2906921
SKU
PHX2906921
MPN
PLC-APT-UI-OUT
Weight
0.072 kg
PLC-APT-UI-OUT - Analog module
Analog output module for PLC logic logic modules (Generation 2 only), single-channel, signal type (4 mA ... 20 mA, 0 mA ... 20 mA, 0 V ... 10 V, 2 V ... 10 V) can be configured via DIP switch, Push-in connection
Technical Specifications
Notes
| Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Product properties
| Product family | PLC logic |
| Operating mode | 100% operating factor |
Insulation characteristics
| Insulation | Basic insulation |
Insulation characteristics: Air clearances and creepage distances
| Insulation | Basic insulation |
| Overvoltage category | III |
| Pollution degree | 2 |
Air clearances and creepage distances
| Rated Insulation Voltage | 50 V |
| Rated surge voltage | 0.5 kV |
Supply
| Rated control circuit supply voltage US | 24 V DC |
| Rated control supply voltage range with reference to US | 0.8 ... 1.1 |
| Rated control supply current IS | ≤ 28 mA |
| Protective circuit | Reverse polarity protection |
| Protective circuit | Surge protection |
Digital input
| Rated actuating voltage UC | 24 V DC |
| Rated actuating current IC | ≤ 1 mA |
Analog
| Output name | Analog voltage output |
| Number of Outputs | 1 |
| Voltage output signal | 0 V ... 10 V |
| Voltage output signal | 2 V ... 10 V |
| Maximum output voltage | 12.3 V |
| Ripple | < 20 mVPP |
| Load/output load voltage output | 10 kΩ |
| Surge voltage protection | > 33 V |
| Maximum transmission error | 1 % |
| Resolution | 10 bit (scaled to 0 to 1000) |
| Protective circuit | Surge protection |
| Output name | Analog output for current |
| Number of Outputs | 1 |
| Current Output Signal | 0 mA ... 20 mA |
| Current Output Signal | 4 mA ... 20 mA |
| Maximum output current | 24.6 mA |
| Load/Output Load Current Output | 500 Ω (20 mA) |
| Surge voltage protection | > 33 V |
| Maximum transmission error | 1 % |
| Resolution | 10 bit |
| Protective circuit | Surge protection |
Connection data
| Connection Method | Push-in connection |
| Stripping length | 10 mm |
| Number of Connections | 4 |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
Signaling
| Operating voltage display | Green LED |
| Error indication | Red LED |
Dimensions
| Width | 6.2 mm |
| Height | 80 mm |
| Depth | 95 mm |
Material specifications
| Color | gray (RAL 7042) |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -20 °C ... 50 °C |
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
CE
| Certificate | CE-compliant |
UL, USA/Canada
| Identification | UL 508 Listed |
Air clearances and creepage distances
| Standards/regulations | DIN EN 50178 |
Mounting
| Mounting Type | DIN rail mounting |
| Assembly instructions | in rows with zero spacing |
| Mounting Position | any |
Why Proax for Phoenix Contact 2906921?
Proax is an authorized distributor of Phoenix Contact 2906921 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |