VAL-MS 320 RW/1+1-FM/60
Series VAL-MS

VAL-MS 320 RW/1+1-FM/60 -

Technical Specifications

Dimensions

Height96.8 mm
Width35.6 mm
Depth65.7 mm (incl. DIN rail 7.5 mm)
Horizontal pitch2 Div.

Ambient conditions

Degree of ProtectionIP20 (only when all terminal points are used)
Ambient Temperature (Operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (Operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
IEC test classificationT2
EN typeT2
Mode of protectionL-N
Mode of protectionL-PE
Mode of protectionN-PE
Mounting TypeDIN rail: 35 mm
Colorjet black RAL 9005
Housing MaterialPA 6.6
Housing MaterialPBT
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of Positions2
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN240/415 V AC (TN-S)
Nominal voltage UN240/415 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N)335 V AC
Maximum continuous operating voltage UC (L-PE)335 V AC
Maximum continuous voltage UC (N-PE)260 V AC
Rated load current IL80 A
Residual current IPE≤ 5 µA
Standby power consumption PC≤ 150 mVA
Nominal discharge current In (8/20) µs20 kA
Maximum discharge current Imax (8/20) µs40 kA
Impulse discharge current (10/350) µs (L-N), charge3.5 As
Impulse discharge current (10/350) µs (L-N), specific energy12.25 kJ/Ω
Impulse discharge current (10/350) µs (L-N), peak current value Iimp7 kA
Impulse discharge current (10/350) µs (L-PE), charge1.25 As
Impulse discharge current (10/350) µs (L-PE), specific energy1.56 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp2.5 kA
Impulse discharge current (10/350) µs (N-PE), charge1.25 As
Impulse discharge current (10/350) µs (N-PE), specific energy1.56 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp2.5 kA
Follow current interrupt rating Ifi (N-PE)100 A
Short-circuit current rating ISCCR25 kA
Voltage protection level Up (L-N)≤ 1.5 kV
Voltage protection level Up (L-PE)≤ 1.8 kV
Voltage protection level Up (N-PE)≤ 1.5 kV
Residual voltage Ures (L-N)≤ 1.5 kV (at In)
Residual voltage Ures (L-N)≤ 1.3 kV (at 10 kA)
Residual voltage Ures (L-N)≤ 1.2 kV (at 5 kA)
Residual voltage Ures (L-N)≤ 1.1 kV (at 3 kA)
Residual voltage Ures (L-PE)≤ 1.8 kV (at In)
Residual voltage Ures (L-PE)≤ 1.4 kV (at 10 kA)
Residual voltage Ures (L-PE)≤ 1.2 kV (at 5 kA)
Residual voltage Ures (L-PE)≤ 1.1 kV (at 3 kA)
Residual voltage Ures (N-PE)≤ 0.4 kV (at In)
Residual voltage Ures (N-PE)≤ 0.25 kV (at 10 kA)
Residual voltage Ures (N-PE)≤ 0.15 kV (at 5 kA)
Residual voltage Ures (N-PE)≤ 0.1 kV (at 3 kA)
TOV behavior at UT (L-N)415 V AC (5 s / withstand mode)
TOV behavior at UT (L-N)440 V AC (120 min / safe failure mode)
TOV behavior at UT (N-PE)1200 V AC (200 ms / withstand mode)
Response time tA (L-N)≤ 25 ns
Response time tA (L-PE)≤ 100 ns
Response time tA (N-PE)≤ 100 ns
Max. backup fuse with V-type through wiring80 A (gG)
Max. backup fuse with branch wiring125 A (gG)

Indicator/remote signaling

Switching functionChangeover contact
Operating Voltage5 V AC ... 250 V AC
Operating Voltage30 V DC
Operating current5 mA AC ... 1.5 A AC
Operating current1 A DC
Connection MethodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection MethodScrew connection
Screw threadM5
Tightening torque3 Nm (1.5 mm² ... 16 mm²)
Tightening torque4.5 Nm (25 mm² ... 35 mm²)
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 25 mm²
Conductor cross section solid1.5 mm² ... 35 mm²
Conductor cross section AWG15 ... 2
Connection MethodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
Standards/regulationsEN 61643-11 2012

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
China RoHSNo hazardous substances above threshold values
Accessories

Why Proax for Phoenix Contact 1050286?

Proax is an authorized distributor of Phoenix Contact 1050286 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size60
Recommended
Sold in quantities of 60

Available for order

Phoenix Contact Availability