Official Distributor
SKU
MPN
VAL-MS 600DC-PV-ST
Weight
0.065 kg
Series VAL-MS
VAL-MS 600DC-PV-ST - Type 2 surge protection plug
Replacement plug for PV arrester combinations from the VAL-MS 600DC-PV-... product range
Technical Specifications
Product properties
Product family | VALVETRAB MS |
IEC test classification | PV II |
IEC test classification | PV T2 |
EN type | T2 |
IEC power supply system | DC |
Type | Male |
Number of Positions | 1 |
Installation location | Interior |
Installation location of the disconnect device | Internal |
Accessibility | Accessible |
Connection configuration | Y configuration |
SPD failure behavior | OCFM (Open-Circuit Failure Mode) |
Surge protection fault message | optical |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
Connection data
Connection Method | pluggable |
Dimensions
Width | 17.5 mm |
Height | 52.4 mm |
Depth | 55.3 mm |
Horizontal pitch | 1 Div. |
Material specifications
Color | black (RAL 9005) |
Color | black (RAL 9005) |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PA 6.6-FR |
Material group | I |
Housing Material | PA 6.6-FR |
Protective circuit
Standby power consumption PC | ≤ 25.00 mVA |
Nominal discharge current In (8/20) µs | 15 kA |
Maximum discharge current Imax (8/20) µs | 40 kA |
Voltage protection level Up | ≤ 1.4 kV |
Residual voltage Ures | ≤ 1.4 kV (at In) |
Residual voltage Ures | ≤ 1.1 kV (at 5 kA) |
Residual voltage Ures | ≤ 1.3 kV (at 10 kA) |
Residual voltage Ures | ≤ 1.5 kV (at 20 kA) |
Residual voltage Ures | ≤ 1.8 kV (at 30 kA) |
Residual voltage Ures | ≤ 2 kV (at 40 kA) |
Response time tA | ≤ 25 ns |
PV protective circuit
Connection configuration | Y configuration |
SPD failure behavior | OCFM (Open-Circuit Failure Mode) |
Protective circuit DC voltage side (DC)
Open circuit voltage UOCSTC | ≤ 330 V DC |
Maximum discharge current Imax (8/20) µs | 40 kA |
Response time tA | ≤ 25 ns |
Insulation resistance Riso | > 5 GΩ (at 500 V DC) |
Nominal discharge current In (8/20) µs | 15 kA |
Continuous operating current ICPV | 20 µA |
Maximum continuous operating voltage UCPV | 400 V DC |
Short-circuit current rating ISCPV | 2000 A |
Residual voltage Ures | ≤ 1.4 kV (at In) |
Residual voltage Ures | ≤ 1.1 kV (at 5 kA) |
Residual voltage Ures | ≤ 1.3 kV (at 10 kA) |
Residual voltage Ures | ≤ 1.5 kV (at 20 kA) |
Residual voltage Ures | ≤ 1.8 kV (at 30 kA) |
Residual voltage Ures | ≤ 2 kV (at 40 kA) |
Voltage protection level Up | ≤ 1.4 kV |
Standby power consumption PC | ≤ 25.00 mVA |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (Operation) | 7.5g (5-500 Hz/2.5 h/XYZ) |
UL specifications
Maximum continuous operating voltage MCOV | 800 V DC |
Short-circuit current rating (SCCR) | 50 kA |
Voltage protection rating VPR | 2 kV |
Nominal discharge current In | 20 kA |
Mode of protection | (L+) - (L-) |
Mode of protection | (L+) - G |
Mode of protection | (L-) - G |
Nominal Voltage | 800 V DC |
Power distribution system | DC PV |
SPD Type | 1CA |
Standards and Regulations
Standards/specifications | EN 61643-31 |
Note | 2019 |
Standards/specifications | IEC 61643-31 |
Note | 2018 |
Mounting
Mounting Type | on base element |
Accessories
Why Proax for Phoenix Contact 2800623?
Proax is an authorized distributor of Phoenix Contact 2800623 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.