QUINT4-UPS/24DC/24DC/40 - Uninterruptible power supply

QUINT USV, IQ Technology, DIN rail mounting, Screw connection, input: 24 V DC, output: 24 V DC / 40 A, charging current: 5 A

  • Easy integration into networks using PROFINET, EtherNet/IP, EtherCAT® and USB interfaces
  • Evaluation of state of health (SOH) and state of charge (SOC), thanks to the intelligent battery management system (BMS)
  • Automatic recognition of the battery capacities and technologies (VRLA-WTR, LI-ION)
  • Monitoring of output current and voltage, as well as manual connection and disconnection of the system
  • SFB Technology selectively trips standard miniature circuit breakers. Loads connected in parallel continue working.
Technical Specifications

Input data

Input Voltage24 V DC
Input voltage range18 V DC ... 30 V DC
Electric strength, max.35 V DC (Protected against polarity reversal)
Internal input fuseno
Typical national grid voltage24 V DC
Voltage type of supply voltageDC
Inrush Current≤ 9 A (≤ 4 ms)
Reverse polarity protectionyes
Fixed backup threshold22 V DC
Fixed backup threshold30 V DC
Dynamic activation threshold> 1 V / 100 ms
Switch-on timemax. 3 s
Switch-on time during battery operation (Bat.-Start)8 s
Voltage drop, input/output0.5 V DC
Current consumption IN (UN, IOUT = IN, Icharge = 0)40.1 A
Current consumption Imax (UN, IOUT = IStat.Boost, Icharge = max)51.2 A
Current consumption INo-Load(UN, IOUT = 0, Icharge = 0)50 mA
Current consumption Icharge (UN, IOUT = 0, Icharge = max)6.1 A
Power consumption PN (UN, IOUT = IN, Icharge = 0)965 W
Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max)1120 W
Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0)1.3 W
Power consumption Pcharge (UN, IOUT = 0, Icharge = max)147 W

Signal state Bat.-Start

Connection labeling3.8 (+)
ChannelDI (digital input)
StateBat.-Mode
State conditionLow level (30 ms)
Signal - state assignmentlow - active
Reference potential3.9 (SGnd, identical to 1.2, 2.2, 4.2)
LED status indicatorYellow (Bat.-Mode)

Signal state PS Boost

Connection labeling3.7 (+)
Channel (configurable)DI (digital input) default, AI (analog input)
State (configurable)Charging current reduced
State conditionLow level
Signal - state assignmentlow - active
Unit signalI (mA)
Reference potential3.9 (SGnd, identical to 1.2, 2.2, 4.2)

Signal state Remote

Connection labeling3.6 (+)
ChannelDI (digital input)
State (configurable)Disconnection
State conditionLow level
Signal - state assignmentlow - active
Reference potential3.9 (SGnd, identical to 1.2, 2.2, 4.2)
LED status indicatorGreen, flashing (DC OK)

Output data

Efficiencytyp. 98 %
Number of Outputs1
Short-circuit-proofyes
No-load proofyes
Switch-over time0 ms
Output current limitIn mains mode according to connected upstream current limiting device
Output current limit> 45 A (Battery operation)
Power dissipation2.8 W (Mains operation)
Power dissipation13 W (Mains operation)
Power dissipation3.51 W (Battery operation)
Power dissipation16.4 W (Battery operation)
UPS connection in parallelno
UPS connection in seriesno
Energy storage device connection in parallelYes, 5 (observe line protection)
Energy storage device connection in seriesno

Mains operation

Output Voltage24 V DC (UOUT = UIN - 0.5 V DC)
Output voltage range18 V DC ... 30 V DC
Output voltage range18 V DC ... 32 V DC
Output current IN40 A
Static Boost (IStat.Boost)45 A
Dynamic Boost (IDyn.Boost)60 A (5 s)
Selective Fuse Breaking (ISFB)215 A (15 ms)
Output power POUT (UN, IOUT = IN)960 W
Output power POUT (UN, IOUT = Istat.Boost)1080 W

Battery operation

Output Voltage24 V DC (UOUT = UBAT - 0.5 V DC)
Output voltage range19 V DC ... 32 V DC
Output current IN40 A
Static Boost (IStat.Boost)45 A
Selective Fuse Breaking (ISFB)215 A (15 ms)
Output power POUT (UN, IOUT = IN)960 W
Output power POUT (UN, IOUT = Istat.Boost)1080 W

Signal supply 24 V DC, 20 mA, SGnd

Connection labeling3.1 (+), 3.9 (SGnd)
Reference potential3.9 (SGnd, identical to 1.2, 2.2, 4.2)

Signal state Alarm

Connection labeling3.2, 3.3
ChannelDO (digital output)
Switching voltagemax. 30 V AC/DC
Switch contact (floating)OptoMOS
State (configurable)Group alarm
State condition (configurable)Alarm threshold
Current carrying capacitymax. 100 mA
State - signal assignmentNC (Normally Closed)
LED status indicatorred (Alarm)

Signal state Bat. mode

Connection labeling3.4 (+)
ChannelDO (digital output)
Semiconductor outputMOSFET
State (configurable)Bat.-Mode
State condition (configurable)UIN < 18 V DC, UIN > 30 V DC, Bat.-Start
State - signal assignmentactive - high
Reference potential3.9 (SGnd, identical to 1.2, 2.2, 4.2)
LED status indicatorYellow (Bat.-Mode)

Signal state Ready

Connection labeling3.5 (+)
ChannelDO (digital output)
Semiconductor outputMOSFET
State (configurable)Ready
State condition (configurable)SOC = 100 %
State - signal assignmentactive - high
Reference potential3.9 (SGnd, identical to 1.2, 2.2, 4.2)
LED status indicatorGreen (state of charge - SOC)

Energy storage

Nominal voltage UN24 V DC
End-of-charge voltage (temperature-compensated)25 V DC ... 32 V DC
End-of-charge voltage (configurable)27.6 V DC
Charging current (configurable)max. 5 A
Nominal capacity (without additional charger)7 Ah ... 135 Ah
Max. capacity135 Ah
Charging time500 min. (38 Ah)
Buffer time33 min. (38 Ah)
Deep discharge protection (configurable)19.2 V DC
Battery technologyVRLA, VRLA-WTR, LI-ION
Charge characteristic curveIU0U
IQ-Technologyyes
Temperature sensoryes
Temperature compensation (configurable)42 mV/K

Input

Position1.x

Conductor connection

Connection MethodScrew connection
rigid0.5 mm² ... 16 mm²
flexible0.5 mm² ... 16 mm²
flexible with ferrule without plastic sleeve0.5 mm² ... 16 mm²
flexible with ferrule with plastic sleeve0.5 mm² ... 16 mm²
rigid (AWG)8 ... 6 (Cu)
Stripping length10 mm (rigid/flexible)
Tightening torque1.2 Nm ... 1.5 Nm
Drive form screw headSlotted L

Output

Position2.x

Conductor connection

Connection MethodScrew connection
rigid0.5 mm² ... 16 mm²
flexible0.5 mm² ... 16 mm²
flexible with ferrule without plastic sleeve0.5 mm² ... 16 mm²
flexible with ferrule with plastic sleeve0.5 mm² ... 16 mm²
rigid (AWG)8 ... 6 (Cu)
Stripping length10 mm (rigid/flexible)
Stripping length8 mm (Ferrule)
Tightening torque1.2 Nm ... 1.5 Nm
Drive form screw headSlotted L

Signal

Position3.x

Conductor connection

Connection MethodPush-in connection
rigid0.2 mm² ... 1 mm²
flexible0.2 mm² ... 1 mm²
flexible with ferrule without plastic sleeve0.2 mm² ... 0.75 mm²
flexible with ferrule without plastic sleeve0.5 mm² (recommended)
flexible with ferrule with plastic sleeve0.2 mm² ... 0.75 mm²
rigid (AWG)24 ... 16 (Cu)
Stripping length8 mm (rigid/flexible)

Battery

Position4.x

Connection technology

Position marking4.1 (+), 4.2 (-), 4.3 ()

Conductor connection

Connection MethodScrew connection
rigid0.5 mm² ... 16 mm²
flexible0.5 mm² ... 16 mm²
flexible with ferrule without plastic sleeve0.5 mm² ... 16 mm²
flexible with ferrule with plastic sleeve0.5 mm² ... 16 mm²
rigid (AWG)20 ... 6 (Cu)
Stripping length10 mm (rigid/flexible)
Tightening torque1.2 Nm ... 1.5 Nm
Drive form screw headSlotted L

LED signaling

Types of signalingDC OK (green)
Types of signalingAlarm (red)
Types of signalingBat.-Mode (yellow)
Types of signalingSOC (red, green)
Types of signalingData (red, green)

Product properties

Product familyQUINT USV
MTBF (IEC 61709, SN 29500)> 1980000 h (25 °C)
MTBF (IEC 61709, SN 29500)> 1205000 h (40 °C)
MTBF (IEC 61709, SN 29500)> 604200 h (60 °C)
Environmental protection directiveRoHS Directive 2011/65/EU
Environmental protection directiveWEEE
Environmental protection directiveReach

Insulation characteristics

Protection classIII (without PE)
Degree of pollution2

Life expectancy (electrolytic capacitors)

Time126720 h

Item dimensions

Width47 mm
Height130 mm
Depth125 mm
Depth125 mm (Device depth (DIN rail mounting))

Item dimensions with alternative mounting

Width123 mm
Height130 mm
Depth49 mm

Installation dimensions

Installation distance right/left (active)5 mm / 5 mm (POut ≥50% )
Installation distance right/left (passive)0 mm / 0 mm (POut ≥50% )
Installation distance right/left (active, passive)0 mm / 0 mm (POut ≤50 %)
Installation distance top/bottom (active)50 mm / 50 mm (POut ≥50% )
Installation distance top/bottom (passive)40 mm / 20 mm (POut ≥50% )
Installation distance top/bottom (active, passive)40 mm / 20 mm (POut ≤50 %)

Mounting

Mounting TypeDIN rail mounting
Mounting PositionOn horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715

Material specifications

Flammability rating according to UL 94 (housing / terminal blocks)V0
Housing MaterialMetal
Hood versionStainless steel X6Cr17
Side element versionAluminum AlMg3

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (start-up type tested)-40 °C
Maximum altitude≤ 4000 m
Climatic class3K3 (EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (Operation)2.3g

Overvoltage category

EN 61010-1II (≤ 4000 m)
EN 61010-2-201II (≤ 4000 m)

Protective extra-low voltage

Standard designationProtective extra-low voltage
Standards/specificationsIEC 61010-1 (SELV)
Standards/specificationsIEC 61010-2-201 (PELV)

UL approval

IdentificationUL/C-UL Listed UL 61010-1
IdentificationUL/C-UL Listed UL 61010-2-201
IdentificationUL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)

CSA

IdentificationCAN/CSA-C22.2 No. 61010-1-12
IdentificationCAN/CSA-IEC 61010-2-201
IdentificationCAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)

CB scheme

IdentificationIEC 61010-1
IdentificationIEC 61010-2-201

DNV

IdentificationClass Guideline DNVGL-CG-0339
NoteLocation classes: Temperature D (see Application/Limitation), Humidity B, Vibration A/C, EMC B

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise emissionEN 61000-6-4
EMC requirements for noise immunityEN 61000-6-1
EMC requirements for noise immunityEN 61000-6-2
Noise immunityImmunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply)
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Noise emissionAdditional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge8 kV (Test Level 4)
Discharge in air15 kV (Test Level 4)
CommentsCriterion B

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 1 GHz
Test field strength20 V/m (Test Level 3)
Frequency Range1 GHz ... 6 GHz
Test field strength10 V/m (Test Level 3)
Frequency Range1 GHz ... 6 GHz
Test field strength10 V/m (Test Level 3)
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input4 kV (Test Level 4 - asymmetrical)
Output4 kV (Test Level 4 - asymmetrical)
Signal4 kV (Test Level 4 - asymmetrical)
CommentsCriterion B

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Input1 kV (Test Level 3 - symmetrical)
Input2 kV (Test Level 3 - asymmetrical)
Output1 kV (Test Level 3 - symmetrical)
Output2 kV (Test Level 3 - asymmetrical)
Signal1 kV (Test Level 2 - asymmetrical)
CommentsCriterion B

Conducted interference

Standards/regulationsEN 61000-4-6
I/O/Sasymmetrical
Frequency Range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)

Power frequency magnetic field

Standards/regulationsEN 61000-4-8
Frequency16.67 Hz
Frequency50 Hz
Frequency60 Hz
Test field strength100 A/m
Additional text60 s
CommentsCriterion A
Frequency50 Hz
Frequency60 Hz
Frequency Range50 Hz ... 60 Hz
Test field strength1 kA/m
Additional text3 s
Frequency0 Hz
Test field strength300 A/m
Additional textDC, 60 s

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Accessories

Why Proax for Phoenix Contact QUINT4-UPS/24DC/24DC/40?

Proax is an authorized distributor of Phoenix Contact QUINT4-UPS/24DC/24DC/40 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesQUINT4UPS24DC24DC40
Pack Size1
Recommended

Available for order

Phoenix Contact Availability