2907976
SKU
PHX2907976
MPN
EEM-MB371-EIP
Weight
0.432 kg
This product is Not Cancellable/Not Returnable
Series EEM-MB
EEM-MB371-EIP - Measuring instrument
Multi-functional energy measuring device without display with direct Rogowski connection and integrated Modbus/TCP and EtherNet/IP™ interface for measuring electrical parameters in low-voltage installations up to 690 V. (phoenixcontact.com/empro-help)
Technical Specifications
Product properties
| Product family | EMpro |
Electrical properties
| Maximum power dissipation for nominal condition | 10 VA |
| Mains type | 3-phase (3 or 4-conductor), 2-phase (2-conductor), and single-phase (1-conductor) |
Electrical isolation
| Test voltage | 4 kV AC (50 Hz, 60 s) |
| Pollution degree | 2 |
Electrical isolation Housing against all potentials IEC 61010-1
| Standards/regulations | IEC 61010-1 |
| Overvoltage category | III (300 V AC) |
| Overvoltage category | II (600 V AC) |
| Insulation | Reinforced insulation |
Electrical isolation Supply against all other potentials IEC 61010-1
| Standards/regulations | IEC 61010-1 |
| Overvoltage category | III (300 V AC) |
| Overvoltage category | II (600 V AC) |
| Insulation | Reinforced insulation |
Electrical isolation Voltage measurement input against all other potentials IEC 61010-1
| Standards/regulations | IEC 61010-1 |
| Measuring category | III (300 V AC) |
| Measuring category | II (600 V AC) |
| Insulation | Reinforced insulation |
Electrical isolation Digital I/Os
| Insulation | Functional insulation |
Electrical isolation Communication interface
| Insulation | Functional insulation |
Insulation characteristics
| Voltage measuring input | Safe isolation |
| Current measuring input | Basic insulation |
| Supply | Safe isolation |
| Digital I/Os | - |
| Communication interface | Functional insulation |
Supply
| Supply Voltage Range | 100 V AC ... 230 V AC (±20 %) |
| Supply Voltage Range | 150 V DC ... 250 V DC (±20 %) |
| Power consumption | ≤ 4 W |
| Nominal frequency | 50 Hz ... 60 Hz (AC sine) |
General
| Measuring Principle | True r.m.s. value measurement |
| Measured value | AC sine (50 Hz/60 Hz) |
| Acquisition of harmonics | up to 63rd harmonic |
| Description of the input | Digital input in accordance with IEC/EN 61131-2 (type 3) |
| Number | 1 |
| Voltage input signal | 24 V DC |
| Voltage input signal | 0 V DC ... 30 V DC |
| Current Input Signal | 2 mA ... 15 mA |
| Protection | 250 mA (fast-blow) |
Measurement: Voltage
| Input name | Voltage measuring input V1, V2, V3 |
| Input voltage range direct | 35 V AC ... 690 V AC (Phase/Phase) |
| Input voltage range direct | 20 V AC ... 400 V AC (Phase/neutral conductor) |
| Input voltage range via external transformers | 60 V AC ... 2000000 V AC (primary) |
| Input voltage range via external transformers | 60 V AC ... 400 V AC (secondary) |
| Surge voltage capacity | 760 V AC (Phase/Phase) |
| Precision | 0.2 % |
| Power consumption | < 2 VA |
Measurement: Current
| Input name | Current measurement RC1, RC2, RC3 |
| Input Current | ≤ 400 A (Measurement level 1) |
| Input Current | ≤ 4000 A (Measurement level 2) |
| Input measuring range voltage | 500 µV ... 400 mV (1000 A) |
| Response threshold from measuring range nominal value | 5 A |
| Operate threshold | 500 µV (5 A) |
| Precision | 0.5 % |
Measurement: Power
| Precision | 1 % |
| Real energy (IEC 62053-21) | Class 1 |
| Reactive power (IEC 62053-23) | Class 2 |
Output data
| Output description | Digital output in accordance with IEC/EN 61131-2 (type 3) |
| Number | 1 |
| Current Output Signal | ≤ 100 mA |
| Voltage output signal | 24 V DC |
| Protection | 250 mA (fast-blow) |
Current / voltage / supply
| Connection Method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 6 mm² |
| Conductor cross section flexible | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 10 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
Digital I/O / communication
| Connection Method | Screw connection |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
Data: Network interface
| Communication Protocol | Modbus/TCP |
| Communication Protocol | REST |
| Connection Method | RJ45 |
| Communication Protocol | EtherNet/IP™ |
| Connection Method | RJ45 |
| Number of Connections | 2 |
| Note | DLR ready |
Dimensions
| Width | 90 mm |
| Height | 80 mm |
| Depth | 82 mm |
Material specifications
| Color | gray (RAL 7042) |
Ambient conditions
| Degree of protection (Housing) | IP20 (Housing) |
| Ambient Temperature (Operation) | -10 °C ... 55 °C |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Altitude | ≤ 2000 m |
| Max. permissible relative humidity (operation) | ≤ 95 % (non-condensing) |
| Max. salt spray content | ≤ 2.5 % |
CE
| Certificate | CE-compliant |
UKCA
| Certificate | UKCA-compliant |
UL, USA/Canada
| Identification | UL/C-UL Listed UL 61010-1 |
UL data
| Operating mode | Indoor use |
| Operating mode | Indoor use |
Mounting
| Mounting Type | DIN rail mounting |
| Mounting Position | Horizontal DIN rail |
Accessories
Why Proax for Phoenix Contact 2907976?
Proax is an authorized distributor of Phoenix Contact 2907976 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.