By ABB
SKU
MPN
1SDA054445R1
Weight
4.762 kg
C.BREAKER TMAX T5H 400 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 400 I3=2000...4000 A
Technical Specifications
Dimensions
Product Net Width | 140 mm |
Product Net Height | 205 mm |
Product Net Depth / Length | 103.5 mm |
Product Net Weight | 4.8 kg |
Additional Information
Electrical Durability | 7000 cycle |
Electrical Durability | 60 cycles per hour |
Mechanical Durability | 20000 cycle |
Mechanical Durability | 120 cycles per hour |
Number of Poles | 3 |
Power Loss | at Rated Operating Conditions per Pole 19.5 W |
Product Main Type | SACE Tmax T |
Product type | Automatic Circuit Breaker |
Rated Current (In) | 400 A |
Rated Impulse Withstand Voltage (Uimp) | 8 kV |
Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Voltage | 690 V AC |
Rated Operational Voltage | 750 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 100 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (380 V AC) 70 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (400 V AC) 70 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (415 V AC) 70 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (440 V AC) 65 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (500 V AC) 50 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (690 V AC) 40 kA |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 5 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 100 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (380 V AC) 70 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 70 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (415 V AC) 70 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (440 V AC) 65 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (500 V AC) 50 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (690 V AC) 40 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (250 V DC) 2 Poles in Series 70 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (500 V DC) 2 Poles in Series 50 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (750 V DC) 3 Poles in Series 36 kA |
Rated Uninterrupted Current (Iu) | 400 A |
Release | TMA |
Release Type | TM |
Short-Circuit Performance Level | H |
Standards | IEC |
Sub-type | T5 |
Suitable for | T5 |
Suitable for Product Class | Moulded Case Circuit Breakers |
Terminal Connection Type | Fixed Circuit-Breakers |
Terminal Connection Type | Front |
Test Voltage Max (Utest) | 3500 V |
Test Voltage at Industrial Frequency for 1 Minute | 3500 V |
Version | F |
Why Proax for ABB T5H 400 TMA 400-4000 3p F F?
Proax is an authorized distributor of ABB T5H 400 TMA 400-4000 3p F F and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | T5H400TMA40040003pFF |
Pack Size | 1 |
Recommended