AF116B-30-22-14
By ABB
SKU
ABBAF116B302214
MPN
1SFL427063R1422
Weight
1.55 kg
The AF116B-30-22-14 is a 3 pole - 690 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and standard ferrules, controlling motors up to 55 kW / 400 V AC (AC-3) or 75 hp / 480 V UL and switching power circuits up to 160 A (AC-1) or 160 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz ), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Technical Specifications
Dimensions
| Product Net Width | 90 mm |
| Product Net Depth / Length | 126 mm |
| Product Net Height | 150 mm |
| Product Net Weight | 1.55 kg |
Technical
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 2 |
| Number of Auxiliary Contacts NC | 2 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. |
| Rated Operational Voltage | Main Circuit 690 V |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 160 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 60 °C 145 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 70 °C 130 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 116 A |
| Rated Operational Current AC-3 (Ie) | (440 V) 55 °C 116 A |
| Rated Operational Current AC-3 (Ie) | (500 V) 55 °C 110 A |
| Rated Operational Current AC-3 (Ie) | (690 V) 55 °C 65 A |
| Rated Operational Current AC-3 (Ie) | (380 / 400 V) 55 °C 116 A |
| Rated Operational Current AC-3 (Ie) | (220 / 230 / 240 V) 55 °C 116 A |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 116 A |
| Rated Operational Current AC-3e (Ie) | (440 V) 60 °C 116 A |
| Rated Operational Current AC-3e (Ie) | (500 V) 60 °C 110 A |
| Rated Operational Current AC-3e (Ie) | (690 V) 60 °C 65 A |
| Rated Operational Current AC-3e (Ie) | (380 / 400 V) 60 °C 116 A |
| Rated Operational Current AC-3e (Ie) | (220 / 230 / 240 V) 60 °C 116 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 3 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 3 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-1 (Ie) | (110 V) 3 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-1 (Ie) | (175 V) 2 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-1 (Ie) | (175 V) 2 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-1 (Ie) | (175 V) 2 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-1 (Ie) | (220 V) 3 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-1 (Ie) | (220 V) 3 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-1 (Ie) | (220 V) 3 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-1 (Ie) | (260 V) 3 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-1 (Ie) | (260 V) 3 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-1 (Ie) | (260 V) 3 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 1-Pole, 40 °C 160 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 1-Pole, 60 °C 145 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 1-Pole, 70 °C 130 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 2 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 2 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 2 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 3 Poles in Series, 40 °C 160 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 3 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-1 (Ie) | (72 V) 3 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-1 (Ie) | (90 V) 1 Pole, 40 °C 160 A |
| Rated Operational Current DC-1 (Ie) | (90 V) 1 Pole, 60 °C 145 A |
| Rated Operational Current DC-1 (Ie) | (90 V) 1 Pole, 70 °C 130 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 145 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 3 Poles in Series, 40 °C 145 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 3 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-3 (Ie) | (110 V) 3 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-3 (Ie) | (220 V) 3 Poles in Series, 40 °C 145 A |
| Rated Operational Current DC-3 (Ie) | (220 V) 3 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-3 (Ie) | (220 V) 3 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 2 Poles in Series, 40 °C 145 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 2 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 2 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 3 Poles in Series, 40 °C 145 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 3 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-3 (Ie) | (72 V) 3 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 145 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 3 Poles in Series, 40 °C 145 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 3 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-5 (Ie) | (110 V) 3 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-5 (Ie) | (220 V) 3 Poles in Series, 40 °C 145 A |
| Rated Operational Current DC-5 (Ie) | (220 V) 3 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-5 (Ie) | (220 V) 3 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 2 Poles in Series, 40 °C 145 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 2 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 2 Poles in Series, 70 °C 130 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 3 Poles in Series, 40 °C 145 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 3 Poles in Series, 60 °C 145 A |
| Rated Operational Current DC-5 (Ie) | (72 V) 3 Poles in Series, 70 °C 130 A |
| Rated Operational Power AC-3 (Pe) | (415 V) 55 kW |
| Rated Operational Power AC-3 (Pe) | (440 V) 75 kW |
| Rated Operational Power AC-3 (Pe) | (500 V) 75 kW |
| Rated Operational Power AC-3 (Pe) | (690 V) 55 kW |
| Rated Operational Power AC-3 (Pe) | (380 / 400 V) 55 kW |
| Rated Operational Power AC-3 (Pe) | (220 / 230 / 240 V) 30 kW |
| Rated Operational Power AC-3e (Pe) | (415 V) 55 kW |
| Rated Operational Power AC-3e (Pe) | (440 V) 75 kW |
| Rated Operational Power AC-3e (Pe) | (500 V) 75 kW |
| Rated Operational Power AC-3e (Pe) | (690 V) 55 kW |
| Rated Operational Power AC-3e (Pe) | (380 / 400 V) 55 kW |
| Rated Operational Power AC-3e (Pe) | (220 / 230 / 240 V) 30 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie AC-3 |
| Rated Breaking Capacity AC-3e | 8.5 x Ie AC-3e |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Rated Making Capacity AC-3e | 12 x Ie AC-3e |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 160 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 536 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 1300 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 928 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 379 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
| Rated Insulation Voltage (Ui) | acc. to UL/CSA 600 V |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Maximum Electrical Switching Frequency | (AC-3) 300 cycles per hour |
| Mechanical Durability | 5 million |
| Maximum Mechanical Switching Frequency | 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (Uc) | 50 Hz / 60 Hz 250 ... 500 V |
| Rated Control Circuit Voltage (Uc) | DC Operation 250 ... 500 V |
| Coil Consumption | Average Pull-in Value 50 Hz 260 V·A |
| Coil Consumption | Average Pull-in Value 60 Hz 260 V·A |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·A |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·A |
| Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 205 V·A |
| Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 205 V·A |
| Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage DC 230 V·A |
| Coil Consumption | Pull-in at Max. Rated Control Circuit Voltage DC 230 W |
| Power Loss | 6 W |
| Power Loss | at Rated Operating Conditions per Pole 6 W |
| Operate Time | Between Coil Energization and NO Contact Closing 25 ... 55 ms |
| Connecting Capacity Main Circuit | Flexible 2 x 10 ... 70 mm² |
| Connecting Capacity Main Circuit | Rigid Cu-Cable 2 x 10 ... 95 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible 2x0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Solid 2 x 1 ... 4 mm² |
| Connecting Capacity Auxiliary Circuit | Stranded 2 x 1 .... 4 mm² |
| Connecting Capacity | Flexible 2 x 10 ... 70 mm² |
| Connecting Capacity | Rigid Cu-Cable 2 x 10 ... 95 mm² |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40 |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Tightening torque | Cable Lug 9 N·m |
| Tightening torque | Main Circuit 8 N·m |
| Terminal Type | Main Circuit: Bars |
| Product Name | Block Contactor |
Technical UL/CSA
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 160 A |
| Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 30 hp |
| Horsepower Rating UL/CSA | (220 ... 240 V AC) Three Phase 40 hp |
| Horsepower Rating UL/CSA | (440 ... 480 V AC) Three Phase 75 hp |
| Horsepower Rating UL/CSA | (550 ... 600 V AC) Three Phase 100 hp |
| Full Load Amps Motor Use | (200 ... 208 V AC) Three Phase 92 A |
| Full Load Amps Motor Use | (220 ... 240 V AC) Three Phase 104 A |
| Full Load Amps Motor Use | (440 ... 480 V AC) Three Phase 96 A |
| Full Load Amps Motor Use | (550 ... 600 V AC) Three Phase 99 A |
ABB EcoSolutions
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility |
| End Of Life Disassembling Instructions | 1SFC100112M0001 |
| Environmental Product Declaration - EPD | 1SFC100092D0201 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 87.8 % |
| Sustainable Material Content in Product (wt. %) | Recycled Metal - 37 % |
Why Proax for ABB AF116B-30-22-14?
Proax is an authorized distributor of ABB AF116B-30-22-14 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Alternate Names | AF116B302214 |
| Pack Size | 1 |
Recommended