2903918
SKU
PHX2903918
MPN
ELR H3-IES-PT- 24DC/500AC-9
Weight
0.287 kg
This product is Not Cancellable/Not Returnable
Series ELR-H
ELR H3-IES-PT- 24DC/500AC-9 - Hybrid motor starter
Hybrid motor starter for starting 3~ AC motors up to 500 V AC and 9 A output current, with 24 V DC control voltage, adjustable overload shutdown, emergency stop function to SIL 3/PL e, and push-in connection.
- 22.5 mm wide
- Safety level in accordance with IEC 61508-1: SIL 3, ISO 13849: PL e
- Reduction in wiring
- Space saving
- Long service life
- 3-phase loop bridges
- Adjustable current for bimetal function
- Low-wear switching
Technical Specifications
Notes
| Notes on operation | If this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to the power distribution board. |
Product properties
| Product family | CONTACTRON |
| Operating mode | 100% operating factor |
Electrical properties
| Number of phases | 3 |
| Motor starter type | Direct starter |
| Maximum power dissipation for nominal condition | 13.5 W |
| Switching frequency | ≤ 2 Hz (Load-dependent) |
| Maximum power dissipation | 14.6 W |
| Minimum power dissipation | 1.1 W |
| Coordination type | 1 |
Supply
| Rated control circuit supply voltage US | 24 V DC |
| Control supply voltage range | 19.2 V DC ... 30 V DC |
| Rated control supply current IS | 40 mA |
| Protective circuit | Surge protection |
| Protective circuit | Reverse polarity protection |
Insulation characteristics
| Rated Insulation Voltage | 500 V |
| Rated surge voltage | 6 kV |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit | Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC |
| Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit | Basic insulation (IEC 60947-1) at operating voltage 300 V AC ... 500 V AC |
| Isolation characteristics between the control input and control supply voltage to auxiliary circuit | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC |
Emergency tripping
| Operate threshold | > 45 A |
| Response time | 2 s |
Control
| Input name | Control input |
| Rated actuating voltage UC | 24 V DC |
| Triggering voltage range | 19.2 V DC ... 30 V DC |
| Rated actuating current IC | 5 mA (Input type 1) |
| Switching threshold | 9.6 V (“0” signal) |
| Switching threshold | 19.2 V (“1” signal) |
| Switching level | < 5 V DC (For EMERGENCY STOP) |
| Typical turn-off time | < 30 ms |
| Protective circuit | Reverse polarity protection |
AC output
| Rated operating voltage Ue | 500 V AC |
| Operating voltage range | 42 V AC ... 550 V AC |
| Rated operating current Ie | 9 A (AC-51) |
| Rated operating current Ie | 6.5 A (AC-53a) |
| Mains frequency | 50/60 Hz |
| Load current range | 1.5 A ... 9 A (see to derating) |
| Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
| Cooling time | 20 min. (for auto reset) |
| Leakage current | 0 mA |
| Protective circuit | Surge protection |
Acknowledge output
| Note | Confirmation: floating change-over contact, signal contact |
| Contact switching type | 1 changeover contact |
| Switching capacity in accordance with IEC 60947-5-1 | 3 A (230 V, AC15) |
| Switching capacity in accordance with IEC 60947-5-1 | 2 A (24 V, DC13) |
Control circuits
| Connection Method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
Load circuit
| Connection Method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
Signaling
| Status display | Yellow LED |
| Operating voltage display | Green LED |
| Error indication | Red LED |
Dimensions
| Width | 22.5 mm |
| Height | 107.5 mm |
| Depth | 114 mm |
Material specifications
| Flammability rating according to UL 94 | V0 (Housing) |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -25 °C ... 70 °C (observe derating) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m |
UKCA
| Certificate | UKCA-compliant |
ATEX
| Identification | II (2) G [Ex e] [Ex d] [Ex px] |
| Identification | II (2) D [Ex t] [Ex p] |
| Certificate | PTB 07 ATEX 3145 |
UL approval
| Certificate | NLDX.E228652 |
Safety Integrity Level (SIL, IEC 61508)
| Identification | ≤ 3 |
| Note | Safe shutdown |
| Identification | 2 |
| Note | Motor protection |
Performance Level (ISO 13849)
| Identification | ≤ e |
| Note | Safe shutdown |
Category (ISO 13849)
| Identification | ≤ 3 |
| Note | Safe shutdown |
UL data
| SCCR | 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault))) |
| SCCR | 5 kA (500 V AC (fuse: 20 A RK5 (standard fault))) |
| FLA | 6.5 A (500 V AC) |
| Group installation | 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded) |
| Group installation | 30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded) |
| Category code | NLDX |
Standards/regulations
| Standards/regulations | IEC 60947-1 |
| Standards/regulations | IEC 60947-4-2 |
| Standards/regulations | IEC 61508 |
| Standards/regulations | ISO 13849 |
Mounting
| Mounting Type | DIN rail mounting |
| Assembly instructions | alignable, for spacing see derating |
| Mounting Position | vertical (horizontal DIN rail, motor output below) |
Accessories
Why Proax for Phoenix Contact 2903918?
Proax is an authorized distributor of Phoenix Contact 2903918 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended