type 3 surge protection device
Attachment connector with surge protection for mains sockets, mains control lamp, optical power and error display. For country-specific use in: D, A, I, NL, S, N, FIN, E, P. Color: White
Technical Specifications
Product properties
| Product family | MAINTRAB |
| IEC power supply system | TN |
| IEC power supply system | TT |
| Type | Attachment plug |
| Number of Positions | 2 |
| For country-specific use in | D, A, NL, E, S, FIN, TR |
| Surge protection fault message | optical |
Insulation characteristics
| Overvoltage category | III |
| Pollution degree | 2 |
| IEC test classification | III |
| IEC test classification | T3 |
| EN type | T3 |
| Number of Ports | One |
Connection data
| Connection Method | Grounding plug/socket |
Dimensions
| Width | 56 mm |
| Height | 76 mm |
| Depth | 78 mm |
Material specifications
| Color | white (RAL 9010) |
| Color | black (RAL 9005) |
| Flammability rating according to UL 94 | V-0 |
| CTI value of material | 400 |
| CTI value of material | 600 |
| Insulating material | PA 6 |
| Housing Material | PA 6 |
Protective circuit
| Mode of protection | L-N |
| Mode of protection | L-PE |
| Mode of protection | N-PE |
| Direction of action | L(N)-PE |
| Nominal voltage UN | 230/400 V AC (TN/TT) |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC (L-N) | 275 V AC |
| Maximum continuous operating voltage UC (L-PE) | 360 V AC |
| Maximum continuous operating voltage UC (N-PE) | 360 V AC |
| Rated load current IL | 16 A (30 °C) |
| Residual current IPE | ≤ 5 µA |
| Standby power consumption PC | ≤ 1.00 VA |
| Reference test voltage UREF | 255.00 V AC |
| Combination wave UOC | 6 kV |
| Voltage protection level Up | ≤ 1.5 kV |
| TOV behavior at UT (L-N) | 460 V AC (5 s / withstand mode) |
| TOV behavior at UT (L-N) | 460 V AC (120 min / safe failure mode) |
| TOV behavior at UT (L-PE) | 460 V AC (5 s / withstand mode) |
| TOV behavior at UT (L-PE) | 460 V AC (120 min / withstand mode) |
| TOV behavior at UT (L-PE) | 1455 V AC (200 ms / safe failure mode) |
| TOV behavior at UT (N-PE) | 1200 V AC (200 ms / safe failure mode) |
| Response time tA (L-N) | ≤ 25 ns |
| Response time tA (L-PE) | ≤ 100 ns |
| Response time tA (N-PE) | ≤ 100 ns |
| Max. required back-up fuse | 16 A (gG / B / C) |
| Short-circuit current rating ISCCR | 1.5 kA AC |
Ambient conditions
| Degree of Protection | IP20 (Child-proofing) |
| Ambient Temperature (Operation) | -25 °C ... 75 °C |
| Ambient temperature (storage/transport) | -25 °C ... 75 °C |
| Altitude | ≤ 2000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
Standards and Regulations
| Standards/specifications | IEC 61643-11 |
| Note | 2011 |
| Standards/specifications | EN 61643-11 |
| Note | 2019 |
Mounting
| Mounting Type | Plugging into the mains socket |
Why Proax for Phoenix Contact 2882213?
Proax is an authorized distributor of Phoenix Contact 2882213 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended