2700775
SKU
PHX2700775
MPN
IB IL AO 2/UI-PAC
Weight
0.089 kg
Series IB-IL-AO
IB IL AO 2/UI-PAC - Analog module
Inline, Analog output terminal, Analog outputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
- 2 analog output channels
- Connection of actuators in 2-conductor technology
- Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
- Voltage ranges: 0 V ... 10 V, ±10 V
- Diagnostic and status indicators
Technical Specifications
Dimensions
| Width | 12.2 mm |
| Height | 119.8 mm |
| Depth | 71.5 mm |
| Note on dimensions | Housing dimensions |
Inline local bus
| Number of interfaces | 2 |
| Connection Method | Inline data jumper |
| Transmission Speed | 500 kbps |
| Transmission physics | Copper |
Module
| ID code (dec.) | 91 |
| ID code (hex) | 5B |
| Length code (hex) | 04 |
| Length code (dec) | 04 |
| Process data channel | 64 bit |
| Input address area | 8 Byte |
| Output address area | 8 Byte |
| Register length | 64 bit |
| Required parameter data | 10 Byte |
| Required configuration data | 5 Byte |
Analog:
| Output name | Analog outputs |
| Connection technology | 2-conductor |
| Note regarding the connection technology | shielded |
| Number of Outputs | 2 |
| D/A conversion time | typ. 10 µs |
| D/A converter resolution | 12 bit |
| Protective circuit | Short-circuit and overload protection; Electronic |
| Protective circuit | Transient protection; Suppressor diode |
| Data formats | IB IL, S7-compatible |
| Representation of output values | 12 bits (11 bits + sign bit) |
| Process data update | bus-synchronous |
| Current Output Signal | 0 mA ... 20 mA |
| Current Output Signal | 4 mA ... 20 mA |
| Current Output Signal | -20 mA ... 20 mA |
| Load/Output Load Current Output | ≤ 450 Ω |
| Voltage output signal | 0 V ... 10 V |
| Voltage output signal | -10 V ... 10 V |
| Load/output load voltage output | > 1 kΩ |
| Permissible cable length | max. 250 m (The specifications refer to nominal operation after complying with installation instructions. The specifications refer to the following reference cable type: Shielded power station cable: LiYCY; 2 x 2 x 0,5 mm²; VDE0812) |
Product properties
| Product family | Inline |
| Type | modular |
| Scope of delivery | including Inline connector and labeling field |
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler |
| Diagnostics messages | I/O supply failure Message in the diagnostic code (in the IB IL format) |
| Diagnostics messages | Short circuit/overload of the outputs Message in the diagnostic code (in the IB IL format) |
| Diagnostics messages | Configuration invalid Message in the diagnostic code (in the IB IL format) |
Insulation characteristics
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Electrical properties
| Maximum power dissipation for nominal condition | max. 1.97 W |
Potentials
| Power consumption | typ. 1.32 W (Nominal voltage load (UOUT1/2 = 10 V, RL = 1 kΩ)) |
| Power consumption | typ. 1.97 W (Nominal current load (IOUT1/2 = 20 mA, RL = 0 Ω)) |
Potentials: Communications power (UL)
| Supply Voltage | 7.5 V DC (via voltage jumper) |
| Current draw | max. 65 mA |
| Current draw | typ. 55 mA |
Potentials: Supply of analog modules (UANA)
| Supply Voltage | 24 V DC (via voltage jumper) |
| Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 75 mA (Nominal current load (IOUT1/2 = 20 mA, RL = 0 Ω)) |
| Current draw | max. 30 mA (No-load) |
| Current draw | typ. 38 mA (Nominal voltage load (UOUT1/2 = 10 V, RL = 1 kΩ)) |
| Current draw | max. 45 mA (Nominal voltage load (UOUT1/2 = 10 V, RL = 1 kΩ)) |
| Current draw | typ. 65 mA (Nominal current load (IOUT1/2 = 20 mA, RL = 0 Ω)) |
| Current draw | typ. 24 mA (No-load) |
Electrical isolation/isolation of the voltage ranges
| Test voltage: 7.5 V supply (bus logics)/24 V analog supply (analog I/O) | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V supply (bus logic)/functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V analog supply (analog I/O)/functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
| Connection name | Inline connector |
Conductor connection
| Connection Method | Spring-cage connection |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
Inline connector
| Connection Method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
Ambient conditions
| Ambient Temperature (Operation) | -25 °C ... 55 °C |
| Degree of Protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Standards and Regulations
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
| Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2700775?
Proax is an authorized distributor of Phoenix Contact 2700775 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
IB IL AO 2/UI-XC-PAC - Inline, Analog output terminal, Analog outputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connector and labeling field
IB IL AO 1/SF-XC-PAC - Inline, Analog output terminal, Analog output: 1, 0 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connectors and marking fields
IB IL AI 2/SF-PAC - Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
IB IL AI 2/SF-ME - Inline, Analog input terminal, Analog inputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field