Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
ELR H3-IES-PT/500AC-9-IOL
Weight
0.299 kg
This product is Not Cancellable/Not Returnable
Series ELR-H

ELR H3-IES-PT/500AC-9-IOL - Hybrid motor starter

Networkable hybrid motor starter for starting 3~ AC motors up to 500 V AC and 9 A output current, with adjustable overload shutdown, emergency stop function up to SIL 3/PL e, and Push-in connection. Connection to IO-Link.

Technical Specifications

Notes

Notes on operationIf this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to the power distribution board.

Product properties

Product familyCONTACTRON
Operating mode100% operating factor

Electrical properties

Number of phases3
Motor starter typeDirect starter
Switching frequency≤ 2 Hz (Load-dependent)
Maximum power dissipation7 W
Minimum power dissipation0.88 W
Coordination type1

Supply

Rated control circuit supply voltage US24 V DC
Control supply voltage range19.2 V DC ... 30 V DC
Rated control supply current IS65 mA
Protective circuitSurge protection
Protective circuitReverse polarity protection; Parallel polarity protection diode

Supply: IO-Link

Nominal voltage for I/O supply24 V DC (This supply voltage is provided via the IO-Link interface of the IO-Link master.)
Current consumptiontyp. 65 mA ±15 % (24 V DC)
Current consumptionmax. 150 mA
Protective circuitReverse polarity protection
Protective circuitShort-circuit protection
Protective circuitOverload protection

Insulation characteristics

Rated Insulation Voltage550 V
Rated surge voltage6 kV
Overvoltage categoryIII
Degree of pollution2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuitSafe isolation (IEC 60947-1)
Isolation characteristics between the control input and control supply voltage to auxiliary circuitSafe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Isolation characteristics between the control input and control supply voltage to auxiliary circuitSafe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC

Emergency tripping

Operate threshold> 60 A
Response time< 0.5 s

Control

Input nameEnable input
Rated actuating voltage UC24 V DC
Triggering voltage range19.2 V DC ... 30 V DC
Rated actuating current IC7 mA
Switching threshold9.6 V (“0” signal)
Switching threshold19.2 V (“1” signal)
Switching level< 5 V DC (For EMERGENCY STOP)
Typical turn-off time< 30 ms

IO-Link

Number of Ports1
Connection MethodCOMBICON
Connection technology3-conductor
SpecificationV1.1.1
Reverse polarity protectionyes
Cycle Time30 ms
Amount of Process Data8 Byte (Input data)
Amount of Process Data2 Byte (Output data)

AC output

Rated operating voltage Ue500 V AC
Operating voltage range42 V AC ... 550 V AC
Rated operating current Ie9 A (AC-51)
Rated operating current Ie7 A (AC-53a)
Mains frequency50/60 Hz
Load current range1.5 A ... 9 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2Class 10A
Cooling time20 min. (for auto reset)
Leakage current0 mA
Protective circuitSurge protection; Varistor

Control circuits

Connection MethodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14

Load circuit

Connection MethodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14

Signaling

Status displayYellow LED
Operating voltage displayGreen LED
Error indicationRed LED

Dimensions

Width22.5 mm
Height127 mm
Depth114 mm

Material specifications

Flammability rating according to UL 94V0 (Housing)

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-5 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m

UKCA

CertificateUKCA-compliant

UL approval

CertificateNLDX.E228652
CertificateNRNT.E172140

Safety Integrity Level (SIL, IEC 61508)

Identification≤ 3
NoteSafe shutdown

Performance Level (ISO 13849)

Identificatione
NoteSafe shutdown

Category (ISO 13849)

Identification≤ 3
NoteSafe shutdown

UL data

SCCR100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
SCCR5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA7.6 A (480 V AC)
Group installation20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
Group installation30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded)
Category codeNLDX / NRNT
Horsepower ratings2 hp (208 V AC)
Horsepower ratings2 hp (230 V AC)
Horsepower ratings2 hp (240 V AC)
Horsepower ratings5 hp (480 V AC)

Standards/regulations

Standards/regulationsIEC 60947-1
Standards/regulationsEN 60947-4-2
Standards/regulationsIEC 61508
Standards/regulationsISO 13849

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsalignable, for spacing see derating
Mounting Positionvertical (horizontal DIN rail, motor output below)
Accessories

Why Proax for Phoenix Contact 2908672?

Proax is an authorized distributor of Phoenix Contact 2908672 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability