SFP 1-20/120AC/EX - EMC filter surge protection device
Device protection, according to type 3/class III, with mains interference filter to prevent high-frequency interference voltages, for 1-phase power supply networks with separate N and PE (3-conductor system: L1, N, PE), with remote indication contact. Can be used in potentially explosive areas in zone 2.
Technical Specifications
Product properties
Product family | SFP |
Type | DIN rail module, one-piece |
Number of Positions | 2 |
For country-specific use in | USA, CN, BR |
Surge protection fault message | Optical, remote indicator contact |
IEC test classification | III |
IEC test classification | T3 |
EN type | T3 |
Indicator/remote signaling
Connection name | Remote fault indicator contact |
Switching function | Changeover contact |
Maximum operating voltage Umax. AC | 250 V AC |
Max. operating current Imax | 1 A (250 V AC) |
Max. operating current Imax | 0.25 A (250 V DC) |
Max. operating current Imax | 1 A (48 V DC) |
Switching capacity max. perm. | 0.25 A/250 V DC |
Switching capacity max. perm. | 1 A / 48 V AC |
Min. permissible switching capacity | 1 A/48 V DC |
Min. permissible switching capacity | 100 mA / 12 V AC |
Input/output
Connection Method | Screw terminal blocks |
Screw thread | M3 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Tightening torque | 5 lbf-in. ... 7 lbf-in. |
Conductor cross section flexible min. | 2.5 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section, rigid min. | 2.5 mm² |
Conductor cross section, rigid max. | 6 mm² |
Dimensions
Width | 112 mm |
Height | 93 mm |
Depth | 79 mm |
Material specifications
Flammability rating according to UL 94 | V-0 |
Insulating material | ABS |
Housing Material | Aluminum |
Mechanical data
Open side panel | No |
Protective circuit
Direction of action | L-N & L(N)-PE |
Nominal frequency fN | 50 Hz |
Nominal frequency fN | 60 Hz |
Maximum continuous operating voltage UC (L-N) | 150 V AC |
Maximum continuous operating voltage UC (L-PE) | 150 V AC |
Rated load current IL | 20 A (40 °C) |
Residual current IPE | ≤ 0.5 mA |
Operating effective current IC at UC | ≤ 10 mA |
Nominal discharge current In (8/20) µs (L-N) | 3 kA |
Nominal discharge current In (8/20) µs (L-PE) | 3 kA |
Maximum discharge current Imax (8/20) µs (L-N) | 10 kA |
Maximum discharge current Imax (8/20) µs (L-PE) | 10 kA |
Energy absorption symmetrical | 170 J |
Enery absorption, asymmetrical | 2x 170 J |
Voltage protection level Up (L-N) | ≤ 450 V (at 6 kV/3 kA) |
Voltage protection level Up (L-PE) | ≤ 450 V (at 6 kV/3 kA) |
Voltage protection level Up (N-PE) | ≤ 450 V (at 6 kV/3 kA) |
Residual voltage at In | ≤ 450 V |
Residual voltage at In | ≤ 450 V |
Residual voltage at In | ≤ 450 V |
Response time tA (L-N) | ≤ 25 ns |
Response time tA (L-PE) | ≤ 25 ns |
Response time tA (N-PE) | ≤ 25 ns |
Inductivity in series | 2x 1 mH ±30 % (with current compensation) |
Capacity (L-N) | 2 µF ±10 % (X2, FOW X2-250V) |
Capacity (L-PE) | 2.2 nF ±20 % (Y, FOW X2-250V) |
Capacity (N-PE) | 2.2 nF ±20 % (Y, FOW X2-250V) |
Max. required back-up fuse | 20 A (gL/gG) |
Max. required back-up fuse | 20 A (MCB, > 125 V, AIC: 14 kA) |
Input attenuation aE, sym. | typ. 40 dB (≥ 500 kHz / 50 Ω) |
Input attenuation aE, asym. | typ. 30 dB (≥ 1 MHz / 50 Ω) |
Filter data
Clamping voltage ringwave (L-N) | 100 V (category A 100 kHz 6 kV/200 A) |
Clamping voltage ringwave (L-N) | 195 V (category B 100 kHz 6 kV/500 A) |
Clamping voltage ringwave (L-PE) | 390 V (category A 100 kHz 6 kV/200 A) |
Clamping voltage ringwave (L-PE) | 390 V (category B 100 kHz 6 kV/500 A) |
Discharge resistance | ≤ 390 kΩ |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 40 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Air clearances and creepage distances
Standards/regulations | DIN VDE 0110-1 / IEC 60664-1 / IEC 61643-1 |
Standards
Standards/regulations | IEC 61643-1 |
Standards/regulations | EN 61643-11/A11 |
Standards/regulations | UL 1449 |
Standards/regulations | UL 1283 |
Standards/regulations | IEC 61643-1 |
Standards/regulations | EN 61643-11/A11 |
Standards/specifications | IEC 61643-1 |
Note | 2005 |
Standards/specifications | DIN EN 61643-11/A11 |
Note | 2007 |
Standards/specifications | UL 1449 |
Note | ed. 3: 2006 T4 for type 2 |
Standards/specifications | UL 1283 |
Note | ed. 5: 2005 |
Mounting
Mounting Type | DIN rail: 35 mm |
Why Proax for Phoenix Contact 2905220?
Proax is an authorized distributor of Phoenix Contact 2905220 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended