CADEN
Cart

AF116B-30-22-11

Official Distributor

By ABB

SKU
ABBAF116B302211
MPN
1SFL427063R1122
Weight
1.55 kg
The AF116B-30-22-11 is a 3 pole - 690 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and standard ferrules, controlling motors up to 55 kW / 400 V AC (AC-3) or 75 hp / 480 V UL and switching power circuits up to 160 A (AC-1) or 160 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Technical Specifications

Dimensions

Product Net Width90 mm
Product Net Depth / Length126 mm
Product Net Height150 mm
Product Net Weight1.55 kg

Technical

Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO2
Number of Auxiliary Contacts NC2
Number of Poles3P
StandardsIEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational VoltageMain Circuit 690 V
Rated Frequency (f)Main Circuit 50 / 60 Hz
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 160 A
Rated Operational Current AC-1 (Ie)(690 V) 60 °C 145 A
Rated Operational Current AC-1 (Ie)(690 V) 70 °C 130 A
Rated Operational Current AC-3 (Ie)(415 V) 55 °C 116 A
Rated Operational Current AC-3 (Ie)(440 V) 55 °C 116 A
Rated Operational Current AC-3 (Ie)(500 V) 55 °C 110 A
Rated Operational Current AC-3 (Ie)(690 V) 55 °C 65 A
Rated Operational Current AC-3 (Ie)(380 / 400 V) 55 °C 116 A
Rated Operational Current AC-3 (Ie)(220 / 230 / 240 V) 55 °C 116 A
Rated Operational Current AC-3e (Ie)(415 V) 60 °C 116 A
Rated Operational Current AC-3e (Ie)(440 V) 60 °C 116 A
Rated Operational Current AC-3e (Ie)(500 V) 60 °C 110 A
Rated Operational Current AC-3e (Ie)(690 V) 60 °C 65 A
Rated Operational Current AC-3e (Ie)(380 / 400 V) 60 °C 116 A
Rated Operational Current AC-3e (Ie)(220 / 230 / 240 V) 60 °C 116 A
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 40 °C 160 A
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 60 °C 145 A
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 70 °C 130 A
Rated Operational Current DC-1 (Ie)(110 V) 3 Poles in Series, 40 °C 160 A
Rated Operational Current DC-1 (Ie)(110 V) 3 Poles in Series, 60 °C 145 A
Rated Operational Current DC-1 (Ie)(110 V) 3 Poles in Series, 70 °C 130 A
Rated Operational Current DC-1 (Ie)(175 V) 2 Poles in Series, 40 °C 160 A
Rated Operational Current DC-1 (Ie)(175 V) 2 Poles in Series, 60 °C 145 A
Rated Operational Current DC-1 (Ie)(175 V) 2 Poles in Series, 70 °C 130 A
Rated Operational Current DC-1 (Ie)(220 V) 3 Poles in Series, 40 °C 160 A
Rated Operational Current DC-1 (Ie)(220 V) 3 Poles in Series, 60 °C 145 A
Rated Operational Current DC-1 (Ie)(220 V) 3 Poles in Series, 70 °C 130 A
Rated Operational Current DC-1 (Ie)(260 V) 3 Poles in Series, 40 °C 160 A
Rated Operational Current DC-1 (Ie)(260 V) 3 Poles in Series, 60 °C 145 A
Rated Operational Current DC-1 (Ie)(260 V) 3 Poles in Series, 70 °C 130 A
Rated Operational Current DC-1 (Ie)(72 V) 1-Pole, 40 °C 160 A
Rated Operational Current DC-1 (Ie)(72 V) 1-Pole, 60 °C 145 A
Rated Operational Current DC-1 (Ie)(72 V) 1-Pole, 70 °C 130 A
Rated Operational Current DC-1 (Ie)(72 V) 2 Poles in Series, 40 °C 160 A
Rated Operational Current DC-1 (Ie)(72 V) 2 Poles in Series, 60 °C 145 A
Rated Operational Current DC-1 (Ie)(72 V) 2 Poles in Series, 70 °C 130 A
Rated Operational Current DC-1 (Ie)(72 V) 3 Poles in Series, 40 °C 160 A
Rated Operational Current DC-1 (Ie)(72 V) 3 Poles in Series, 60 °C 145 A
Rated Operational Current DC-1 (Ie)(72 V) 3 Poles in Series, 70 °C 130 A
Rated Operational Current DC-1 (Ie)(90 V) 1 Pole, 40 °C 160 A
Rated Operational Current DC-1 (Ie)(90 V) 1 Pole, 60 °C 145 A
Rated Operational Current DC-1 (Ie)(90 V) 1 Pole, 70 °C 130 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 40 °C 145 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 60 °C 145 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 70 °C 130 A
Rated Operational Current DC-3 (Ie)(110 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-3 (Ie)(110 V) 3 Poles in Series, 60 °C 145 A
Rated Operational Current DC-3 (Ie)(110 V) 3 Poles in Series, 70 °C 130 A
Rated Operational Current DC-3 (Ie)(220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-3 (Ie)(220 V) 3 Poles in Series, 60 °C 145 A
Rated Operational Current DC-3 (Ie)(220 V) 3 Poles in Series, 70 °C 130 A
Rated Operational Current DC-3 (Ie)(72 V) 2 Poles in Series, 40 °C 145 A
Rated Operational Current DC-3 (Ie)(72 V) 2 Poles in Series, 60 °C 145 A
Rated Operational Current DC-3 (Ie)(72 V) 2 Poles in Series, 70 °C 130 A
Rated Operational Current DC-3 (Ie)(72 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-3 (Ie)(72 V) 3 Poles in Series, 60 °C 145 A
Rated Operational Current DC-3 (Ie)(72 V) 3 Poles in Series, 70 °C 130 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 40 °C 145 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 60 °C 145 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 70 °C 130 A
Rated Operational Current DC-5 (Ie)(110 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-5 (Ie)(110 V) 3 Poles in Series, 60 °C 145 A
Rated Operational Current DC-5 (Ie)(110 V) 3 Poles in Series, 70 °C 130 A
Rated Operational Current DC-5 (Ie)(220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-5 (Ie)(220 V) 3 Poles in Series, 60 °C 145 A
Rated Operational Current DC-5 (Ie)(220 V) 3 Poles in Series, 70 °C 130 A
Rated Operational Current DC-5 (Ie)(72 V) 2 Poles in Series, 40 °C 145 A
Rated Operational Current DC-5 (Ie)(72 V) 2 Poles in Series, 60 °C 145 A
Rated Operational Current DC-5 (Ie)(72 V) 2 Poles in Series, 70 °C 130 A
Rated Operational Current DC-5 (Ie)(72 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-5 (Ie)(72 V) 3 Poles in Series, 60 °C 145 A
Rated Operational Current DC-5 (Ie)(72 V) 3 Poles in Series, 70 °C 130 A
Rated Operational Power AC-3 (Pe)(415 V) 55 kW
Rated Operational Power AC-3 (Pe)(440 V) 75 kW
Rated Operational Power AC-3 (Pe)(500 V) 75 kW
Rated Operational Power AC-3 (Pe)(690 V) 55 kW
Rated Operational Power AC-3 (Pe)(380 / 400 V) 55 kW
Rated Operational Power AC-3 (Pe)(220 / 230 / 240 V) 30 kW
Rated Operational Power AC-3e (Pe)(415 V) 55 kW
Rated Operational Power AC-3e (Pe)(440 V) 75 kW
Rated Operational Power AC-3e (Pe)(500 V) 75 kW
Rated Operational Power AC-3e (Pe)(690 V) 55 kW
Rated Operational Power AC-3e (Pe)(380 / 400 V) 55 kW
Rated Operational Power AC-3e (Pe)(220 / 230 / 240 V) 30 kW
Rated Breaking Capacity AC-38 x Ie AC-3
Rated Breaking Capacity AC-3e8.5 x Ie AC-3e
Rated Making Capacity AC-310 x Ie AC-3
Rated Making Capacity AC-3e12 x Ie AC-3e
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 160 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 536 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 1300 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 928 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 379 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Insulation Voltage (Ui)acc. to UL/CSA 600 V
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Maximum Electrical Switching Frequency(AC-3) 300 cycles per hour
Mechanical Durability5 million
Maximum Mechanical Switching Frequency300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)50 Hz / 60 Hz 24 ... 60 V
Rated Control Circuit Voltage (Uc)DC Operation 20 ... 60 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 5.5 V·A
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 60 Hz 5.5 V·A
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage 50 Hz 225 V·A
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage 60 Hz 225 V·A
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage DC 210 V·A
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage DC 210 W
Power Loss6 W
Power Lossat Rated Operating Conditions per Pole 6 W
Operate TimeBetween Coil Energization and NO Contact Closing 25 ... 55 ms
Connecting Capacity Main CircuitFlexible 2 x 10 ... 70 mm²
Connecting Capacity Main CircuitRigid Cu-Cable 2 x 10 ... 95 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible 2x0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitSolid 2 x 1 ... 4 mm²
Connecting Capacity Auxiliary CircuitStranded 2 x 1 .... 4 mm²
Connecting CapacityFlexible 2 x 10 ... 70 mm²
Connecting CapacityRigid Cu-Cable 2 x 10 ... 95 mm²
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Tightening torqueCable Lug 9 N·m
Tightening torqueMain Circuit 8 N·m
Terminal TypeMain Circuit: Bars
Product NameBlock Contactor

Technical UL/CSA

Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 160 A
Horsepower Rating UL/CSA(200 ... 208 V AC) Three Phase 30 hp
Horsepower Rating UL/CSA(220 ... 240 V AC) Three Phase 40 hp
Horsepower Rating UL/CSA(440 ... 480 V AC) Three Phase 75 hp
Horsepower Rating UL/CSA(550 ... 600 V AC) Three Phase 100 hp
Full Load Amps Motor Use(200 ... 208 V AC) Three Phase 92 A
Full Load Amps Motor Use(220 ... 240 V AC) Three Phase 104 A
Full Load Amps Motor Use(440 ... 480 V AC) Three Phase 96 A
Full Load Amps Motor Use(550 ... 600 V AC) Three Phase 99 A

ABB EcoSolutions

ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNon-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions1SFC100112M0001
Environmental Product Declaration - EPD1SFC100092D0201
Improved Energy Efficiency for CustomersProduct Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 87.8 %
Sustainable Material Content in Product (wt. %)Recycled Metal - 37 %

Why Proax for ABB AF116B-30-22-11?

Proax is an authorized distributor of ABB AF116B-30-22-11 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate NamesAF116B302211
Pack Size1
Recommended

CAD$1,106.73

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability