Technical Specifications
Dimensions
Height | 96.8 mm |
Width | 35.6 mm |
Depth | 65.7 mm (incl. DIN rail 7.5 mm) |
Horizontal pitch | 2 Div. |
Ambient conditions
Degree of Protection | IP20 (only when all terminal points are used) |
Ambient Temperature (Operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (Operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
IEC test classification | II |
IEC test classification | T2 |
EN type | T2 |
Mode of protection | L-N |
Mode of protection | L-PE |
Mode of protection | N-PE |
Mounting Type | DIN rail: 35 mm |
Color | jet black RAL 9005 |
Housing Material | PA 6.6 |
Housing Material | PBT |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | DIN rail module, two-section, divisible |
Number of Positions | 2 |
Surge protection fault message | Optical, remote indicator contact |
Protective circuit
Nominal voltage UN | 240/415 V AC (TN-S) |
Nominal voltage UN | 240/415 V AC (TT) |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous operating voltage UC (L-N) | 335 V AC |
Maximum continuous operating voltage UC (L-PE) | 335 V AC |
Maximum continuous voltage UC (N-PE) | 260 V AC |
Rated load current IL | 80 A |
Residual current IPE | ≤ 5 µA |
Standby power consumption PC | ≤ 150 mVA |
Nominal discharge current In (8/20) µs | 20 kA |
Maximum discharge current Imax (8/20) µs | 40 kA |
Impulse discharge current (10/350) µs (L-N), charge | 3.5 As |
Impulse discharge current (10/350) µs (L-N), specific energy | 12.25 kJ/Ω |
Impulse discharge current (10/350) µs (L-N), peak current value Iimp | 7 kA |
Impulse discharge current (10/350) µs (L-PE), charge | 1.25 As |
Impulse discharge current (10/350) µs (L-PE), specific energy | 1.56 kJ/Ω |
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp | 2.5 kA |
Impulse discharge current (10/350) µs (N-PE), charge | 1.25 As |
Impulse discharge current (10/350) µs (N-PE), specific energy | 1.56 kJ/Ω |
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp | 2.5 kA |
Follow current interrupt rating Ifi (N-PE) | 100 A |
Short-circuit current rating ISCCR | 25 kA |
Voltage protection level Up (L-N) | ≤ 1.5 kV |
Voltage protection level Up (L-PE) | ≤ 1.8 kV |
Voltage protection level Up (N-PE) | ≤ 1.5 kV |
Residual voltage Ures (L-N) | ≤ 1.5 kV (at In) |
Residual voltage Ures (L-N) | ≤ 1.3 kV (at 10 kA) |
Residual voltage Ures (L-N) | ≤ 1.2 kV (at 5 kA) |
Residual voltage Ures (L-N) | ≤ 1.1 kV (at 3 kA) |
Residual voltage Ures (L-PE) | ≤ 1.8 kV (at In) |
Residual voltage Ures (L-PE) | ≤ 1.4 kV (at 10 kA) |
Residual voltage Ures (L-PE) | ≤ 1.2 kV (at 5 kA) |
Residual voltage Ures (L-PE) | ≤ 1.1 kV (at 3 kA) |
Residual voltage Ures (N-PE) | ≤ 0.4 kV (at In) |
Residual voltage Ures (N-PE) | ≤ 0.25 kV (at 10 kA) |
Residual voltage Ures (N-PE) | ≤ 0.15 kV (at 5 kA) |
Residual voltage Ures (N-PE) | ≤ 0.1 kV (at 3 kA) |
TOV behavior at UT (L-N) | 415 V AC (5 s / withstand mode) |
TOV behavior at UT (L-N) | 440 V AC (120 min / safe failure mode) |
TOV behavior at UT (N-PE) | 1200 V AC (200 ms / withstand mode) |
Response time tA (L-N) | ≤ 25 ns |
Response time tA (L-PE) | ≤ 100 ns |
Response time tA (N-PE) | ≤ 100 ns |
Max. backup fuse with V-type through wiring | 80 A (gG) |
Max. backup fuse with branch wiring | 125 A (gG) |
Indicator/remote signaling
Switching function | Changeover contact |
Operating Voltage | 5 V AC ... 250 V AC |
Operating Voltage | 30 V DC |
Operating current | 5 mA AC ... 1.5 A AC |
Operating current | 1 A DC |
Connection Method | Plug-in/screw connection via COMBICON |
Screw thread | M2 |
Tightening torque | 0.25 Nm |
Stripping length | 7 mm |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Connection data
Connection Method | Screw connection |
Screw thread | M5 |
Tightening torque | 3 Nm (1.5 mm² ... 16 mm²) |
Tightening torque | 4.5 Nm (25 mm² ... 35 mm²) |
Stripping length | 16 mm |
Conductor cross section flexible | 1.5 mm² ... 25 mm² |
Conductor cross section solid | 1.5 mm² ... 35 mm² |
Conductor cross section AWG | 15 ... 2 |
Connection Method | Fork-type cable lug |
Conductor cross section flexible | 1.5 mm² ... 16 mm² |
Standards and Regulations
Standards/regulations | IEC 61643-11 2011 |
Standards/regulations | EN 61643-11 2012 |
Environmental Product Compliance
REACh SVHC | Lead 7439-92-1 |
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
China RoHS | No hazardous substances above threshold values |
Accessories
Why Proax for Phoenix Contact 1050286?
Proax is an authorized distributor of Phoenix Contact 1050286 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 60 |