2737384
SKU
PHX2737384
MPN
IBS RL 480 MLR R DIO6/1-LK
Weight
4.301 kg
This product is Not Cancellable/Not Returnable
Series IBS-RL
IBS RL 480 MLR R DIO6/1-LK - Motor starter
Electromechanical reversing load motor starter for INTERBUS; fiber optic technology with 500 kbaud, inputs (24 V DC), integrated motor protection relay (220 V AC to 480 V AC; 8 A, maximum), sensor connection via 5-pos. M12 female connectors, rugged metal housing, IP67 protection
- Rugged Line connector for INTERBUS with fiber optic and supply voltage
- M12 connector for digital inputs
- COMBICON connector for motor output
- Comprehensive diagnostic functions including motor current monitoring
- Emergency operation on the device or via external operating elements
- Rugged metal housing
Technical Specifications
Dimensions
| Width | 185.1 mm |
| Height | 193 mm |
| Depth | 138 mm |
Utilization restriction
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
INTERBUS
| Connection Method | Fiber optics |
| Transmission Speed | 500 kbps |
Module
| ID code (dec.) | 3 |
| ID code (hex) | 03 |
| Length code (hex) | 01 |
| Length code (dec) | 1 |
| Process data channel | 16 bit |
| Input address area | 2 Byte |
| Output address area | 2 Byte |
| Register length | 2 Byte |
Digital: Digital inputs
| Number of Inputs | 6 |
| Connection Method | M12 connector |
| Connection technology | 3-, 4-conductor |
| Number of Positions | 5 |
| Input Voltage | 24 V DC (DIN EN 61131-2) |
| Input voltage range "0" signal | 0 V ... 5 V |
| Input voltage range "1" signal | 11 V ... 30 V |
| Filter time | 3 ms |
| Typical input current per channel | 5 mA (for US1 = 24 V) |
Product properties
| Product family | Ruggedline |
| Type | Block design |
| Diagnostics messages | Mains failure, phase failure, blown fuse Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
| Diagnostics messages | Motor connector not plugged in, motor temperature exceeded, thermistor line short-circuited Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
| Diagnostics messages | Sensor supply failure Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
| Diagnostics messages | Failure of the actuator supply Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
| Diagnostics messages | Motor overcurrent Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
| Diagnostics messages | Output stage cannot be controlled Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
| Diagnostics messages | Module error during self test Message to the master |
Supply: Module electronics
| Supply Voltage | 24 V DC |
| Supply Voltage Range | 18.5 V DC ... 32 V DC (including ripple) |
| Ripple | 3.6 Vpp |
Connection data
| Connection Method | M12 connector |
Ambient conditions
| Degree of Protection | IP65/IP67 |
| Ambient Temperature (Operation) | 0 °C ... 55 °C |
| Air pressure (operation) | 860 hPa ... 1080 hPa (up to 1500 m above sea level) |
| Air pressure (storage/transport) | 660 hPa ... 1080 hPa (up to 3500 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Permissible humidity (operation) | 100 % |
| Permissible humidity (storage/transport) | 95 % (non-condensing) |
Standards and Regulations
| Protection class | I (IEC 61140, EN 61140, VDE 0140-1) |
Air clearances and creepage distances
| Air clearances and creepage distances | in accordance with EN 50178: 1998 |
Mounting
| Mounting Type | on mounting panel |
| Mounting Type | Wall mounting |
Why Proax for Phoenix Contact 2737384?
Proax is an authorized distributor of Phoenix Contact 2737384 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
IBS RL 480 MLR R DIO6/1-LK2MBD - Electromechanical reversing load motor starter for INTERBUS; fiber optic technology with 2 Mbaud, inputs (24 V DC), integrated motor protection relay (220 V AC to 480 V AC; 8 A, maximum), sensor connection via 5-pos. M12 female connectors, rugged metal housing, IP67 protection
IBS RL 400 MLR R DIO6/1 LK2MBD - Electromechanical reversing load motor starter for INTERBUS; fiber optic technology with 2 Mbaud, inputs (24 V DC), integrated motor protection relay (220 V AC to 440 V AC; 8 A, maximum), sensor connection via 5-pos. M12 female connectors, rugged metal housing, IP67 protection