2800419
SKU
PHX2800419
MPN
PWT 35-800AC-FM
Weight
3.5 kg
This product is Not Cancellable/Not Returnable
Series PWT
PWT 35-800AC-FM - Lightning/surge arrester type 1/2
Lightning/surge arrester, according to type 1/2 / class I/II, for 1-phase power supply networks with combined PE and N installed in one conductor (L1, PEN).
- Use in harsh environments with robust design
- Universal solution for various network types
- Function monitoring using optical status indicator
- Multi-stage status monitoring via remote indication contact
Technical Specifications
General
| Note | Assembling: Two 8 mm screws with 8 Nm on an isolated or grounded surface |
| Note | Long-wave surge current 2 ms in accordance with IEC 60099-4: 250 x 1.0 kA; 500 x 0.5 kA. |
Product properties
| Product family | POWERTRAB |
| IEC test classification | I / II |
| IEC test classification | T1 / T2 |
| EN type | T1 / T2 |
| IEC power supply system | TN-C |
| IEC power supply system | IT |
| Type | Installation module |
| Number of Positions | 1 |
| Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics
| Overvoltage category | 8 kV: IV (600 V), III (1000 V) |
| Pollution degree | 3 |
Electrical properties
| Nominal frequency fN | 50 Hz (60 Hz) |
| Nominal voltage UN | 690 V AC |
Indicator/remote signaling
| Connection name | Remote fault indicator contact |
| Switching function | 2x N/C contacts, 1-pos. |
| Operating Voltage | 30 V AC |
| Operating Voltage | 30 V DC |
| Operating current | 1.5 A AC |
| Operating current | 1.5 A DC |
Supply: Status indicator/remote signaling
| Operating Voltage | 19.2 V AC/DC ... 30 V AC/DC |
| Operating current | 7 mA AC/DC ... 13 mA AC/DC |
| Rated current | 10 mA AC/DC |
| Max. required back-up fuse | 1 A (e.g. T to IEC 127-2/III) |
| Immunity to interference according to IEC 61000-4-5 (line-line) | 1 kV |
| Immunity to interference according to IEC 61000-4-5 (line-earth) | 6 kV |
Double terminal point
| Connection Method | Screw connection |
| Screw thread | M6 |
| Tightening torque | 8.5 Nm |
| Stripping length | 24 mm |
| Conductor cross section flexible | 16 mm² ... 50 mm² |
| Conductor cross section rigid | 16 mm² ... 50 mm² |
| Conductor cross section AWG | 6 ... 1/0 |
PE conductor connection
| Connection Method | Ring cable lug |
| Tightening torque | 20 Nm |
| Conductor cross section flexible | 16 mm² ... 95 mm² |
| Conductor cross section rigid | 16 mm² ... 95 mm² |
| Conductor cross section AWG | 6 ... 3/0 |
Remote fault indicator contact
| Screw thread | M3 |
| Tightening torque | 0.55 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
Dimensions
| Width | 56 mm |
| Height | 191 mm |
| Depth | 280 mm |
| Horizontal pitch | 3 Div. |
Material specifications
| Color | Silver |
| Flammability rating according to UL 94 | V-2 |
| CTI value of material | 600 |
| CTI value of material | 250 |
| Insulating material | PA/PC |
| Material group | I (PA 6.6/PC) |
| Material group | IIIa (PA 4.6) |
| Housing Material | Die-cast aluminum, salt water resistant |
| Housing surface material | die-cast aluminum |
Mechanical data
| Open side panel | No |
Protective circuit
| Mode of protection | L-PE |
| Direction of action | 1L-PEN |
| Nominal voltage UN | 690 V AC |
| Nominal voltage UN | 554/960 V AC (TN-C) |
| Nominal voltage UN | 690 V AC (IT) |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC (L-PE) | 800 V AC |
| Rated load current IL | 150 A (Serial through wiring with 50 mm²) |
| Residual current IPE | ≤ 20 µA |
| Standby power consumption PC | ≤ 16.00 mVA |
| Nominal discharge current In (8/20) µs (L-PE) | 35 kA |
| Maximum discharge current Imax (8/20) µs (L-PE) | 100 kA |
| Impulse discharge current (10/350) µs (L-PE), charge | 17.5 As |
| Impulse discharge current (10/350) µs (L-PE), specific energy | 305 kJ/Ω |
| Impulse discharge current (10/350) µs (L-PE), peak current value Iimp | 35 kA |
| Follow current interrupt rating Ifi (L-PE) | 50 kA |
| Short-circuit current rating ISCCR | 50 kA |
| Voltage protection level Up (L-PE) | ≤ 4.5 kV |
| Residual voltage Ures (L-PE) | ≤ 2.7 kV (at In) |
| Residual voltage Ures (L-PE) | ≤ 2.5 kV (at 20 kA) |
| Residual voltage Ures (L-PE) | ≤ 2.3 kV (at 10 kA) |
| Residual voltage Ures (L-PE) | ≤ 2.2 kV (at 5 kA) |
| Residual voltage Ures (L-PE) | ≤ 2.1 kV (at 3 kA) |
| TOV behavior at UT (L-PE) | 1960 V AC (200 ms / withstand mode) |
| TOV behavior at UT (L-PE) | 1500 V AC (5 s / withstand mode) |
| Response time tA (L-PE) | ≤ 100 ns |
| Max. backup fuse with V-type through wiring | 125 A (gG at ≥35 mm²) |
| Max. backup fuse with branch wiring | 400 A (gG at 2x 50 mm²) |
| Max. backup fuse with branch wiring | 800 A (aR (only up to Iimp = 25 kA)) |
Ambient conditions
| Degree of Protection | IP20 (only when all terminal points are used) |
| Ambient Temperature (Operation) | -40 °C ... 80 °C |
| Ambient Temperature (Operation) | -40 °C ... 55 °C (serial through wiring ≥ 35 mm²) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 4000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (Operation) | 5g (10 ... 150 Hz / 2.5 h / X, Y, Z) |
| Vibration (Operation) | 4g (5 ... 100 Hz / X, Y, Z - according to GL ) |
UL specifications
| Maximum continuous operating voltage MCOV (L-G) | 800 V AC |
| Nominal discharge current In (L-G) | 20 kA |
| Mode of protection | L-G |
| Nominal Voltage | 690 V AC |
| Power distribution system | Single phase |
| Nominal frequency | 60 Hz |
| Measured limiting voltage MLV (L-G) | 4370 V |
| SPD Type | 4CA |
UL indicator/remote signaling
| Operating Voltage | 30 V AC |
| DC operating voltage | 30 V DC |
| AC operating current | 1.5 A AC |
| DC operating current | 1.5 A DC |
UL connection data Double terminal point
| Tightening torque | 75 lbf-in. |
| Conductor cross section AWG | 1/0 ... 6 |
UL connection data PE conductor connection
| Tightening torque | 175 lbf-in. |
| Conductor cross section AWG | 3/0 |
Standards and Regulations
| Standards/specifications | IEC 61643-11 |
| Note | 2011 |
| Standards/specifications | EN 61643-11 |
| Note | 2012 |
Mounting
| Mounting Type | Screw mounting |
Why Proax for Phoenix Contact 2800419?
Proax is an authorized distributor of Phoenix Contact 2800419 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.