The circuit breaker for transformer protection MS132-10T is a compact 45 mm width device designed to protect control transformers on the primary side. This device has a rated operational current of Ie = 10 A. It allows fuse-less protection against overload and short-circuit. The short-circuit current setting is fixed to 20 times the rated operational current to handle the high inrush current generated by transformers. The device allows manually connect and disconnect the transformer from the mains thanks of its built-in disconnection function. The circuit breaker for transformer protection offers a rated service short-circuit breaking capacity of Ics = 100 kA at 400 VAC and a trip class 10. Further features are temperature compensation, trip-free mechanism, rotary handle with a clear switch position indication and short circuit trip indicator. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips, power in-feed blocks and terminal spacers are available as accessory.
Technical Specifications
Dimensions
Product Net Width | 45 mm |
Product Net Height | 97.8 mm |
Product Net Depth / Length | 86.05 mm |
Product Net Weight | 0.265 kg |
Technical
Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 100 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (400 V AC) 100 kA |
Rated Service Short-Circuit Breaking Capacity (Ics) | (440 V AC) 30 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 100 kA |
Rated Instantaneous Short-Circuit Current Setting (Ii) | 200 A |
Setting range | 6.3 ... 10 A |
Rated Operational Voltage | Main Circuit 690 V AC |
Rated Operational Current (Ie) | 10 A |
Rated Frequency (f) | Main Circuit 50 Hz |
Rated Frequency (f) | Main Circuit 60 Hz |
Operating Frequency (fsw) | 0 ... 400 Hz |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 6 kV |
Rated Insulation Voltage (Ui) | 690 V |
Power Loss | at Rated Operating Conditions per Pole 0.7 ... 1.7 W |
Number of Poles | 3 |
Conventional Free-air Thermal Current (Ith) | Main Circuit 10 A |
Degree of Protection | Housing IP20 |
Degree of Protection | Main Circuit Terminals IP10 |
Pollution degree | 3 |
Electrical Durability | 50000 cycle |
Mechanical Durability | 100000 cycle |
Terminal Type | Screw Terminals |
Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
Connecting Capacity Main Circuit | Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm² |
Connecting Capacity Main Circuit | Flexible 1/2x 0.75 ... 2.5 mm² |
Connecting Capacity Main Circuit | Rigid 1/2x 1 ... 4 mm² |
Tightening torque | Main Circuit 0.8 ... 1.2 N·m |
Wire Stripping Length | Main Circuit 9 mm |
Recommended Screw Driver | M3.5 |
Recommended Screw Driver | Pozidriv 2 |
Mounting Position | 1 ... 6 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Minimum Mounting Distance | Electrical Conductive Board, Vertical 75 mm |
Minimum Mounting Distance | Other Device Same Type, Horizontal 9 mm |
Minimum Mounting Distance | Other Device Same Type, Vertical 150 mm |
Actuator Type | Rotary Handle |
Contact Position Indication | ON / OFF / TRIP |
Standards | IEC/EN 60947-1 |
Standards | IEC/EN 60947-2 |
Standards | IEC/EN 60947-4-1 |
Technical UL/CSA
Short-circuit current rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA |
Short-circuit current rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA |
Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
Horsepower Rating UL/CSA | (120 V AC) Single Phase 0.5 Hp |
Horsepower Rating UL/CSA | (220 ... 240 V AC) Single Phase 1.5 Hp |
Full Load Amps Motor Use | (120 V AC) Single Phase 9.8 A |
Full Load Amps Motor Use | (220 ... 240 V AC) Single Phase 10 A |
Locked Rotor Amps | (120 V AC) Single Phase 58.8 A |
Locked Rotor Amps | (220 ... 240 V AC) Single Phase 58.8 A |
Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 16-12 AWG |
Connecting Capacity Main Circuit UL/CSA | Stranded 1/2x 16-12 AWG |
Tightening Torque UL/CSA | Main Circuit 10 ... 12 in·lb |
Why Proax for ABB MS132-10T?
Proax is an authorized distributor of ABB MS132-10T and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | MS13210T |
Pack Size | 1 |