S802S-D4 2 Poles D Characteristic 4A 6 kA 400/690 VAC High Performance Circuit Breaker HPCB
Technical Specifications
Technical
Standards | IEC/EN 60947-2 |
Standards | IEC/EN 60898-1 |
Standards | UL 1077 |
Tripping characteristic | D |
Rated Operational Voltage | acc. to IEC 60898-1 400 V AC |
Rated Operational Voltage | acc. to IEC 60947-2 690 V AC |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 690 V |
Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Input Voltage Type | AC/DC |
Rated Current (In) | 4 A |
Rated Short-Circuit Capacity | (400 V AC) 25 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (415 V AC) 50 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (440 V AC) 30 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (500 V AC) 15 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (690 V AC) 6 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (250 V DC) 30 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (415 V AC) 40 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (440 V AC) 22.5 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (500 V AC) 11 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (690 V AC) 4 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (250 V DC) 30 kA |
Rated Frequency (f) | 50/60 Hz |
Power Loss | 4 W |
Power Loss | at Rated Operating Conditions per Pole 2 W |
Contact Position Indication | ON / OFF / TRIP |
Energy Limiting Class | 3 |
Number of Protected Poles | 2 |
Number of Poles | 2 |
Overvoltage category | IV |
Tightening torque | 3.5 N·m |
Actuator Marking | I / O |
Housing Material | Insulation group I, RAL 7035 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting Position | Any |
Recommended Screw Driver | Pozidriv 2 |
Accessories Available | Yes |
Remarks | Connection from top and bottom Connecting with CU only IP40 in enclosure with cover Cage terminal with captive screw |
Connecting Capacity | Flexible 0 … 50 mm² |
Connecting Capacity | Rigid 0 … 70 mm² |
Terminal Type | Screw Terminals |
Technical UL/CSA
Interrupting Rating acc. to UL1077 | (240 V AC) 30 kA |
Interrupting Rating acc. to UL1077 | (480Y / 277 V AC) 14 kA |
Interrupting Rating acc. to UL1077 | (600Y / 347 V AC) 6 kA |
Dimensions
Width in Number of Modular Spacings | 3 |
Product Net Width | 54 mm |
Product Net Height | 95 mm |
Product Net Depth / Length | 82.5 mm |
Product Net Weight | 0.49 kg |
Built-In Depth (t2) | 82.5 mm |
Installation
Instructions and Manuals | 2CCC413016M0008 |
Why Proax for ABB S802S-D4?
Proax is an authorized distributor of ABB S802S-D4 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | S802SD4 |
Pack Size | 1 |
Recommended
- The S802S-D125 is a 2-pole High Performance Circuit breaker with D-Dharacteristic, with cage terminal and a rated current of 125 A. It is a current limiting device with a maximum breaking capacity of 50kA at 240/415V. It can be used for voltages up to 400/690V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S802S-D125 complies with IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S802S-D125 more comfortable. Due to the fast arc extinction of S802S-D125 your application will be secured.
- The S802S-D100 is a 2-pole High Performance Circuit breaker with D-Dharacteristic, with cage terminal and a rated current of 100 A. It is a current limiting device with a maximum breaking capacity of 50kA at 240/415V. It can be used for voltages up to 400/690V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S802S-D100 complies with IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S802S-D100 more comfortable. Due to the fast arc extinction of S802S-D100 your application will be secured.