Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
UNO-PS/1AC/24DC/240W
Weight
0.888 kg
Series UNO-PS

UNO-PS/1AC/24DC/240W - Power supply unit

Please use the following item in new systems: 1096432.Primary-switched UNO power supply for DIN rail mounting, input: 1-phase, output: 24 V DC / 240 W

  • Flexible mounting by simply snapping onto the DIN rail
  • More space in the control cabinet with up to 20 % higher power density
  • Maximum energy efficiency, thanks to over 90 % efficiency and extremely low idling losses under 0.3 W
  • Outdoor installation, thanks to the wide temperature range from -25°C to +70°C
Technical Specifications

AC operation

Nominal input voltage range100 V AC ... 240 V AC
Input voltage range85 V AC ... 264 V AC (< 95 V AC Derating 1 %/V)
Derating< 95 V AC (1 %/V)
Input Voltage Range AC85 V AC ... 264 V AC
Voltage type of supply voltageAC
Inrush Current< 80 A (typ.)
Inrush current integral (I2t)< 2 A2s (typ.)
AC frequency range50 Hz ... 60 Hz
Frequency range (fN)50 Hz ... 60 Hz ±10 %
Mains buffering time> 10 ms (120 V AC)
Mains buffering time> 10 ms (230 V AC)
Current consumptiontyp. 2.69 A (100 V AC)
Current consumptiontyp. 1.08 A (240 V AC)
Nominal Power Consumption260 VA
Protective circuitTransient surge protection; Varistor
Power factor (cos phi)0.99
Typical response time< 1 s
Input fuse5 A (slow-blow, internal)
Recommended breaker for input protection6 A ... 16 A (Characteristics B, C, D, K)

Output data

Efficiencytyp. 90 % (120 V AC)
Efficiencytyp. 93 % (230 V AC)
Output characteristicU/I
Nominal Output Voltage24 V DC
Setting range of the output voltage (USet)24 V DC ... 28 V DC ±1 %
Nominal output current (IN)10 A (-25 °C ... 55 °C)
Derating55 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance< 35 V DC
Protection against overvoltage at the output (OVP)≤ 35 V DC
Control deviationchange in load, static 10 % ... 90 %
Control deviation< 2 % (change in load, dynamic 10 % ... 90 %)
Control deviation< 0.1 % (change in input voltage ±10 %)
Residual ripple< 50 mVPP (with nominal values)
Short-circuit-proofyes
Output Power240 W
Maximum no-load power dissipation< 1.1 W
Power loss nominal load max.< 18.8 W
Rise time< 0.5 s (UOUT (10 % ... 90 %))
Response time< 2 ms
Connection in parallelyes, for redundancy and increased capacity
Connection in seriesNo

Input

Connection MethodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length8 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Output

Connection MethodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length8 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Signaling

Types of signalingLED

Electrical properties

Number of phases1.00
Insulation voltage input/output4 kV AC (type test)
Insulation voltage input/output3 kV AC (routine test)

Product properties

Product familyUNO POWER
MTBF (IEC 61709, SN 29500)> 641000 h (40 °C)

Insulation characteristics

Protection classI (in closed control cabinet)
Degree of pollution2

Dimensions

Width45 mm
Height130 mm
Depth125 mm

Installation dimensions

Installation distance right/left0 mm / 0 mm
Installation distance top/bottom30 mm / 30 mm

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsalignable: 0 mm horizontally, 30 mm vertically
Mounting Positionhorizontal DIN rail NS 35, EN 60715

Material specifications

Flammability rating according to UL 94 (housing / terminal blocks)V0
Housing MaterialAluminum / polycarbonate
Type of housingAluminum/polycarbonate

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (start-up type tested)-25 °C
Climatic class3K22 (in accordance with EN 60721-3-3)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (Operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (Operation)15 Hz ... 150 Hz, 2.3g, 90 min.

Standards and Regulations

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Standard - Electrical safetyIEC 62368-1 (SELV)
Standard – Safety extra-low voltageIEC 62368-1 (SELV) und EN 60204-1 (PELV)
Standard - Safe isolationDIN VDE 0100-410
Standard - Safety of transformersEN 61558-2-16
Approval - requirement of the semiconductor industry with regard to mains voltage dipsEN 61000-4-11

Approvals

CSACAN/CSA-C22.2 No. 60950-1-07
CSACSA-C22.2 No. 107.1-01
CSACAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
UL approvalsUL/C-UL listed UL 508
UL approvalsUL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
UL approvalsUL/C-UL Recognized UL 60950-1

Conformity/Approvals

SIL in accordance with IEC 615080

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise emissionEN 61000-6-4
EMC requirements for noise immunityEN 61000-6-1
EMC requirements for noise immunityEN 61000-6-2
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge6 kV (Test Level 3)
Discharge in air8 kV (Test Level 3)
CommentsCriterion B

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 1 GHz
Test field strength10 V/m (Test Level 3)
Frequency Range1 GHz ... 6 GHz
Test field strength10 V/m (Test Level 3)
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input4 kV (Test Level 4 - asymmetrical)
Output2 kV (Test Level 3 - asymmetrical)
CommentsCriterion B

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Input1 kV (Test Level 2 - symmetrical)
Input2 kV (Test Level 3 - asymmetrical)
Output0.5 kV (Test Level 1 - symmetrical)
Output1 kV (Test Level 2 - asymmetrical)
CommentsCriterion B

Conducted interference

Standards/regulationsEN 61000-4-6
Input/Outputasymmetrical
Frequency Range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)

Voltage dips

Standards/regulationsEN 61000-4-11
Voltage230 V AC
Frequency50 Hz
Voltage dip70 %
Number of periods25 periods
Additional textClass 3
CommentsCriterion A
Voltage dip40 %
Number of periods10 periods
Additional textClass 3
CommentsCriterion A
Voltage dip0 %
Number of periods1 period
Additional textClass 3
CommentsCriterion B

Emitted interference

Standards/regulationsEN 61000-6-3
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Accessories

Why Proax for Phoenix Contact 2904372?

Proax is an authorized distributor of Phoenix Contact 2904372 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability