AF205B-30-22RT-12
By ABB
SKU
ABBAF205B3022RT12
MPN
1SFL527062R1222
Weight
2.4 kg
The AF205B-30-22RT-12 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and ring tongue ferrules, controlling motors up to 110 kW / 400 V AC (AC-3) or 150 hp / 480 V UL and switching power circuits up to 350 A (AC-1) or 300 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories. Includes Mounting kit, containing all neccessary screws, washers and sockets for connecting the terminals, and screws for mounting the device.
Technical Specifications
Dimensions
| Product Net Width | 105 mm |
| Product Net Depth / Length | 152 mm |
| Product Net Height | 196 mm |
| Product Net Weight | 2.4 kg |
Technical
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 2 |
| Number of Auxiliary Contacts NC | 2 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 275 A |
| Rated Operational Current AC-1 (Ie) | (1000 V) 60 °C 250 A |
| Rated Operational Current AC-1 (Ie) | (1000 V) 70 °C 200 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 350 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 60 °C 300 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 70 °C 240 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 205 A |
| Rated Operational Current AC-3 (Ie) | (440 V) 55 °C 205 A |
| Rated Operational Current AC-3 (Ie) | (500 V) 55 °C 165 A |
| Rated Operational Current AC-3 (Ie) | (690 V) 55 °C 165 A |
| Rated Operational Current AC-3 (Ie) | (1000 V) 55 °C 100 A |
| Rated Operational Current AC-3 (Ie) | (380 / 400 V) 55 °C 205 A |
| Rated Operational Current AC-3 (Ie) | (220 / 230 / 240 V) 55 °C 205 A |
| Rated Operational Current DC-1 (Ie) | (100 V) 1 Pole, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (100 V) 1 Pole, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (100 V) 1 Pole, 70 °C 240 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 3 Poles in Series, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 3 Poles in Series, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 3 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-1 (Ie) | (175 V) 2 Poles in Series, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (175 V) 2 Poles in Series, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (175 V) 2 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-1 (Ie) | (200 V) 2 Poles in Series, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (200 V) 2 Poles in Series, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (200 V) 2 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-1 (Ie) | (220 V) 3 Poles in Series, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (220 V) 3 Poles in Series, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (220 V) 3 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-1 (Ie) | (260 V) 3 Poles in Series, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (260 V) 3 Poles in Series, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (260 V) 3 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-1 (Ie) | (300 V) 3 Poles in Series, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (300 V) 3 Poles in Series, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (300 V) 3 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 1-Pole, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 1-Pole, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 1-Pole, 70 °C 240 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 2 Poles in Series, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 2 Poles in Series, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 2 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 3 Poles in Series, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 3 Poles in Series, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 3 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-1 (Ie) | (90 V) 1 Pole, 40 °C 350 A |
| Rated Operational Current DC-1 (Ie) | (90 V) 1 Pole, 60 °C 300 A |
| Rated Operational Current DC-1 (Ie) | (90 V) 1 Pole, 70 °C 240 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 275 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 60 °C 275 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 3 Poles in Series, 40 °C 275 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 3 Poles in Series, 60 °C 275 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 3 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-3 (Ie) | (220 V) 3 Poles in Series, 40 °C 275 A |
| Rated Operational Current DC-3 (Ie) | (220 V) 3 Poles in Series, 60 °C 275 A |
| Rated Operational Current DC-3 (Ie) | (220 V) 3 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 2 Poles in Series, 40 °C 275 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 2 Poles in Series, 60 °C 275 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 2 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 3 Poles in Series, 40 °C 275 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 3 Poles in Series, 60 °C 275 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 3 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 275 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 60 °C 275 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 3 Poles in Series, 40 °C 275 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 3 Poles in Series, 60 °C 275 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 3 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-5 (Ie) | (220 V) 3 Poles in Series, 40 °C 275 A |
| Rated Operational Current DC-5 (Ie) | (220 V) 3 Poles in Series, 60 °C 275 A |
| Rated Operational Current DC-5 (Ie) | (220 V) 3 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 2 Poles in Series, 40 °C 275 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 2 Poles in Series, 60 °C 275 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 2 Poles in Series, 70 °C 240 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 3 Poles in Series, 40 °C 275 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 3 Poles in Series, 60 °C 275 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 3 Poles in Series, 70 °C 240 A |
| Rated Operational Power AC-3 (Pe) | (415 V) 110 kW |
| Rated Operational Power AC-3 (Pe) | (440 V) 132 kW |
| Rated Operational Power AC-3 (Pe) | (500 V) 110 kW |
| Rated Operational Power AC-3 (Pe) | (690 V) 160 kW |
| Rated Operational Power AC-3 (Pe) | (1000 V) 132 kW |
| Rated Operational Power AC-3 (Pe) | (380 / 400 V) 110 kW |
| Rated Operational Power AC-3 (Pe) | (220 / 230 / 240 V) 55 kW |
| Rated Breaking Capacity AC-3e | 8.5 x Ie AC-3e |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Rated Making Capacity AC-3e | 12 x Ie AC-3e |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 947 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 2050 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1640 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 670 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
| Rated Insulation Voltage (Ui) | acc. to UL/CSA 600 V |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Maximum Electrical Switching Frequency | (AC-3) 300 cycles per hour |
| Mechanical Durability | 5 million |
| Maximum Mechanical Switching Frequency | 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (Uc) | 50 Hz / 60 Hz 48 ... 130 V |
| Rated Control Circuit Voltage (Uc) | DC Operation 48 ... 130 V |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 4 V·A |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 60 Hz 4 V·A |
| Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·A |
| Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 180 V·A |
| Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage DC 150 V·A |
| Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage DC 150 W |
| Power Loss | 8 W |
| Power Loss | at Rated Operating Conditions per Pole 8 W |
| Connecting Capacity Main Circuit | Flexible 2 x 50 ... 95 mm² |
| Connecting Capacity Main Circuit | Rigid Cu-Cable 2 x 50 ... 120 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible 2x0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Solid 2 x 1 ... 4 mm² |
| Connecting Capacity Auxiliary Circuit | Stranded 2 x 1 .... 4 mm² |
| Connecting Capacity | Flexible 2 x 50 ... 95 mm² |
| Connecting Capacity | Rigid Cu-Cable 2 x 50 ... 120 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40 |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Tightening torque | Cable Lug 9 N·m |
| Tightening torque | Main Circuit 14 ... 31 N·m |
| Terminal Type | Main Circuit: Bars |
| Product Name | Block Contactor |
Technical UL/CSA
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (1000 V AC) 275 A |
| Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 60 hp |
| Horsepower Rating UL/CSA | (220 ... 240 V AC) Three Phase 75 hp |
| Horsepower Rating UL/CSA | (440 ... 480 V AC) Three Phase 150 hp |
| Horsepower Rating UL/CSA | (550 ... 600 V AC) Three Phase 200 hp |
| Full Load Amps Motor Use | (200 ... 208 V AC) Three Phase 177 A |
| Full Load Amps Motor Use | (220 ... 240 V AC) Three Phase 192 A |
| Full Load Amps Motor Use | (440 ... 480 V AC) Three Phase 180 A |
| Full Load Amps Motor Use | (550 ... 600 V AC) Three Phase 192 A |
ABB EcoSolutions
| End Of Life Disassembling Instructions | 1SFC100112M0001 |
Why Proax for ABB AF205B-30-22RT-12?
Proax is an authorized distributor of ABB AF205B-30-22RT-12 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Alternate Names | AF205B3022RT12 |
| Pack Size | 1 |
Recommended