SKU
MPN
IBS RL 480 MLR R DIO6/1-LK2MBD
Weight
4.151 kg
This product is Not Cancellable/Not Returnable
Series IBS-RL
IBS RL 480 MLR R DIO6/1-LK2MBD - Motor starter
Electromechanical reversing load motor starter for INTERBUS; fiber optic technology with 2 Mbaud, inputs (24 V DC), integrated motor protection relay (220 V AC to 480 V AC; 8 A, maximum), sensor connection via 5-pos. M12 female connectors, rugged metal housing, IP67 protection
- Rugged metal housing
- Emergency operation on the device or via external operating elements
- Comprehensive diagnostic functions including motor current monitoring
- Rugged Line connector for INTERBUS with fiber optic and supply voltage
- COMBICON connector for motor output
- M12 connector for digital inputs
Technical Specifications
Dimensions
Width | 185.1 mm |
Height | 193 mm |
Depth | 138 mm |
INTERBUS
Connection Method | Fiber optics |
Transmission Speed | 2 Mbps |
Module
ID code (dec.) | 3 |
ID code (hex) | 03 |
Length code (hex) | 01 |
Length code (dec) | 1 |
Process data channel | 16 bit |
Input address area | 2 Byte |
Output address area | 2 Byte |
Register length | 2 Byte |
Digital: Digital inputs
Number of Inputs | 6 |
Connection Method | M12 connector |
Connection technology | 3-, 4-conductor |
Number of Positions | 5 |
Input Voltage | 24 V DC (DIN EN 61131-2) |
Input voltage range "0" signal | 0 V ... 5 V |
Input voltage range "1" signal | 11 V ... 30 V |
Filter time | 3 ms |
Typical input current per channel | 5 mA (for US1 = 24 V) |
Product properties
Product family | Ruggedline |
Type | Block design |
Diagnostics messages | Mains failure, phase failure, blown fuse Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
Diagnostics messages | Motor connector not plugged in, motor temperature exceeded, thermistor line short-circuited Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
Diagnostics messages | Sensor supply failure Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
Diagnostics messages | Failure of the actuator supply Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
Diagnostics messages | Motor overcurrent Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
Diagnostics messages | Output stage cannot be controlled Error message in diagnostic code (bus) and display by means of the E LED on the motor starter |
Diagnostics messages | Module error during self test Message to the master |
Supply: Module electronics
Supply Voltage | 24 V DC |
Supply Voltage Range | 18.5 V DC ... 32 V DC (including ripple) |
Ripple | 3.6 Vpp |
Connection data
Connection Method | M12 connector |
Ambient conditions
Degree of Protection | IP65/IP67 |
Ambient Temperature (Operation) | 0 °C ... 55 °C |
Air pressure (operation) | 860 hPa ... 1080 hPa (up to 1500 m above sea level) |
Air pressure (storage/transport) | 660 hPa ... 1080 hPa (up to 3500 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Permissible humidity (operation) | 100 % |
Permissible humidity (storage/transport) | 95 % (non-condensing) |
Standards and Regulations
Protection class | I (IEC 61140, EN 61140, VDE 0140-1) |
Air clearances and creepage distances
Air clearances and creepage distances | in accordance with EN 50178: 1998 |
Mounting
Mounting Type | on mounting panel |
Mounting Type | Wall mounting |
Accessories
Why Proax for Phoenix Contact 2734497?
Proax is an authorized distributor of Phoenix Contact 2734497 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- IBS RL 480 MLR R DIO6/1-LK - Electromechanical reversing load motor starter for INTERBUS; fiber optic technology with 500 kbaud, inputs (24 V DC), integrated motor protection relay (220 V AC to 480 V AC; 8 A, maximum), sensor connection via 5-pos. M12 female connectors, rugged metal housing, IP67 protection
- IBS RL 400 MLR R DIO6/1 LK2MBD - Electromechanical reversing load motor starter for INTERBUS; fiber optic technology with 2 Mbaud, inputs (24 V DC), integrated motor protection relay (220 V AC to 440 V AC; 8 A, maximum), sensor connection via 5-pos. M12 female connectors, rugged metal housing, IP67 protection