Official Distributor
SKU
MPN
VAL-MS 690 ST
Weight
0.08 kg
Series VAL-MS
VAL-MS 690 ST - Type 2 surge protection plug
Type 2 surge protection plug with high-capacity varistor for VAL-MS base element, thermal monitoring, visual fault warning. Design: 690 V AC
Technical Specifications
General
Note | For use in all low-voltage systems between L-PEN.Only for use in IT systems between L-PE if the bodies of the equipment in the low-voltage system are connected to the grounding system of the transformer station. (common grounding of the HV transformer station and the bodies of the LV consumer's installation. RE = RA according to IEC 60364-4-442/VDE 0100-442 Figure 44D/example a) |
Note | A maximum backup fuse (with branch line wiring) of F=250 A gG can be used for systems with a prospective short-circuit current of between 3 kA to 50 kA. |
Product properties
Product family | VALVETRAB MS |
IEC test classification | II |
IEC test classification | T2 |
EN type | T2 |
IEC power supply system | TN |
IEC power supply system | IT |
Type | Male |
Distance between live and grounded parts | 8 mm |
Number of Positions | 1 |
Surge protection fault message | optical |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
Electrical properties
Nominal frequency fN | 50 Hz (60 Hz) |
Connection data
Connection Method | pluggable |
Dimensions
Width | 17.5 mm |
Height | 52.4 mm |
Depth | 55.3 mm |
Horizontal pitch | 1 Div. |
Material specifications
Color | black (RAL 9005) |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PA 6.6 |
Material group | I |
Housing Material | PA 6.6 |
Protective circuit
Mode of protection | L-PE (IT) |
Mode of protection | L-PEN (TN-C) |
Direction of action | 1L-N/PE |
Nominal voltage UN | 554/960 V AC (TN) |
Nominal voltage UN | 690 V AC (IT) |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 760 V AC |
Residual current IPE | ≤ 0.5 mA |
Standby power consumption PC | ≤ 400.00 mVA |
Nominal discharge current In (8/20) µs | 20 kA |
Maximum discharge current Imax (8/20) µs | 30 kA |
Short-circuit current rating ISCCR | 25 kA |
Voltage protection level Up | ≤ 2.9 kV |
TOV behavior at UT | 1005 V AC (5 s / withstand mode) |
TOV behavior at UT | 1056 V AC (120 min / safe failure mode) |
Response time tA | ≤ 25 ns |
Max. backup fuse with branch wiring | 200 A (gG) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 85 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m (amsl) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (Operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
UL specifications
Maximum continuous operating voltage MCOV (L-N) | 750 V AC |
Nominal discharge current In (L-N) | 20 kA |
Mode of protection | L-N |
Nominal Voltage | 690 V AC |
Power distribution system | Single phase |
Nominal frequency | 50/60 Hz |
Measured limiting voltage MLV (L-N) | 3040 V |
SPD Type | 4CA |
Standards and Regulations
Standards/specifications | IEC 61643-11 |
Note | 2011 |
Standards/specifications | EN 61643-11 |
Note | 2012 |
Mounting
Mounting Type | on base element |
Accessories
Why Proax for Phoenix Contact 1068842?
Proax is an authorized distributor of Phoenix Contact 1068842 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 10 |
Recommended